Mr. Brad Rzechula <br /> Leading Edge Construction, LLC <br /> Plan Check Number: B1803-029, First Review <br /> May 4, 2018 <br /> 30.The structure has a Type 4 Horizontal Structural Irregularity per ASCE 7-10 Table 12.3-1. The <br /> design forces of the diaphragm connections to shearwalls and collectors, collectors, and <br /> collector connections to shear walls shall be increased per Section 12.3.3.4. Design forces shall <br /> also comply with Section 12.10.2.1. Calculations substantiating the design shall be submitted <br /> for review. See IBC Sections 1604.1 and 1613.1. <br /> 31. Continuing with the previous comment, the Upper Level diaphragm does not directly connect <br /> to the shear walls on Grid 3 per Sheet S-5.0. Note that additional openings occur in the floor <br /> along the collectors per Sheet 5-of-10 that do not appear on Sheet S-5.0 and further reduce <br /> the connection capacity. Calculations substantiating the load path shall be submitted for <br /> review. See IBC Section 1604.4. <br /> 32. Section 3/S-6.0 indicates that the prefabricated roof trusses will align with the shear walls <br /> below and provide the horizontal load path between the roof diaphragm and walls. Design <br /> criteria for the trusses should be included in the"Design Loads" section of the General Notes <br /> on Sheet SS-1.0. See IBC Sections 107.2.1, 1603.1.8, and 1604.4, and ASCE 7-10 Section 1.4. <br /> 33. Holdown Mark"2"on Sheet S-5.0 specifies connections to the W14 beams at the Main Level <br /> floor using 5/8-inch bolts through the top flanges. Calculations evaluating the concentrate <br /> loads on the flanges per AISC 360-10 Section 310. Stiffener plates shall be provided as <br /> required. See other requirements requiring amplification of holdown forces per ASCE 7-10 <br /> Section 12.3.3.3. See IBC Sections 1604.2, 1613.1, and 2205.1. <br /> This review has been performed for general compliance with the building codes as adopted and <br /> amended by the state of Washington and the city of Everett. Corrections and comments made <br /> during the review process do not relieve the project from compliance with code and permit <br /> requirements. The designers-of-record are responsible for a complete design in accordance with <br /> the laws of the state of Washington. <br /> If you have any questions or require additional clarification, please contact us. <br /> Respectfully, <br /> Drew Martin, P.E., S.E. <br /> Associate Engineer / Plans Examiner <br /> (425)257-8813 <br /> dmartin@everettwa.gov <br /> S:\BMartin\2018\61803-029.docx <br /> 8of <br /> CITY OF EVERETT • 3200 Cedar Street • Everett,WA 98201 • (425) 257-8810 • Fax(425) 257-8857 <br />