Drew Martin <br /> From: Drew Martin <br /> Sent: Tuesday,November 13, 2018 2:41 PM <br /> To: 'randyh@evha.org' <br /> Subject: City of Everett Public Works:2701 12th Street (B1807-032) <br /> Randy, <br /> I've completed my review of the second resubmittal. There are still several items that have not been completely <br /> addressed by the design team. The architectural comments and Structural Comments 13 and 26a may be redlined upon <br /> confirmation and approval. Structural Comment 29 requires supplemental documentation from the EOR. <br /> Architectural <br /> 5b.The minimum insulation shall be R-9.5 continuous or R-21. <br /> 16.The following should be specified in the drawings: <br /> a.Specify demolition required to convert Main Floor restrooms to single-user restrooms. Work includes, but is <br /> not limited to: compartment walls,stud partition walls(i.e., inside men's room, outside women's room),second toilet in <br /> women's room. <br /> b. Provide interior locks for doors. <br /> 22.Specify maximum 1:20 slope for sidewalk on east side of the building. <br /> 32.This comment has not been addressed. Structural drawings have been added to the construction drawing set that <br /> were not included in the original submittal. The architectural drawings include structural information that <br /> duplicates or differs from information provided in the structural drawings. A note shall be provided on Sheet A-0 <br /> stating: "The architectural drawings include structural information that is duplicated by the structural <br /> drawings. Where discrepancies occur,the structural drawings shall control the structural work to be <br /> performed." See IBC Section 107.2.1. <br /> Structural <br /> 13. Sheet A-7 still shows both new 2x8 framing and trusses. Confirm the former should be removed from the plan. <br /> 26a.Sheet A-6 still shows the detail. Confirm detail should be removed. <br /> 29.The design for the holdown concrete anchors has not been performed per code. The design loads are the Simpson <br /> holdown allowable capacities divided by the seismic ASD multiplier of 0.7; see calculation page 17. This is not valid. The <br /> design loads shall be determined using the overstrength factor and load combinations as specified in the original <br /> comment. Based on the loads on page 16,the maximum design load is at least 15 kips; the LRFD design load shall be <br /> substantiated (i.e.,the design shall not be performed using the 15 kips stated in this comment). Alternatively,the <br /> holdown anchor may be designed using the tested ultimate strength(i.e.,failure capacity) of the holdowns as <br /> determined by the manufacturer. This alternative approach satisfies ACI 318-14 Section 17.2.3.4.3 Option <br /> (b)/(c). Documentation from the manufacturer establishing the ultimate strength shall be submitted; a soft-converstion <br /> of the allowable capacity it not valid. Supplemental calculations substantiating the anchor design shall be submitted for <br /> review. <br />