Laserfiche WebLink
Fault Current Calculations <br /> Project: James Monroe ES-Portables 2017 Date: 10/16/2017 <br /> Job# 17-159 By: Jeff Hoover, PE <br /> Fault on Load Side of Transformer with Infinite Short Circuit Current on Primary Available. AFC <br /> Node# kVA L-L Voltage 0 %Z Short Circuit Current <br /> Utility XFMR 100 208 25,169 <br /> Fault Current at the End of a Run of Cable. <br /> Short Circuit Current Length Conductors Conductor Raceway Short Circuit Current at End of Cable <br /> Node# at Beginning of Run of Run L-L Voltage Per Phase 0 Type Type Wire Size Run <br /> DP-PORT 25,169 20 208 3 1 Copper iktV4 Non-Metallic =,7<350 kcmil €7 24,307 <br /> Panel PORT1 24,307 140 208 1 1 Aluminum Igo Non-Metallic v #3/0 , 8,694 <br />