1 2 3 4 5 �' <br /> GENERAL NOTES NON-STRUCTURAL ELECTRICAL NOTES ABBREVIATIONS <br /> 1. PERFORM WORK IN ACCORDANCE WITH APPLICABLE 1. THE FOLLOWING ITEMS ARE TAKEN DIRECTLY FROM A AMPERE kVA KILOVOLT AMPERE UG UNDERGROUND <br /> � NATIONAL AND STATE CODES AS AMENDED LOCALLY THE 2015 INTERNATIONAL BUILDWG CODE AND FROM AC AIR CONDITIONING; ALTERNATING CURRENT; kW KILOWATT UL UNDERWRITERS LABORATORIES � ' � <br /> AND ENFORCED BY THE AHJ. THE AMERICAN SOCIETY OF CIVIL ENGINEERS (ASCE) ABOVE COUNTER KCMIL THOUSAND CIRCULAR MILS UON UNLESS OTHERWISE NOTED . <br /> STANDARD 7. THE CONTRACTOR SHALL REFER TO THE AF AMP FUSE; AMP FRAME KVAR KILOVOLT AMPERE REACTIVE UPS UNINTERRUPTIBLE POWER SUPPLY <br /> 2. OBTAIN AND PAY FOR PERMITS REQUIRED FOR ABOVE FOR ADDITIONAL INFORMATION, EXCEPTIONS, AFF ABOVE FINISHED FLOOR USB UNIVERSAL SERIAL BUS , � <br /> INSTALLATION OF WORK. ARRANGE AND SCHEDULE AND FURTHER DESCRIPTIONS. THE CONTRACTOR AG ABOVE GRADE � • <br /> REQUIRED INSPECTIONS. SHALL ADHERE TO REQUIREMENTS AND AS SUCH, LAN LOCAL AREA NETWORK UTP UNSHIELDED TWISTED PAIR <br /> SHALL BE INCLUDED WITHIN BID. ALSO REFER TO AHJ AUTHORITIES HAVING JURISDICTION LCP LIGHTING CONTROL PANEL UV UNIT VENTILATOR <br /> 3. COORDINATE ELECTRICAL WORK WITH THAT OF SPECIFICATIONS. AHU AIR HANDLING UNIT LEC LOCAL EXCHANGE CARRIER � � � � �' <br /> OTHER TRADES. REFER TO MECHANICAL, AIC AMPERE WTERRUPTWG CURRENT LT LIGHT V VOLTS � <br /> ARCHITECTURAL, C1VIL, AND LANDSCAPE DRAWINGS 2. 2015 IBC, 1613.1, SCOPE: ARCHITECTURAL, AL ALUMINUM LTG LIGHTING VA VOLT AMPERES <br /> AND SPECIFICATIONS. COORDINATION SHALL OCCUR MECHANICAL, ELECTRICAL, AND NON-STRUCTURAL ANSI AMERICAN NATIONAL STANDARDS INSTITUTE VFD VARIABLE FREQUENCY DRIVE � � � � <br /> PRIOR TO FABRICATION, PURCHASE, AND COMPONENTS THAT ARE PERMANENTLY ATTACHED TO AS AMP SWITCH ' ' ' ' " " ' '' � <br /> INSTALLATION OF WORK. STRUCTURES AND 7HEIR SUPPORTS AND M METER <br /> ATTACHMENTS SHALL BE DESIGNED AND AT AMP TRIP MAN METROPOLITAN AREA NETWORK W WATT; WIRE ' • <br /> 4. COMPLETION OF WORK SHALL BE EXECUTED IN CONSTRUCTED TO RESIST THE EFFECTS OF ATS AUTOMATIC TRANSFER SWITCH MPOP MAIN POINT OF PRESENCE W/ WITH <br /> � ACCORDANCE WITH THE PROJECT SCHEDULE. EARTHQUAKE MOTIONS IN AGCORDANCE WITH ASCE 7, ATM ASYNCHRONOUS TRANSFER MODE MTD MOUNTED W/O WITHOUT • � <br /> SCHEDULE INSTALLATION WITH OTHER TRADES TO EXCLUDING CHAPTER 14 AND APPENDIX 11A. AV AUDIO VISUAL MTS MANUAL TRANSFER SWITCH WA WORKSTATION AREA <br /> ENSURE PROJECT MILESTONES ARE MET. AWG AMERICAN WIRE GAUGE WAN WIDE AREA NE7WORK H � R G I S , � <br /> 3. ASCE 7-02 11A.1.2.2 CONTRACTOR RESPONSIBILITY: . <br /> 5. DRAWINGS ARE DIAGRAMMATIC AND DO NOT SHOW EACH CONTRACTOR SHALL BE RESPONSIBLE FOR THE (N) NEW WG WIRE GUARD <br /> ALL COMPONENTS REQUIRED FOR A COMPLETE CONSTRUCTION OF A SEISMIGFORCE-RESISTING BAS BUILDING AUTOMATION SYSTEM N NEUTRAL WH WATT HOUR METER Hargis Engineers, Inc. '' <br /> BATT BATTERIES WP WEATHERPROOF <br /> INSTALLATION. PROVIDE COMPONENTS REQUIRED SYSTEM, DESIGNATED SEISMIC SYSTEM, OR NAC NOTIFICATION APPLIANCE CIRCUIT 1201 ThirciAvenue, Suite6�0 � Seattle,WA981Q1 � <br /> FOR COMPLETE AND OPERATIONAL SYSTEMS COMPONENT LISTED IN THE QUALITY ASSURANCE PLAN BKBD BACKBOARD NEC NATIONAL ELECTRICAL CODE t�206,448.3376 f�206.448.4450 w� hargis.biz <br /> INCLUDING RACEWAYS, CONDUCTORS, BOXES, SHALL SUBMIT A WRITTEN CONTRACTOR'S STATEMENT BIL BASIC IMPULSE INSULATION LEVEL NATIONAL ELECTRICAL MANUFACTURERS <br /> SUPPORTS AND SIMILAR ITEMS. OF RESPONSIBILITY TO THE REGULATORY AU7HORITY BKR BREAKER NEMA ASSOCIATION XMFR TRANSFORMER ����MEq.�wic�•E�Ecrwc.�u.•r�E�nnurvicnTio�vs <br /> HAVING JURISDICTION AND TO THE OWNER PRIOR TO BLDG BUILDING NF NON-FUSED <br /> 6. BRANCH CIRCUIT HOMERUNS ARE SHOWN TO THE COMMENCEMENT OF WORK ON THE SYSTEM OR NIC NOT IN CONTRACT Y WYE . � � � . ' ' � <br /> , INDICATE CIRCUIT PROPERTIES AND CONFIGURATION. COMPONENT. THE CONTRAGTOR'S STATEMENT OF C CONDUIT; DEGREES CELSIUS NL MGHT LIGHT <br /> SINGLE-CIRCUIT HOMERUNS SERVED FROM THE RESPONSIBILITY SHALL INCLUDE THE FOLLOWING: Z IMPEDANCE <br /> SAME PANELBOARD MAY BE COMBINED W CAB CABINET � � l <br /> ACCORDANCE WITH THE DIVISION 26 SPECIFICATIONS, A. ACKNOWLEDGMENT OF AWARENESS OF THE CAT CATEGORY OFC OPTICAL FIBER CABLE • . <br /> UNLESS INDICATED OTHERWISE. EXTEND AND SPECIAL REQUIREMENTS CONTAINED IN THE CATV COMMUNITY ANTENNA TELEVISION OHL OVERHEAD LINE � <br /> C CONNECT BRANCH CIRCUIT RACEWAY AND WIRING QUALITY ASSURANCE PLAN CB CIRCUIT BREAKER OL OVERLOAD , C <br /> FROM HOMERUN TO DEVICES AND EQUIPMENT WITH B. ACKNOWLEDGMENT THAT CONTROL WILL BE CCTV CLOSED CIRCUIT TELEVISION OS OCCUPANCY SENSOR � <br /> CIRCUIT NUMBERS INDICATED. CONDUCTOR EXERCISED TO OBTAIN CONFORMANCE WITH CLG CEILING OSP OUTSIDE PLANT <br /> QUANTITIES AND SIZES ARE INDICATED AT THE CONSTRUCTION DOCUMENTS APPROVED �S <br /> HOMERUNS ONLY. SHOW ACTUAL RACEWAY BY THE AUTHORITY HAVING JURISDICTION; CM CEILINGMOUNTED � <br /> ROUTWG AND CIRCUITING ON RECORD DRAWINGS. C. PROCEDURES FOR EXERCISING CONTRO� CO CONDUIT ONLY P POLE �',,�I,� <br /> MINIMUM CONDUCTOR SIZE#12 AWG. WITHIN THE CONTRACTOR'S ORGANIZATION, THE COW COMPUTER ON WHEELS PBX PRIVATE BRANCH EXCHANGE . <br /> METHOD AND FREQUENCY OF REPORTING AND CR CONTROLLED RECEPTACLE PF POWER FACTOR <br /> , 7. LOCATIONS OF RACEWAY, PATHWAY AND SIMILAR THE DISTRIBUTION OF THE REPORTS; AND CT CURRENT TRANSFORMER PH PHASE � � � � � � <br /> ITEMS ARE SHOWN SCHEMATICALLY. COORDINATE D. IDENTIFICATION AND QUALIFICATIONS OF THE CU COPPER PIR PASSIVE INFRARED <br /> INSTALLATION, INCLUDING BUT NOT LIMITED TO PERSON(S) EXERGSING SUCH CONTROL AND PIV POST INDICATING VALVE Cascade H S 2019 <br /> CABLING, TELECOMMUNICATION PATHWAYS AND THEIR POSITION(S) IN THE ORGANIZATION. ' • <br /> SPACES, AND EXACT LOCATION OF HORIZONTAL AND DDC DIRECT DIGITAL CONTROL PNL PANEL PO I��C�IJ I EiS <br /> BACKBONE CABLING WITH LOCATIONS OF FIXED 4. DIVISION 26 RESPONSIBILITIES: DEMARC DEMARCATION POINT PP PATCH PANEL <br /> CASEWORK AND BUILDING CONDITIONS AFFECTWG DISC DISCONNECT PT POTENTIAL TRANSFORMER � <br /> THE WORK OF THIS CONTRACT. A. HANGERS AND SEISMIC BRACING FOR DIST DISTRIBUTION PVC POLYVINYL CHLORIDE FOR <br /> ELECTRICAL SYSTEMS SHALL BE DESIGNED AND DSL DIGITAL SUBSCRIBER LINE � <br /> SPECIFIED BY DIVISION 26. DIVISION 26 SHALL DWG DRAWING RCP REFLECTED CEILING PLAN ++ h <br /> REFER TO THE ELECTRICAL DRAWINGS FOR EVe 1 P l l P U!J I I C <br /> LOCATIONS OF EQUIPMENT AND ELECTRICAL REC RECEPTACLE <br /> SYSTEMS AS STRUCTURAL DRAWINGS DO NOT (E) EXISTING REF REFER TO SCI IOOIS <br /> , SHOW THE LOCATIONS OF ELECTRICAL EA EACH REV REVISION � <br /> EQUIPMENT, RACEWAYS, AND OTHER EF EXHAUS7 FAN RM ROOM <br /> COMPONENTS. EIA ELECTRONIC INDUSTRIES ASSOCIATION RU RACK UNIT . <br /> B. DIVISION 26 SHALL COORDINATE THE SUPPORT AT . <br /> SYSTEMS AND DESIGN LOADS FOR HUNG ELEV ELEVATION <br /> RACEWAYS AND OTHER ELECTRICAL SYSTEMS EM EMERGENCY SHT SHEET 801 E Casino Rd <br /> (INCLUDING COMBWED MULTIPLE RACEWAY EMT ELECTRICAL METALLIC TUBING SLC SIGNALING LINE CIRCUIT �' <br /> RUNS) WITH THE GENERAL CONTRACTOR AND ENCL ENCLOSURE SM SINGLEMODE Everett WA 98203 � <br /> THE STEEL AND WOOD JOIST MANUFACTURERS EPM ELECTRONIC POWER METER SMFC SURFACE-MOUNTED OPTICAL FIBER CABINET . <br /> IN ADDITION TO OTHER TRADES THAT MAY BE EPO EMERGENCY POWER OFF SMR SURFACE METAL RACEWAY � PERM IT RESU BM ITTAL � <br /> IMPACTED. EQUIP EQUIPMENT SONET SYNCHRONOUS OPTICAL NETWORK <br /> B 12/18/2019 . <br /> ETR EXISTING TO REMAIN SP SERVICE PROVIDER B <br /> , EWC ELECTRIC WATER COOLER SPD SURGE PROTECTIVE DEVICE - <br /> This drawing is: <br /> SPEC SPECIFICATIONS 1. Copyright 2019 Dykeman, Inc. <br /> F FUSE;DEGREES FAHRENHEIT SPST SINGLE POLE SINGLE THROW 2. The Architect's Instrument of Professional Service. <br /> FA FIRE ALARM ST SHUNT TRIP 3. For use on this project only. Obtain Architect's • <br /> written permission for any other use or reproduction. � <br /> FAAP FIRE ALARM ANNUNCIATOR PANEL STP SHIELDED TWISTED PAIR <br /> FACP FIRE ALARM CONTROL PANEL SVGA SUPER VIDEO GRAPHICS ARRAY - - � �' <br /> FBO FURNISHED BY OWNER SW SWITCH � <br /> FOIC FURNISHED BY OWNER INSTALLED BY SWBD SWITCHBOARD ZO� 9-OZ V <br /> CONTRACTOR - <br /> � FO10 FURNISHED BY OWNER INSTALLED BY OWNER TBB TELECOMMUNICATIONS BONDING BACKBONE <br /> FSD FIRE SMOKE DAMPER TEL TELEPHONE • ' <br /> TELCO TELEPHONE COMPANY <br /> � G GROUND TGB TELECOMMUNICATIONS GROUNDING BUSBAR MARK DATE DESCRIPTION <br /> GF GROUND FAULT CIRCUIT INTERRUPTER TIA TELECOMMUNICATIONS INDUSTRY ASSOCIATION <br /> GFP GROUND FAULT PROTECTION TMGB TELECOMMUNICATIONS MAIN GROUNDWG � " <br /> GND GROUND BUSBAR <br /> GRS GALVANIZED RIGID STEEL TP TAMPERPROOF •; <br /> TR TELECOMMUNICATIONS ROOM � <br /> HC HORIZONTAL CROSS CONNECT TTB TELEPHONE TERMINAL BOARD <br /> HID HIGH INTENSITY DISCHARGE TV TELEVISION <br /> HP HORSEPOWER TVSS TRANSIENT VOLTAGE SURGE SUPPRESSION <br /> HTR HEATER TYP TYPICAL , , <br /> Hz HERTZ � � <br /> PRINCIPAL.IN CHARGE: � - , <br /> IC INTERMEDIATE CROSS CONNECT PROJECT MANAGER: � - <br /> IBC INTERNATIONAL BUILDING CODE PR0,IECT ARCHITECT: � - � - <br /> IDF INTERMEDIATE DISTRIBUTION FRAME JOB CAPTAIN: � - � <br /> A INSTITUTE OF ELECTRICAL AND ELECTRONIC A <br /> IEEE ENGINEERS � � � <br /> IG ISOLATED GROUND E L E CT R I CAL <br /> IMC INTERMEDIATE METALLIC CONDUIT � <br /> ISDN INTEGRATED SERVICES DIGITAL NETWORK ABBREVIATIONS AND <br /> _ � JUNCTION _��zF N F R A I N�T F� � ' � <br /> , � , <br /> ' ' .; <br /> 1 2 3 4 5 . <br /> r ' • <br /> � . <br />