62ySpecify the Whole house Ventilation System you will use to comply with section M1507.3 IRC. <br /> Each dwelling unit shall be equipped with a ventilation system complying with section <br /> M1507.3,4, M1507.3.5, M1507.3.6 or M1507.3.7. Show the entire code section of the whole <br /> house ventilatioi stem chosen •1 the •la Is •• . •l reference the code section. <br /> 34. he plans as drawn do not meet the prescriptive requirements for lateral bracing. All braced <br /> wall lines and braced wall panels shall be clearly identified on the plans. <br /> Provide a complete braced/shear wall plan and reference a braced /shear wall schedule at each <br /> braced/shear wall location. (R602.10). Braced/Shear wall schedule to include anchor bolts, <br /> holdowns, studs and spacing, sheathing and nailing. (T.602.3(1)), (R403.1.6, 403.1.6.1). <br /> Address'alternate braced wall panels' per (R602.10.6). Coordinate post locations with <br /> holdowns on foundation plan. (R602.11.1). Show and identify each required holdown on <br /> foundation plan. Provide Wood-Stud wall Engineering Analysis for bearing walls Over 10 Feet <br /> High. <br /> 4630 how elevation, (relative to the site) as determined by the Height calculations, on the Elevation <br /> Drawings. Show the"Base Elevation", Finished 1st Floor, Top Plate Finished 2nd Floor, Top <br /> P te, Proposed elevation at top of ridge and the Allowed Elevation above the Base Elevation. <br /> . Provide and identifyall required safetyglazingR308 . <br /> q ( ) <br /> how location of all posts supporting point loads from above. <br /> If you have any questions, please email or call me at (425) 257-8976. Upon submittal of the <br /> drawings, your application will be given priority and plan reviews will recommence. All required <br /> submittals shall be sufficient detail and contain sufficient information to ensure that the proposed <br /> structure will be constructed in compliance with all adopted codes. <br /> Please prepare a response letter showing where each item in this correction <br /> letter is addressed on the plan set. <br /> Sincerely, <br /> Jeff Heilman <br /> Development Technician <br /> City of Everett Public Works Department <br /> 3200 Cedar St, Everett, WA 98201 <br /> Office: 425-257-8810 I Direct: 425-257-8976 <br /> Email: JHeilmanPeverettwa,gov <br /> u <br /> PUBLIC WORKS <br /> The Permit Services Counter is located on the 2"d Floor. <br /> Hours of Operation: Monday-Friday 7:30am -12:00pm and 1:00pm-4:OOpm. <br /> All emails, and attachments, sent to and from City of Everett are Public <br /> Records and may be subject to public disclosure pursuant to RCW 42.56. <br /> ` P_4 44, 44 of <br /> CITY OF EVERETT • 3200 Cedar Street • Everett, WA 98201 • (425) 257-8810 • Fax(425) 257-8857 <br />