. . <br /> , <br /> DESIGN BUILD NOTES KEY NOTES 0 GENERAL NOTES <br /> PROJECT TO BE ELECTRICAL AND MECHANICAL DESIGN-BUILD. NEW LIGHTING SHALL MEET C405.2.1 OCCUPANCY SENSORS. OCCUPANCY SENSORS SHALL BE INSTALLED IN 2. STEPPED DIMMING USING MULTI-LEVEL SWITCHING AND DAYLIGHT-SENSING 1. START OF CEILING GRID. 1. THE REFLECTED CEILING PLAN OR FINISH SCHEDULE(A6.2) INDICATES THE <br /> THE FOLLOWING MINIMUM REQUIREMENTS: ALL CLASSROOMS, CONFERENCE/ MEETING ROOMS, EMPLOYEE LUNCH AND CONTROLS THAT ARE CAPABLE OF REDUCING LIGHTING POWER AUTOMATICALLY. THE LOCATION OF CEILING HEIGHTS, LIGHT FIXTURES,SWITCH LOCATIONS,AND Nelco Architectare Inc. <br /> A. IBC 1008,1 - ILLUMINATION REQUIREMENT BREAK ROOMS, PRIVATE OFFICES, RESTROOMS, WAREHOUSE SPACES, STORAGE SYSTEM SHALL PROVIDE A MINIMUM OF TWO CONTROL CHANNELS PER ZONE AND BE 2. CENTER CEILING GRID IN ROOM. ASSOCIATEC� ITEMS. REFER TO ENGINEERING DRAWINGS FOR CIRCUITING, � <br /> 1. THE MEANS OF EGRESS, INCLUDING THE EXITDISCHARGE, SHALL BE ROOMS AND JANITORIAL CLOSETS, AND OTHER SPACES 300 SQUARE FEET(28 INSTALLED IN A MANNER SUCH THAT AT LEAST ONE CONTROL STEP IS BETWEEN 50 WIRING LAYOUT, AND ADDITIONAL INFORMATION. ALL MEP-FP DEVICE <br /> ILLUMINATED AT ALL TIMES THE BUILDING SPACE SERVED BY THE M2) OR LESS ENCLOSED BY FLOOR-TO-CEILING HEIGHT PARTITIONS. THESE PERCENT AND 70 PERCENT OF DESIGN LIGHTING POWER AND ANOTHER CONTROL STEP LOCATIONS NOT SHOWN ON DRAWINGS,OR IN CONFLICT WITH MEP/FP <br /> MEANS OF EGRESS IS OCCUPIED. AUTOMATIC CONTROL DEVICES SHALL BE INSTALLED TO AUTOMATICALLY TURN IS NO GREATER THAN 35 PERCENT OF DESIGN POWER, AND THE 5YSTEM IS CAPABLE DRAWINGS, ARE TO BE COORDINATED WITH ARCHITECT PRIOR TO <br /> B. IBC 1008.2.1 - ILLUMINATION LEVEL OFF LIGHTS WITHIN 30 MINUTES OF ALL OCCUPANTS LEAVING THE SPACE,AND OF AUTOMATICALLY TURNING THE SYSTEM OFF, IN5TALLATION. IN THE EVENT OF DISCREPANCIES BEfWEEN THE ARCHITECT'S <br /> 1. THE MEANS OF EGRESS ILLUMINATION LEVEL SHALL NOT BE LESS THAN 1 SHALL EITHER BE MANUAL ON OR SHALL BE CONTROLLED TO AUTOMATICALLY REFLECTED CEILING PLAN AND THE ENGINEERS' PLANS, IMMEDIATELY NOTIFY 1200 Fifth Ave. <br /> FOOT-CANDLE (11 LUX) AT THE FLOOR LEVEL. TURN THE LIGHTING ON TO NOT MORE THAN 50 PERCENT POWER. C408.2.3 FUNCTIONAL TESTING. TESTING SHALL ENSURE THAT CONTROL HARDWARE AND THE ARCHITECT IN WRITING BEFORE ORDERING MATERIALS OR PROCEEDING Suite 1300 <br /> C. IBC 1008.3 - ILLUMINATION EMERGENCY POWER SOFfWARE ARE CALIBRATED, ADJUSTED, PROGRAMMED AND IN PROPER WORKING WITH THE WORK. S2attI2, WA 98101 <br /> 1. THE POWER SUPPLY FOR MEANS OF EGRESS ILLUMINATION SHALL C405.2.4 DAYLIGHT ZONE CONTROL. DAYLIGHT ZONES SHALL BE DESIGNED SUCH CONDITION IN ACCORDANCE WITH THE CONSTRUCTION DOCUMENTS AND MANUFACTURER'S 2. FOLLOWING COMPLETION OF THE ACOUSTICAL CEILING INSTALLATION,ALL phone: (206)408-8500 <br /> NORMALLY BE PROVIDED BY THE PREMISE'S ELECTRIC SUPPLY. THAT LIGHTS IN THE DAYLIGHT ZONE ARE CONTROLLED INDEPENDENTLY OF INSTALLATION INSTRUCTIONS. JOINTS AND GRID SHALL BE STRAIGHT, TRUE TO LINE,WITH EXPOSED <br /> 1.1 LOCATIONS INCLUDE: DEDICATED EGRESS ROUTES IN LARGER ROOMS GENERAL AREA LIGHTING AND ARE CONTROLLED IN ACCORDANCE WITH NEW HVAC SOLUTION SHALL MEET THE FOLLOWING MINIMUM REQUIREMENT: SURFACES FLUSH AND LEVEL. DIRTY OR DISCOLORED SURFACES OF TILE ARE WWW.NELSONWORLbWIDE.COM <br /> OR SPACES, PUBLIC OR COMMON EGRESS ELEMENTS, ESSENTIAL SECTION C405.2.2.3.2. EACH DAYLIGHT CONTROL ZONE SHALL NOT EXCEED A. NEW MECHANICAL ELEMENTS, INCLUDING BUT NOT LIMITED TO PACKAGED UNITS, TO BE CLEANED OR REPLACED, AND LEFT FREE OF DEFECTS. AFfER 30 DAYS <br /> PORTIONS OF THE INTERIOR EGRESS SYSTEM, INTERIOR EXIT 2,500 SQUARE FEET (232 M2). CONTIGUOUS DAYLIGHT ZONES ADJACENT TO CONTROLS, DAMPERS, DUCTING, COMMISSIONING; TO FULLY COMPLY WITH THE FROM SUBSTANTIAL COMPLETION, IN5PECT THE WORK AND ADJUST TILE NOT <br /> DISCHARGE ELEMENTS, AND EXTERIOR PORTIONS OF THE EXIT VERTICAL FENESTRATION ARE ALLOWED TO BE CONTROLLED BY A SINGLE PROVISIONS OF WSEC SECTION C403. IN ALIGNMENT WITH OTHER CEILING TILES AND REPLACE MISSING OR <br /> DISCHARGE, INCLUDING INTERIOR EXIT STAIRWAYS&RAMPS. CONTROLLING DEVICE PROVIDED THAT THEY DO NOT INCLUDE ZONES FACING B. VENTILATION REQUIREMENTS FOR RESTROOMS PER WASHINGTON STATE DAMAGED UNITS. <br /> 2. PER IBC 1008.3.3, IN THE EVENT OF POWER SUPPLY FAILURE,AN MORE THAN TWO ADJACENT CARDINAL ORIENTATIONS(I.E.,NORTH, EAST, MECHANICAL CODE (WAC 51-52) 3, WITHIN A ROOM OR AREA, THE CONTRACTOR SHALL ESTABLISH A SINGLE <br /> EMERGENCY ELECTRICAL SYSTEM SHALL AUTOMATICALLY ILLUMINATE THE SOUTH, WEST). THE PRIMARY DAYLIGHT ZONE SHALL BE CONTROLLED C, ALL OCCUPIED SPACES SHALL BE VENTILATED BY MECHANICAL MEANS IN FLOOR ELEVATION THAT IS TO BE USED AS THE ORIGIN FOR ALL CEILING <br /> FOLLOWING AREAS: ELECTRICAL EQUIPMENT ROOMS, FIRE COMMAND CENTERS, SEPARATELY FROM THE SECONDARY DAYLIGHT ZONE. DAYLIGHT ZONES UNDER ACCORDANCE WITH SECTION 403 IN THE 2015 INTERNATIONAL MECHANICAL CODE HEIGHTS ABOVE FINISHED FLOOR. <br /> FIRE PUMP ROOMS, GENERATOR ROMS, PUBLIC RESTROOMS WITH AN AREA SKYLIGHTS MORE THAN 15 FEET(4572 MM) FROM THE PERIMETER SHALL BE THE VENTILATION SYSTEM SERVING THE SPACE SHALL BE DESIGNED TO PROVIDE 4. VERIFY FIELD CONDITIONS AND LOCATIONS OF ALL MEPJFP AND STRUCTURAL <br /> GREATER THAN 300 SF. DURATION OF EMERGENCY POWER SHALL BE PER CONTROLLED SEPARATELY FROM DAYLIGHT ZONES ADJACENT TO VERTICAL VENTILATION OVER AND ABOVE THAT REQUIRED BY TABLE 403.3.1.1 IN ACCORDANCE ELEMENTS. CONTRACTOR TO COORDINATE THE WORK OF ALL TRADES <br /> 1008.3.4: NOT LESS THAN 90 MINUTES AND SHALL CONSIST OF STORAGE FENESTRATION. WITH ACCEPTED ENGINEERING PRACTICE. NECESSARY TO MAINTAIN THE FINISHED CEILING HEIGHTS INDICATED. <br /> BATTERIES, UNIT EQUIPMENT OR AN ON-SITE GENERATOR. ILLUMINATION LEVEL CONTROL SHALL: NEW EXIT SIGNAGE SHALL MEET THE FOLLOWING MINIMUM REQUIREMENT5: INSTALL DUCTWORK TIGHT TO UNDERSIDE OF BEAMS. WITH A SMALL SPACE <br /> UNDER EMERGENCY POWER PER 1008.3.5: INITIAL ILLUMINATION NOT LESS 1. CONTROL ONLY LUMINAIRES WITHIN THE DAYLIT AREA. A. ALL REQUIRED EXIT SIGNS SHALL HAVE LETTERS SIX INCHES HIGH MINIMUM AND TO AVOID VIBRATION. INSTALLATION AND/OR ALTERATION OF DUCTWORK, <br /> THAN1 FC, MINIMUM AT ANY POINT OF 0.1 FC MEASURED ALONG THE PATH OF 2. INCORPORATE TIME-DELAY CIRCUITS TO PREVENT CYCLING OF LIGHT SHALL CONFORM WITH ALL APPLICABLE CODES. PIPING OR OTHER EQUIPMENT THAT WILL REQUIRE FASCIAS,SOFFITS AND <br /> EGRESS AT FLOOR LEVEL. LEVEL CHANGES OF LESS THAN THREE MINUTES. THE BUILDING IS FULLY SPRINK�ERED. THE FIRE PROTECTION CONTRACTOR SHALL PROVIDE OTHER TRANSITIONS IN CEILING HEIGHT SHALL BE REVIEWED WITH THE <br /> 3. EACH ROOM SHALL COMPLY WITH THE PROVISIONS OF C405.2 INTERIOR EXCEPTION: DAYLIGHT ZONES ENCLOSED BY WALLS OR CEILING HEIGHT FIRE PROTECTION DRAWINGS AS REQUIRED BY THE GOVERNING AUTHORITY.THE FIRE ARCHITECT PRIOR TG PROc;EEDING. CONTRACTOR TO PROVIDE COMPLETE <br /> LIGHTING CONTROLS. EACH AREA ENCLOSED BY WALLS OR FLOOR-TO-CEILING PARTITIONS AND CONTAINING TWO OR FEWER LIGHT FIXTURES ARE NOT PROTECTION CONTRACTOR SHALL SUBMIT DRAWINGS TO THE ARCHITECT FOR REVIEW COORDINATION DRAWINGS FOR THE ARCHITECT AND ENGINEER'S REVIEW. <br /> PARTITION5 SHALL HAVE AT LEAST ONE MANUAL CONTROL FOR THE LIGHTING REQUIRED TO HAVE A SEPARATE SWITCH FOR GENERAL AREA LIGHTING. PRIOR TO COMMENCING WITH THE WORK. 5. REWORK EXISTING FIRE, LIFE, SAFETY SYSTEM AS REQUIRED PER NEW WALL <br /> SERVING THAT AREA. THE REQUIRED CONTROLS SHALL BE LOCATED WITHIN THE LAYOUT AND CURRENT CODE. ENGINEERING AND INSTAIIATION BY BUILDING <br /> AREA SERVED BY THE CONTROLS OR BE A REMOTE SWITCH THAT IDENTIFIES C405.2.1 OCCUPANCY SENSORS. OCCUPANCY SENSORS SHALL BE INSTALLED IN RECOMMENDED SUB-CONTRACTOR. <br /> THE LIGHTS SERVED AND INDICATES THEIR STATUS. ALL CLASSROOMS, CONFERENCE/ MEETING ROOMS, EMPLOYEE LUNCH AND 6. PROVIDE SMOKE DETECTORS THROUGHOUT TENANT AREAS IN ACCORDANCE <br /> BREAK ROOMS. THESE CON7ROL5 DEVICES SHALL BE CAPABLE OF WITH LOCAL CODES AND MANUFACTURER'S RECOMMENDATIONS. <br /> C405.2.2.2 LIGHT REDUCTION CONTROLS. LIGHT REDUCTION CONTROLS NEED AUTOMATICALLY REDUCING THE LIGHTING POWER IN RESPONSE TO AVAILABLE 7. ALL CEILING MOUNTED DEVICES SHALL BE WHITE. <br /> NOT BE PROVIDED IN THE FOLLOWING AREAS AND SPACES: DAYLIGHT BY EITHER ONE OF THE FOLLOWING METHODS: 8. PROVIDE BLOCKING ABOVE CEILING REQUIRED FOR ALL CEILING MOUNTED <br /> 1, AREAS THAT ARE CONTROLLED BY AN OCCUPANT-SENSING DEVICE. 1. CONTINUOUS DIMMING USING DIMMING BALLASTS AND EQUIPMENT. PROVIDE ADDITIONAL SUPPORT FOR LIGHT FIXTURES AS <br /> 2. CORRIDORS, EQUIPMENT ROOMS, STOREROOMS, RESTROOMS, PUBLIC DAYLIGHT-SENSING AUTOMATIC CONTROLS THAT ARE CAPABLE OF REDUCING RECOMMENDED BY FIXTURE MANUFACTURER. <br /> LOBBIES, ELECTRICAL OR MECHANICAL ROOMS. THE POWER OF GENERAL LIGHTING IN THE DAYLITE ZONE CONTINUOUSLY TO 9. LOCATE ANY CONTROLS THAT NEED ACCESSING OVER ACOUSTICAL CEILING <br /> 3. DAYLIGHT SPACES COMPLYING WITH SECTION C405.2.2.3.2. LESS THAN 20 PERCENT OF RATED POWER AT MAXIMUM LIGHT OUTPUT. TILE AREAS. DO NOT PLACE ANY ABOVE GYPSUM BOARD CEILINGS, UNLESS <br /> APPROVED BY ARCHITECT. <br /> C405.2.2. AUTOMATIC TIME SWITCH CONTROL DEVICES. AUTOMATIC TIME 10. PROVIDE CEILING ACCESS REQUIRED FOR EQUIPMENT AND SYSTEM � <br /> SWITCH CONTROLS NEED NOT BE IN SPACES CONTROLLED BY OCCUPANCY MAINTENANCE. MATCH ADJACENT CEIIING FINISH U.N.O. SYSTEMS AND <br /> SENSORS. EQUIPMENT REQUIRING ACCESS SHALL BE LOCATED AT ACCESSIBLE CEILINGS- � '" <br /> ACCESS PANELS NOT SHOWN ON DRAWINGS SHALL NOT BE INSTALLED IN f; <br /> GYPSUM BOARD CEILINGS WITHOUT PRIOR APPROVAL. <br /> �� , <br /> 11. ALL ACCESS PANELS IN GYPSUM BOARD CEILINGS SHALL BE FRAMELESS; <br /> LOCATIONS SHALL BE COORDINATED WITH ARCHITECf. GROUP DEVICES TO P A N A T T � N I� <br /> - - MINIMIZE THE NUMBER AND SIZE OF ACCESS PANELS. <br /> 12. ALL CONDUITS, BOXES, DUCTS, HVAC UNITS, PIPES, ETC., SHALL BE INSTALLED pANATTONI <br /> AS HIGH AS POSSIBLE, NOT LOWER THAN 8"ABOVE LINE OF HIGHEST <br /> FINISHED CEILING. <br /> 3�'O�� 3�'O�� 13. THERE SHALL BE NO COMBUSTIBLE MATERIALS IN THE PLENUM SPACE. DEVELOPM ENT <br /> 14. WHEN MULTIPLE SWITCHES OCCUR IN CLOSE PROXIMITY GANG UNDER SINGLE COM PANY, LLC <br /> J� � � SWITCH PLATE. <br /> �� 15. FURNISH AND INSTALL NEW THERMOSTATS AS REQUIRED. INSTALL CLOSE TO g00 SW 16TH STREET SUITE 330 <br /> DOOR OPENINGS, DO NOT INSTALL IN CENTER OF WALL. ARCHITECT AND r <br /> . , . i � � CLIENT TO APPROVE ALL LOCATIONS. RENTON, WA, 98057 <br /> ,EXI EXI 16. ALL LIGHTS TO BE CONTROL�ED BY MOTION SENSOR. PROVIDE OVERRIDE <br /> � SWITCH AT ALL CONFERENCE ROOMS <br /> � , 17. ALL LAMPS SHALL BE IDENTICAL FROM ONE MANUFACTURER IN SAME GLACIER PEAK - <br /> W � . 10 TEMPERATURE, UON. <br /> � �� 15. IN EXISTING ALTERED SPACE REPAIR AND OR REPLACE COMPONENTS <br /> G <br /> REAT LITTLE BOX <br /> ' � .. � +9-0 , / <br /> NECESSARY TO INSURE ALL EXISTING AND OR RELOCATED LIGHT FIXTURES <br /> ARE FUNCTIONING, INCLUDING BUT NOT LIMITED TO LAMPS, BALLASTS,AND <br /> TOILET � � �. ��� � LENSES. RELAMP ALL EXISTING AND RELOCATED FIXTURES TO REMAIN. ' <br /> �, � � �. 1os 607 RIVERSIDE ROAD <br /> �' .. � ��+8�-0�� �� �� � � CEILING NOTES EVERErr, wa 9$zoi <br /> , 1. CENTER CEILING GRID IN ROOM OR AREA IN TWO DIRECTIONS,TYPICAL UON. Description: No: Date: <br /> � � • 106 2. CENTER LIGHT FIXTURES/SPRINKLER HEAD/CEILING ELEMENT IN 24" PORTION <br /> � OF 48"CEILING TILE,TYPICAL UON. PERMIT SET 02/14/2020 <br /> . 3. LOCATE ALL LIGHT FIXTURES, SPEAKERS, LIFE-SAFETY DEVICES AND SIMILAR <br /> � CEILING ELEMENTS, ErC., IN THE CENTER OF CEILING TILE IN BOTH <br /> �� DIRECTIONS AND ALIGN WITH ADJACENT FIXTURES, DEVICES OR HEADS IN A <br /> �+ • RUN OR ROW, U.N.O. <br /> W 4, REFER TO ELEVATIONS AND SECTIONS FOR MOUNTING HEIGHTS OF WALL <br /> � SURFACE MbUNTED LIGHT FIXTURES. <br /> � �; 5. PROVIDE SEISMIC BRACING AT ALL SUSPENDED CEILING SYSTEMS. SUSPENDED <br /> � MEN�S TOILET � CEILING AND BRACING SHALL MEET THE MINIMUM REQUIREMENTS OF CISCA <br /> - OFFI E AND ASCE 7-10 SECTION 13.5.6. AS SUMMARIZED ON SHEET A8.2 <br /> • 104.: <br /> � 09 <br /> � � +8�.0�� <br /> i W ' . . . +9'-0" � <br /> . LEGEND <br /> • � � INTERNALLY ILLUMINATED EXIT SIGNAGE W/ BATTERY BACKUP <br /> EXI QEXI D pER IBC SECTION 1013, CONFIRM OPERATION FOR EXISTING. <br /> � ADD WHERE NOT EXISTING. ARROW = DIRECTION INDICATOR, <br /> � 1 � �FFI E - IF REQUIRED <br /> PEN OFFIC 08 � 1X4 SURFACE MOUNTED LED LIGHT FIXTURE W/WRAP AROUND <br /> 10 <br /> ACRYLIC LENS <br /> +9'-0" �� NEW 2X4 LAY-IN LED LIGHT FIXTURE, 18 CELL PARABOLIC � <br /> � <br /> HATCH INDICATES "NIGHT LIGHT" FOR EGRESS ILLUMINATION <br /> NOT LESS THAN 1 FC PER IBC SECTION 1008.2.1 WITH <br /> CONFERE CE � EMERGENCY POWER PER 1008.3.3 <br /> I +9'- ' ', � EXHAUST FAN (SONE RATING LESS THAN 1.0 SONE) <br /> - i0194 <br /> RECEPTIO REc�r'TERED <br /> ��1�` 10 6 SUSPENDED ACOUSTIC CEILING TILE AND GRID: AR,� HITECT <br /> � �' OFFI E A8-1 ARMSTRONG, CORTEGA, 24"X 48° SQUARE LAY-IN TILE, 1 ' <br /> 07 Typ WHITE WITH CLASS "A" 15/16" EXPOSED"T"GRID SYSTEM, <br /> +9'-0" W HITE <br /> AM EG� L <br /> I �WB STATE OF WASi�i1t�,.�TON <br /> 2> I <br /> GYPSUM BOARD CEILING �1 <br /> i OPEN TO STRUCTURE <br /> I EXI <br /> 0 0 -- - <br /> - - - - <br /> � - - - � I DAYLIGHT ZONE <br /> ,�. ,I <br /> I � � � - - - - � � � (PRIMARY DEPTH = TO WINDOW HEAD HEIGHT,24" BEYOND <br /> WIDTH OF WINDOW) <br /> � � � _ _ - _ � � � (SECONDARY DEPTH - 2 TIMES WINDOW HEAD HEIGHT) <br /> � � C = _ _ _ � � � � NEW LIGHT SWITCH <br /> �� _ _ _ _ _ _ �b REFLECTED CEILING <br /> PLAN <br /> Proj. No: 19.0005640.000 Reviewed By: PA/PM <br /> i� REFLECTED CEILING PLAN _ <br /> �A2.2 1/4"=1'-0" <br /> 0 2' 4' 8' � <br /> SCALE: 1/4" = 1'-0" A 2 � 2 <br />