2. The electric water tank should be shown on minimum R-10 incompressible insulation and <br /> strapped at the top and bottom 1/3 of the tank to prevent overturning. Section R403.5.5 <br /> STRUCTURAL <br /> 1. On Sheet A8, the shear wall schedule contains nailing with nail spacing closer than 4"oc. <br /> Please provide a schedule of special inspections for such walls per IBC 1705.11.1. <br /> 2. On Detail 7/A3, it appears that the retaining wall schedule has heights greater than 4'-0" <br /> that are required to be designed by a designer (architect/engineer) licensed by the state <br /> of Washington. Please provide design calculations for such walls as they occur on this <br /> project. <br /> 3. Detail 7/A3 appears to specify slab-on-grade at the crawl space level. Detail 8/A3 does <br /> not indicate a surrounding slab-on-grade. Please clarify where the slab-on-grade <br /> terminates at the crawl space level on the plans. <br /> 4. The raised shearwall on the foundation plan should be shown to be a minimum of 24" <br /> wide as shown in Detail 1/A3. The width of the wall on plan as shown on Sheet A3 is 1'- <br /> 10 1/2"and only 1'-0"on Sheet A4. Please address the geometry discrepancy and provide <br /> structural calculations verifying the wall's capacity for which condition is to be constructed. <br /> 5. Please indicate in further detail the guardrail connections to the exterior deck and <br /> stairways. For instance on Detail 15/A6, it is unclear how the lag screws are to be located <br /> into the framing. Please indicate details for these items to be shown on the stairways, as <br /> they do not appear to be on the plans. Also, please provide engineering calculations for <br /> these post-frame assemblies subjected to applicable loads in Section R301.5. <br /> 6. It appears that Detail 15/A6 is referenced as Detail 15/A5 on plan sheet A4. Please revise <br /> callouts for clarity. <br /> 7. On Detail 15/A6, the notched condition of the proposed 6x6 post reduces the capacity of <br /> the post for shear and flexural strength. Please provide design calculations verifying the <br /> post's adequacy when subjected to the loading requirements in IRC Table R 301.5. <br /> 8. On Sheets A8 and A9, the floor-sheathing schedule appears to have conflicting nailing <br /> requirements. Please clarify. <br /> 9. From Sheet A6, it appears that engineered trusses are being proposed for the roof <br /> framing. Please indicate the design loads, including wind uplift (where occurs) for such <br /> trusses as well as indicate that these trusses are to be deferred submittals on the plans. <br /> Section R106.1 <br /> 10. On Sheet A8 and A9, framing grades for timber appear to conflict with each other. Please <br /> clarify. For instance, joists and rafters are to b- & -L #2 on Sheet A9, but are indicated <br /> as HF #2 on Sheet A8. <br /> LI <br /> 0 3200 Cedar Street 0 425.257.8810tlee@everettwa.gov <br /> Everett,WA 98201 425.257.8857 fax \Y everettwa.gov <br />