at <br /> • <br /> City of Everett <br /> Development and Construction <br /> Public Works - Permit Services <br /> ve er 14,2019 <br /> Page 2 <br /> 1010.1.9.7 Delayed Egress: <br /> 1. The delay electronics of the delayed egress locking system shall deactivate upon <br /> actuation of the sprinkler system <br /> 2. The delay electronics of the delayed egress locking system shall deactivate upon <br /> loss of power controlling the lock <br /> 3. The delayed egress locking system shall have the capability of being deactivated <br /> at the fire command center. <br /> 4. An attempt to egress shall initiate an irreversible process that shall allow such <br /> egress in not more than 15 seconds when a physical effort to exit is applied to the <br /> egress side door hardware for not more than 3 seconds. Initiation of the <br /> irreversible process shall activate an audible signal in the vicinity of the door. <br /> Once the delay electronics have been deactivated, rearming the delay electronics <br /> shall be by manual means only. <br /> Exemption to #4:Where approved, a delay of not more than 30 seconds is <br /> permitted on a delay egress door. <br /> 5. The egress path shall not pass thru more than one delayed egress system. <br /> 6. A sign shall be provided on the door located above and within 12"of the door exit <br /> hardware. <br /> 6.1 For doors that swing in the direction of egress,the sign shall read: PUSH <br /> UNTIL ALARM SOUNDS. DOOR CAN BE OPENED IN 15 (30) SECONDS. <br /> 6.2 The sign shall comply with the visual character requirements in ICC A117.1. <br /> Summery: <br /> We believe we meet the requirements for a delayed egress door at Door-A. We request <br /> the City of Everett approves this design. <br /> 800()Ctlite_79/ <br /> Douglas McNutt Principal <br /> Encl: See Everett Pharmacy Refresh permit drawings dated 11-14-2019 <br /> C: Bryan Moorman,Project Manager <br /> Jordan Jackson Project Manager, <br /> National Facility Services Kaiser Permanente <br /> R. David Frum, FAIA,ACHA <br /> Z:\18044-EVM Pharmacy Upgrade\Documents\06.00 Agency Reviews\06.10 Municipal\Kaiser Everett Clinic 1st Floor Delayed Egress Door Memo_11-14-2019.docx <br />