h <br /> • <br /> Page 9 of 9 <br /> .The shear walls on Grid A.1 are discontinuous to the foundation, resulting in a Type 4 <br /> Horizontal Structural Irregularity per ASCE 7-10 Table 12.3-1. Furthermore, the walls are <br /> not consistent between the second and third stories per the plans on Sheets S-5.0 and S- <br /> 6.0. All structural elements supporting the discontinuous walls at both levels shall be <br /> designed considering the over-strength factor per Section 12.3.3.3. Structural elements <br /> required to meet this loading criteria include but are not limited to: beams including bearing <br /> and mechanical shear connections, columns and posts, foundations, and connections <br /> between elements including those resisting uplift. Note that the connections per Detail 1/S- <br /> 4.0 do not appear structural adequate to transfer the required uplift forces. The design <br /> shall include the seismic load combinations per Section 12.4.3.2. The design shall provide a <br /> complete load path to the foundation. See IBC Sections 1604.2, 1604.4, and 1613.1. <br /> Response;Design for the irregularities for the structural system components was <br /> performed. Calculations are attached for your review. <br /> .The structure has a Type 4 Horizontal Structural Irregularity per ASCE 7-10 Table 12.3-1. <br /> The design forces of the diaphragm connections to Shearwalls and collectors, collectors, and <br /> collector connections to shear walls shall be increased per Section 12.3.3.4. Design forces <br /> shall also comply with Section 12.10.2.1. Calculations substantiating the design shall be <br /> submitted for review. See IBC Sections 1604.1 and 1613.1. <br /> Response:Design for the irregularities and forces you requested was performed and <br /> supplemental calculations are attached per your request <br /> ontinuing with the previous comment, the Upper Level diaphragm does not directly <br /> connect to the shear walls on Grid 3 per Sheet S-5.0. Note that additional openings occur in <br /> the floor along the collectors per Sheet 5-of-10 that do not appear on Sheet S-5.0 and <br /> further reduce the connection capacity. Calculations substantiating the load path shall be <br /> submitted for review. See IBC Section 1604.4. <br /> Response;Design for the irregularities and forces you requested was performed and <br /> supplemental calculations are attached per your request <br /> . Section 3/S-6.0 indicates that the prefabricated roof trusses will align with the shear walls <br /> below and provide the horizontal load path between the roof diaphragm and walls. Design <br /> criteria for the trusses should be included in the"Design Loads" section of the General <br /> Notes on Sheet SS-1.0. See IBC Sections 107.2.1, 1603.1.8, and 1604.4, and ASCE 7-10 <br /> Section 1.4. <br /> Response:The design axial load was provided to the Truss Mfg. in the instruction on Sheet <br /> S6 note 4.E as 3500 lbs. Further load criteria is provided in the general notes. <br /> "Hold-down Mark"2"on Sheet S-5.0 specifies connections to the W14 beams at the Main <br /> Level floor using 5/8-inch bolts through the top flanges. Calculations evaluating the <br /> concentrate loads on the flanges per AISC 360-10 Section 310. Stiffener plates shall be <br /> provided as required. See other requirements requiring amplification of hold-down forces <br /> per ASCE 7-10 Section 12.3.3.3. See IBC Sections 1604.2, 1613.1, and 2205.1. <br /> Response; <br /> See attached requested supplemental information and calculations <br /> 817 Metcalf Street, Suite 207 Office: 360.855.2333 Ext.207 <br /> Sedro-Woolley,WA 98284 Cell: 360.982.0928 <br />