Laserfiche WebLink
The"Typical 2-Story Wall Section"(sheet A-10) and the"Shear Transfer Detail"(Sheet <br /> S-1) show different blocking at the top plate of exterior walls. Please clarify which <br /> blocking is to be used and provide specific detail for projections located in the 5 foot <br /> side yard setback. <br /> (Attic ventilation calculations may need to be modified to meet the requirement for <br /> ventilation with no openings on the east side property line.) <br /> Please prepare a response letter showing where each item in this <br /> correction letter is addressed on the plan set. <br /> All required submittals shall be of sufficient detail and contain sufficient information to ensure <br /> that the proposed structure will be constructed in compliance with all adopted codes. <br /> Sincerely, <br /> Jeff Heilman <br /> Development Technician <br /> 425-257-8976 <br /> Email: iheilman(aci.everett.wa.us <br /> S:\1Common\Clerical\]Heilman\C1508-005(10531 Washington Way).doc <br />