Laserfiche WebLink
li'age <br /> 22. Page 38 of the structural calculations appears to provide line loads for earthquake loading at <br /> "Level 2 of 3". See IBC Sections 1604.1, 1604.4, and 1613.1. The following additional <br /> information shall be submitted for review: <br /> Specify the procedure being used for the design (i.e., Equivalent Lateral Force or <br /> Modal). See ASCE 7-10 Sections 12.8 and 12.9. Note that the following comments <br /> presume the ELFP has been used. If the modal procedure has been used, provide <br /> documentation substantiating the lateral forces as required by Section 12.9. <br /> Response; <br /> The Seismic procedure used was per ASCE 7-10 Equivalent Lateral Force Procedure <br /> Lize Provide calculations substantiating the seismic weight tributary to each level. <br /> Response; <br /> The requested detailed calculations are attached per your request. Please see <br /> Woodworks tabulations printout on pages 20-23 and detailed load tabulations. <br /> ,Provide calculations substantiating the vertical distribution of the seismic base shear to <br /> each diaphragm level including the roof. <br /> Response; <br /> The requested detailed calculations are attached per your request Please see <br /> Woodworks tabulations printout on pages 20-23 and detailed load tabulations. <br /> 0.4-ie Foundation and Main Level floor framing plans on Sheets S-3.0 and S-4.0, respectively, <br /> and Section 7/S4.1, indicate shear walls occur at the first story on Grid B. The shear walls <br /> are not specified on the plans. <br /> Response; <br /> The detail under question was erroneous and has been corrected <br /> The plans appear to have a discrepancy on the presence of a wall at Grid B/3. The <br /> drawings should be reviewed and revised as needed. See IBC Sections 107.2.1 and 1603.1. <br /> Response; <br /> The requested drafting correction has been made for the redundant column <br /> G[ 44LRY (1 .4.-1- 6'Get'•®•gi ow 4'LEI 0. <br /> he design includes wood portal frames at the first story on Grid A.5 per Sheet S-4.0. <br /> Apr <br /> Calculations substantiating the design of the portal frames shall be submitted for review. <br /> Note that the design does not qualify for use of the prescriptive design procedures of the <br /> IRC or IBC Section 2308 per Table 2308.2.1. The calculations shall substantiating the <br /> capacity of the design to resist the governing design lateral forces per ASCE 7-10. At the <br /> EOR's option, a proprietary system may use in the design; an ESR shall be submitted to <br /> substantiate the design. The documentation shall establish the response modification factor <br /> appropriate to the system per Section 12.2.1; the most stringent value shall be used for the <br /> entire building per Section 12.2.3.1. See IBC Sections 1604.1, 1604.4, 1609.1, and 1613.1. <br /> Response; <br /> Attached you will find supplemental APA information for the portal frame per your request <br /> -Orr 7/5-2.0: V rr� 3d 3S0 a / tc r f IVIt Oils rABt.E I2E) <br /> 817 Metcalf Street, Suite 207 Office: 360.855.2333 Ext. 207 <br /> Sedro-Woolley,WA 98284 Cell: 360.982.0928 <br />