Laserfiche WebLink
29. Per field evaluation from the Fire Marshal's Office- Fire lanes shall be provided as required in Everett Municipal <br /> Code 46.44. Fire lanes shall be identified by red curbs with white stenciling stating"NO PARKING-FIRE LANE" <br /> and vertical signs stating "NO-PARKING--FIRE LANE TOW AWAY ZONE--EMC-46:28:130":- Location shall be <br /> approved by the Fire Code Official. <br /> 30. Premises shall be clearly identified by the correct address at the street entry. Buildings shall be clearly identified <br /> so as to be visible and legible from the access road. Individual apartments and suites,where applicable, shall be <br /> clearly and legibly identified from the access road. See EMC 16.03, Section 505.1.1 (Address Posting Policy). 10- <br /> inch to 12-inch numbers shall be placed on the building. <br /> 31. Fire hydrants locations as planned are acceptable. <br /> 32. Fire flow for this project is 2,000 gpm. <br /> 33. A portable fire extinguisher with a minimum U.L. rating of 2-A:10-B:C shall be provided within 75 feet of travel on <br /> all floors of each building during construction and prior to occupancy. <br /> 34. An approved automatic fire detection system shall be provided as required by City Ordinance No. 3021-07, <br /> Chapter 16.76, of the Everett Municipal Code. <br /> Plans for such system shall be submitted to the Fire Code Official for review and approval prior to installation. <br /> Submittal shall include cut sheets of all equipment intended for use. Appropriate trip tests, witnessed by a Fire <br /> Department Inspector, shall be performed, along with a certificate of completion, prior to final acceptance of the <br /> system. <br /> Fire alarm systems shall be installed according to NFPA Chapter 72, 2010 Edition. Installation of fire alarm <br /> components, including basic wiring, may not commence before plans are approved by the Fire Department Plan <br /> Reviewer. Fire alarm drawings must be professionally rendered, in sufficient detail, and must be internally <br /> consistent. Riser diagrams must match installation plans and load calculations. Components must be listed and <br /> approved for use together. Changes to plans must include new drawings and calculations and must be approved <br /> by the Fire Department Plan Reviewer prior to installation. Fire alarm installation is subject to field inspection by a <br /> Fire Department Inspector. An approved set of plans and the Engineering & Public Services Department electrical <br /> permit must be present for any installation inspection. <br /> • Fire alarm systems shall be installed under permit of the City of Everett Engineering& Public Services <br /> Department. Electrical inspections and approval are required prior to calling for acceptance tests. Call (425)257- <br /> 8810 for permit information. The absence of working phone lines for the alarm system will be cause for postponing <br /> Fire Department inspection and testing and shall result in denial of occupancy. <br /> A copy of NFPA 72 Record of Completion form must be filled out prior to final occupancy(NFPA 72, 2010 Edition, <br /> Chapter 10, page 114). <br /> Call for design requirements per Authority Having Jurisdiction. <br /> Automatic smoke detection is required. <br /> 35. An approved automatic suppression system shall be provided as required by City Ordinance No. 3021-07, Chapter <br /> 16.76, of the Everett Municipal Code. The system must include a mechanical water gong bell. Plans for any such <br /> system shall be submitted to the Engineering & Public Services Department for examination and approval. Such <br /> plans shall include plans for the underground mains that will supply the sprinkler system. <br /> The type of sprinkler to be installed will be determined by the Building Official. It may be an NFPA 13, NFPA 13R, <br /> or NFPA 13D system depending upon several factors. Sprinkler installation shall not begin without an approved <br /> and stamped set of plans from the Engineering & Public Services Department. The Fire Department will also <br /> review the plans and shall field inspect the installation based only on approved plans that must be on site. <br /> Changes to plans must be approved by both the Engineering & Public Services and Fire Departments. <br /> / <br />