Laserfiche WebLink
I <br /> Ms. Amanda Moore <br /> PSF Mechanical, Inc. <br /> Plan Check Number: M1908-012, First Building Review <br /> September 4, 2019 <br /> 5. The Level 2 Plan on Sheet M2.11A shows new combination fire/smoke dampers throughout the <br /> ventilation system. The required damper ratings for both fire and smoke shall be specified for <br /> all dampers. See IBC Section 717.3.2. <br /> 6. The project includes numerous piping that penetrate the walls and wall membranes, and the <br /> horizontal assemblies. The architectural drawings under Permit No. B1905-020 do not include <br /> details for sealing the penetrations in the fire and smoke barriers. Details shall be included in <br /> the mechanical drawing set to seal the penetrations. The details shall include rated assemblies <br /> and shall provide the test listing. See IBC Section 714. <br /> This review has been performed for general compliance with the building codes as adopted and <br /> amended by the state of Washington and the city of Everett. Corrections and comments made <br /> during the review process do not relieve the project from compliance with code and permit <br /> requirements. The designers-of-record are responsible for a complete design in accordance with <br /> the laws of the state of Washington. <br /> If you have any questions or require additional clarification, please contact us. <br /> Respectfully, <br /> Drew Martin, P.E., S.E. <br /> Associate Engineer/ Commercial Plans Examiner <br /> (425)257-8813 <br /> dmartin@everettwa.gov <br /> S:\BMartin\2019\M1908-012_Rtdocx <br /> O3200 Cedar Street 0425.257.8810 O everetteps@everettwa.gov <br /> Everett,WA 98201 425.257.8857 fax everettwa.gov/permits <br /> '°) <br />