Laserfiche WebLink
combinations; LRFD-based loads shall be used to verify the anchorage design, not soft conversions. See <br /> IBC Sections 1613.1 and 1901.2. <br /> j. The design of the HDU8 anchor requires a minimum embedment of 11";the calculations states a footing <br /> thickness of 14". The footings are only 12" thick per Sheet S2.O. The design shall be revised. The <br /> minimum concrete cover of 3" per ACI 318-14 shall be maintained. Verify the minimum clearance <br /> required by the manufacturer for this product. <br /> k. The following comments shall be addressed for the Hold-Down table in Detail 12/S3.O: <br /> i. The design strengths shall be defined as ASD or LRFD. Note that the design values in the Shear <br /> Wall Schedule of Detail 11/S3.0 should be similarly defined. <br /> ii. The embedment lengths shall be revised for the HDU8. <br /> iii. Calculation page T-8 is based on the Hilti HIT-RE 500 system. Note 6 specifies the HILTI HIT-HY <br /> 200 system. The note shall be revised. Note that holdowns used for other locations are based <br /> on the HILTI HIT-HY 200 system. If all anchors are changed to the new system, revised <br /> calculations for all holdowns shall be submitted for review. <br /> I. The following comments shall be addressed for the lid joists: <br /> i. Revised calculations for the gravity framing should be submitted for review as needed based on <br /> comments above for the gravity loading. Framing shall be designed for concentrated gravity <br /> loads where they occur. <br /> ii. If openings larger than 12" (i.e.,joist spacing minus the width of the joist top chords) are <br /> required, supplemental framing and details for the openings shall be provided. <br /> iii. Additional calculations shall be provided for continuous joists supporting transfer loads from <br /> adjacent discontinuous joists at openings. <br /> iv. Calculations substantiating the design of wall framing supporting concentrated loading from <br /> above shall be submitted for review. <br /> 1DrewCELEBRATING47, <br /> 125 <br /> Martin, P.E.,S.E. <br /> Associate Engineer—Commercial Plans Examiner 1 Permit Services <br /> YEARS 425.257.8813 1 3200 Cedar Street, 2nd Floor, Everett,WA 98201 <br /> A story worth telling everettwa.gov/permits 1 Facebook 1 Twitter <br /> Note:Emails and attachments sent to and from the City of Everett are public records and may be subject to disclosure pursuant to the Public <br /> Records Act. <br /> From: Nadia Azarova <nadia@craftarchitects.com> <br /> Sent:Thursday, November 8, 2018 1:18 PM <br /> To: Drew Martin<dmartin@everettwa.gov> <br /> Subject: RE:City of Everett Public Works: 3315 Seaway Blvd (B18O8-012) <br /> Drew, <br /> I forwarded your email to Craig. Please email us right away for any other items that need further attention. We greatly <br /> appreciate this expedited way of communication. <br /> Thank you, <br /> Nadia Azarova <br /> NELSON <br /> formerly Craft Architects <br /> p:206.720.7001 <br /> \. <br /> 8) <br />