Laserfiche WebLink
Mr. James Grafton <br /> Providence Health and Services-Washington <br /> Plan Check Number: B1905-020, First Building Review <br /> June 25, 2019 <br /> d. The floor construction shall be evaluated for the additional load. Where the load paths are <br /> not sufficient to supporting the infills, supplemental framing shall be provided. <br /> e. The live loads on the infills shall be specified in the drawings. See IBC Section <br /> f. Special inspection shall be specified in the drawings as required. The required type and <br /> frequency of each special inspection shall be specified. At a minimum, inspections for cast- <br /> in-place concrete, reinforcing steel, and post-installed anchorage are anticipated; additional <br /> requirements for steel or other materials shall be specified as needed. See IBC Sections <br /> 1704.3, 1704.3.1, 1705.2, and 1705.3, and Table 1705.3. <br /> This review has been performed for general compliance with the building codes as adopted and <br /> amended by the state of Washington and the city of Everett. Corrections and comments made <br /> during the review process do not relieve the project from compliance with code and permit <br /> requirements. The designers-of-record are responsible for a complete design in accordance with <br /> the laws of the state of Washington. <br /> If you have any questions or require additional clarification, please contact us. <br /> Respectfully, <br /> Drew Martin, P.E., S.E. <br /> Associate Engineer/ Commercial Plans Examiner <br /> (425)257-8813 <br /> dmartin@everettwa.gov <br /> S:\BMartin\2019\131905-020_R1.dooc <br /> O3200 Cedar Street 0425.257.8810 /"/ everetteps@everettwa.gov <br /> Everett,WA 98201 425.257.8857 fax ��� everettwa.gov/permits <br /> Q.:7e4of4 <br />