Laserfiche WebLink
CITY OF EVERETT <br /> Public Works Department <br /> November 20, 2018 <br /> Vladimir Pyatak <br /> pyanvladi@hotmail.com • <br /> 3120 W Mukilteo Blvd <br /> Everett, WA 98203 <br /> Plan Check No: C1808-007 <br /> RE: Building Permit Review Letter <br /> Dear Mr. Pyatak, <br /> In response to the application for a building permit, the plans have been examined and you are <br /> advised that revisions may be necessary before a permit can be issued. Please review and <br /> respond to the comments below. <br /> NON STRUCTURAL <br /> Construction <br /> 1. The location of the adjacent grade should be shown on the elevations on Sheet A2. Section <br /> R106.1.1 <br /> 2. Rim Joists, blocking and interior wall support within floor/ceiling assemblies should be <br /> shown on Section A/A2. Section R106.1.1 <br /> 3. The posts for the isolated spread footings shown on the foundation plan on Sheet A3 <br /> should be shown supporting the beams. Section R106.1.1 <br /> 4. Some of the STHD 14 holddowns are located at foundation vents. The vents should not <br /> be located closer than a 1/2 inch to any holddown per Simpson installation requirements. <br /> 5. The anchor bolts in detail 6/A3 should be revised to minimum 5/8" diameter per the <br /> shearwall schedule notes on Sheet A8. <br /> 6. The one-hour fire-resistive separation between dwelling units should be delineated on the <br /> plans. The walls must continue up to the underside of the roof sheathing of the storage <br /> sheds on each side of the wall (if that is the locatie of the separation). A detail/section <br /> should be provided. Section R302.3 <br /> 3200 Cedar Street ( 425.257.8810 0 tlee@everettwa.gov <br /> �j Everett,WA 98201 425.257.8857 fax everettwa.gov <br />