�i �2 MECHANICAL NOTES: <br /> O 1. DUCT MATERIAL IS 26 GA. GALV. AND FLEX DUCT. DUCTWORK SHALL BE SUPPORTED PER 2015 IMC � <br /> WAC CHAPTER 6. SECTION 603 <br /> 2. MATERIAL IN DUCTS SHALL HAVE A FI.AME SPREAD INDEX OF LESS THAN 25, SMOKE DEVELOPMENT <br /> OF 50 PER 2015 IMC WAC CHAPTER 6. SECTION 602 <br /> 3. LOW PRESSURE DUCT SYSTEMS SHALL HAVE LONGITUDINAL AND TRANSVERSE JOINTS, SEAMS AND <br /> ' CONNECTIONS OF SUPPLY AND RETURN DUCTS AND PLENUMS SECURELY FASTENED AND SEALED WITH <br /> WELDS, GASKETS, MASTICS (ADHESIVES), MASTIC-PLUS EMBEDDED-FABRIC SYSTEMS OR APPROVED TAPES <br /> INSTALLED IN ACCORDANCE WITH 2O15 IMC WAC CHAPTER 6 SECTION 603.9. ' <br /> CD-1 CD-1 <br /> 10" 10" 4. WHEN ISOLATION SLEEVES ARE USED AT LINE CONNECTIONS TO PLENUMS, THEN THEY SHALL COMPLY <br /> WITH IMC CHAPTER 6 <br /> WALL MOUNT <br /> 1 RETURN 5. 10" DIFFUSERS WITH NO MANUAL DAMPERS. USE FLOW CONTROLS AT WYES, TYPICAL AS NOTED ON PLAN � <br /> 2� �0, �� . <br /> � � 12 6. MINIMUM OUTSIDE AIR VENTILATION PER 2015 IMC WAC CHAPT�R 4, TABLE 403.3.1.1. <br /> ,� O ,� 2 7. OUTSIDE AIR DAMPERS SHALL COMPLY WITH 2O15 WSEC, SECTION C403.2.4.3. <br /> HP-1 <br /> �1� 8. SING�E PACKAGE UNITARY FAN COOLING UNITS HAVWG A TOTAL COOLING CAPACITY OF GREATER THAN <br /> 2'�O �o r TCURBF 20,000 Btu/h REQUIRE ECONOMIZERS PER WSEC 403.3. EXCEPT AS PERMITTED BY C403.3 EXCEPTION 1 <br /> O - - - - - - - - - - � - - - - - - - <br /> SUPPLY PLENUM <br /> #Pws�3� MECHANICAL NOTES: (cont.) <br /> OCCUPIED SET POINT MECHANICAL EQUIPMENT INSTALLATION IN OR ON THIS BUILDING SHALL BE IN ACCORDANCE WITH <br /> TO BE CONTROLLED BY THE REQUIREMENTS OF THE 2015 IMC WAC CHAPTER 6. <br /> nLIGHT OCCUPANCY ' <br /> SENSORS ROUND FLEX DUCT SHALL BE U.L. LISTED CLASS 1, STANDARD 181 - FACTORY MADE AIR DUCTS AND AIR � <br /> ' CONNECTORS. MEASURED IN ACCORDANCE TO ASTM C 518 OR ASTM C 177 AT 75DEG F MEAN <br /> TEMPERATURE. INSTALLATION SHALL BE IN ACCORDANCE WITH MANUFACTURES INSTALLATION INSTRUCTIONS <br /> CD-1 CD-1 <br /> 10" 10" MECHANICAL DRAWINGS SHOW DUCTWORK SIZES TO BE CLEAR WSIDE DIMENSION. <br /> ' DUCT INSULATION SHALL COMPLY WITH 2O15 IMC WAC CHAPTER 6, SEC. 604. <br /> ELECTRICIAN MUST VERIFY ALL ELECTRICAL REQUIREMENTS AND LOCATIONS. � <br /> THERMOSTAT SCNEDULING TO BE PERFORMED ON SITE BY OTHERS. <br /> ALL HVAC EQUIPMENT LEAVES FACTORY WlRED FOR 240 VOLT OPERATION ' <br /> THE ACCEPTABLE OPERATWG RANGE FOR THE 240V & 208V TAPS ARE: <br /> \.:� TAP RANGE <br /> 240 253-216 <br /> M �� HAN I CAL � LAN 208 220-187 <br /> 1/4" = 1'-0" SITE MECHANICAL CONTRACTOR IS RESPONSIBLE FOR MAKING SURE THE RIGHT TAP IS CONNECTED FOR <br /> THE APPLIED SITE VOLTAGE. • . <br /> , <br /> MINIMUM VENTILATION RATES PER IMC SECTION 403 AIR FILTERS IN HVAC UNITS OR SYSTEMS ARE TO BE CHANGED EVERY 30 DAYS BY OTHERS ON SITE. - <br /> Rp <br /> room# name Az(sf) sf/1000 Occ. Dens Pz(calc} Pz(used) (cfm/person) Ra (cfm/sf) Vbz�cfm) REGISTER AIR FLOW TEST AND BA�ANCE OF HVAC SYSTEM TO BE PROVIDED AND PERFORMED BY OTHERS ON SITE. , <br /> 1 Classroom 817 0.817 35 29 29 10 0.12 388 . <br /> - 388cfm HVAC SITE CONTRACTOR IS R�SPONSIBLE FOR BALANCING THE SYSTEM. (2015 IMC WAC 403.3.3.1.5) <br /> Az=room area (sf) <br /> Occ. Dens=occupant density(from Table 403.3} <br /> Pz(calc� =zone population or occupant quantity(calculated� <br /> � Pz(used) =zone population or occupant quantity (user can override the calculation-increase onfy) <br /> Rp=people outdoor airflow rate in breathing zone (cfm/person) . <br /> Ra=area outdoor airflow rate in breathing zone (cfm/sf) <br /> Vbz=Breathing zone outdoor airflow rate per eq. 4-1{ Rp*Pz+Ra*Az) <br /> PACKAGE *SPVU* HIGH EFFICIENCY WALL MOUNT HEAT PUMP - SCHEDULE � <br /> DOAS/ERV/ELECTRICAL � DOAS/ERV/ELECTRICAL Q COOLING CAPACITY OO HEATWG CAPACITY �4 DOAS UNIT HEAT STRIPS <br /> ENERGY RECOVERY ELECT. INFORM. ELECT. INFORM. <br /> DOAS LOW VENTILATION MODE FULL VENTILATION MODE <br /> COMP TOTAL ECON. COOL SENS. COOL SENS. HTG HTG OUTDOOR ELEC. ELEC. OPER. <br /> BARD TYPE CFM B�R. 100% ERV ECM ECM OUTSIDE ENT ENT CAP. CAP. CAP. CAP. OUTSIDE CAP. CAP. SUMMER DB/WB HRS HRL WINTER INDOOR WHR HEAT HEAT WGT. ADDITIONAL <br /> TAG QTY MODEL # TONS SCROLL NOM. TYPE. FREEFLOW VENTIL. V-PH ERV BLOWER V-PH ERV BLOWER DB DB WB EER IPLV BTUH BTUH BTUH BTUH DB COP BTUH BTUH EFFICIENT DEG'S BTUH BTUH EFFICIENT DB MOP V-PH MCA MOP CiCT V-PH MCA BTUH CKT KW BTUH LBS. REMARKS <br /> � PART/FULL M,OTOR MOTOR PART LOAD PART LOAD FULL LOAD FULL LOAD PART/LOAD FUIL/LOAD � <br /> HP-1 1 C36HA-AtOZP4XXR 3 2-STAGE 750 ECM NO 388 230/1 AMPS-1.3 AMPS-.87 230/1 AMPS-2.2 AMPS-1J4 95 80 67 11.0 14.5 23.4K 18.5K 35K 26.3K 47 3.3 22.7K 31K 65% 95/70 6,318 1,711 80% 1,711 23,328 230/1 27 40 A 240/1 52 60 B 10 34,130 678 1, 2, 3, 4, 5, 6, 7, 8 , <br /> 1100 450 WATTS-296 WATTS-95 WATTS-497 WATTS-192 <br /> ADDITIONAL REMARKS; C36H1 The sequence of operation for the Integrated DOAS system. <br /> 1 - PLAN # ----_----- <br /> 2 - INCLUDE BARD WALL CURB #TCURBF3642A-4. ERV Watts - Low 296 Watts Blower Full Load 192 Watts 1. Upon a call from the occupancy sensor the(DOAS) ERV and the indoor(ECM) motor will <br /> 3 - THERMOSTAT, BARD # 8403-060, 7-DAY PROGRAMMABLE. ERV Am s - Low 1.3 Am s Blower Full Load 1.74 Am s start in low vent mode and ventilate the space continuously as occupied. <br /> 4 - WALL CO2 SENSOR. #8403-067 ERV CFM - Low 300 CFM Blower Part Load 95 Wptts Note: 1 on the HVAC Schedule. ' <br /> 5 - OCCUPANCY SENSOR, (SUPPLIED BY BLAZER) ERV Watts - Med 415 Watts Blower Part Load 0.87 Am s 2, Upon a call from the CO2 sensor the(DOAS) ERV and the indoor(ECM) motor will <br /> 6 - GPS (FIELD INSTALLED CONTROL KIT). ERV Am s - Med 1.8 Am s <br /> � 7 - 2" FILTER. ERV CFM - Med 375 CFM Com ressor Full 2588 Watts change to full vent mode and ventilate the space until the CO2 sensor is satisfied and then <br /> 8 - ERV (DOAS) ENERGY RECOVERY. ERV Watts - Hi 497 Watts Com ressor Full 11.46 Am s revert back to the low vent mode during the occupied time. <br /> 9 - UNIT COLOR IS *BUCKEYE GRAY* ERV Am s - Hi 2.2 Am s Com ressor Part 1734 Watts Note; 2 on the HVAC Schedule. <br /> 10 - PRE INSTALLED OUTDOOR THERMOSTAT, SET AT 40DEG'S. ERV CFM - Hi 450 CFM Com ressor Part 7.99 Am s 3. The Heating and Cooling section will only work if there is a Heating or Cooling call from <br /> ** M.C. TO REFER TO INSTALLATION INSTRUCTIONS FOR START UP AND EQUIPMENT SET. Outdoor Fan 38o Watts the thermostat. This action works entirely independent of the DOAS ventilation portion. <br /> ** M.C. TO CHECK SITE VOLTAGE AND SET CORRECT TAP ON TRANSFORMER. Outdoor Fan 1.67 Am s Note; 3&4 on the HVAC Schedule. <br /> � ** M.C. TO SET AND PROGRAM THERMOSTAT PER CUSTOMERS REQUIREMENTS. 4. ThIS aCtlOil WIII k2ep 1"epe8tlllg ItSelf 8S f@qUlf@d by th@ OCCUpanCy Seflsof, CO2 sensof <br /> and Room Thermostat. <br /> 8-18-17 REVISE HEAT PUMP SCHEDULE,ADD SEQUENCE OF OP. RMS COPYRIGHT 2017, BLAZER INDUSTRIES, �Nc. MODULAR C�+�S.�r'(�o� fo�.' Approved for Const: Job No: 19039 <br /> 9-6-17 ADD SUPPLY PLENUM NUMBER (#PWS131) LDG THIS MATERIAL IS THE EXCLUSIVE PROPERTY <br /> OF BLAZER INDUSTRIES, INC.AND SHALL �■ � � � File Copy: <br /> NOT BE REPRODUCED, USED, OR DISCLOSED 2$ X 32 <br /> � INDUSTRIES,INC. <br /> TO OTHERS EXGEPT AS AUTHORIZED BY THE �o www.blazerind.com � � Drawn By: LDG • <br /> DATE REVISION BY WRITi�EN PERMISSION OF BLAZER INDUSTRIES. �� P.Q.BOX489 ■ Aumsviue,OR97325-OA89 WA. ��LD �'acific Mobile 17 �LMP-04 A9 WA Issue Date: 9-6-17 ' � <br />