Laserfiche WebLink
411, • <br /> Mr. McIlvain <br /> CRM Architects&Planners, Inc. <br /> Plan Check Number: B1805-010, First Review <br /> August 1, 2018 <br /> 11.The required foundation dimensions are obscured at multiple locations by solid wall shading. <br /> See IBC Section 1603.1. The following dimensions should be revised: See structural response <br /> letter <br /> a. Interior footing width on Grids 2 and 3. <br /> b. Exterior footing width on Grid C. <br /> c. Building dimension at Grid 4/B.2. <br /> d. Widened foundation at locations referenced with Section 9/SF1.2. Note that width appears <br /> to vary around the building perimeter. The required dimensions shall be specified at each <br /> location. <br /> 12.The column base plate information in Details 10/SF1.2 and 12/SF1.2 appear to conflict with <br /> Detail 5/S1.0. It appears that Detail 5/S1.0 is intended to control the design. Notable <br /> discrepancies include: plate size (see Detail 5/SF1.2), anchor bolt size, column-base plate <br /> alignment for exterior columns, anchor bolt material (see notes on Sheet SO.0), and welding <br /> requirements (missing from Detail 5/S1.0). The design of the base plates should be reviewed <br /> and revised. Duplicate information should be removed from the construction drawings. See <br /> IBC Section 107.2.1. See structural response letter <br /> 13. Details 7, 9, and 11 on Sheet SF1.2 specify J-bolts connecting the walls to the foundations. <br /> Details 2, 3, and 4 on Sheet S1.0 specify post-installed screw anchors. The anchorage should <br /> be reviewed and revised. It is recommended that the anchorage only be specified in one <br /> location. See IBC Section 107.2.1. See structural response letter <br /> Gravity System: <br /> 14.The material grades used in the design of the gravity framing the structural calculations does <br /> not appear consistent with the General Notes and Specifications on Sheet SO.0. For example, <br /> many of the calculations specify manufactured SPF with Fb=1,650 psi, which significantly <br /> exceeds the bending capacities of the listed solid-sawn grades. Note that DFL and HF are <br /> typically available in the project locale, while SPF is not. Other products appearing in the <br /> calculations that are not clearly specified in the drawings are DF-S and Louisiana Pacific LVL. <br /> The notes should be revised to specify the products considered in the calculations. Where the <br /> calculations are based on products with capacities exceeding the products to be used in the <br /> project, revised calculations substantiating the intended construction shall be submitted for <br /> review. See IBC Sections 107.2.1 and 1604.1. See structural response letter <br /> 15.The headers in the exterior walls consist of built-up boards per the"Header Schedule"on <br /> Sheet S3.0 and the structural calculations. See IBC Sections 1604.1 and 1604.4. The following <br /> comments should be addressed: See structural response letter <br /> a. The dead load appears to represent the roof weight only. The weight of the walls and <br /> parapet above should be included. <br /> b. The snow load does not appear adequate for the flat roof load and the drift surcharge. See <br /> other comments regarding the snow drift calculation. <br /> c. The design does not include wind loading. The headers support out-of-plane wall loads <br /> from both the wall framing and window glazing. The headers should be evaluated for <br /> biaxial bending per NDS-15 Section 3.9.2 and considering IBC Equations 16-12 and 16-13. <br /> Wind loads shall be determined by ASCE 7-10 Chapter 30. The highest pressures on the <br /> Page 6 of -/ <br /> CITY OF EVERE1T• 3200 Cedar Street • Everett, WA 98201 • (425) 257-8810 • Fax(425) 257- <br />