Mr. McIlvain <br /> CRM Architects&Planners, Inc. <br /> Plan Check Number: B1805-010, First Review <br /> August 1, 2018 <br /> a. The details appears to provide an out-of-plane connection for the wall consisting of ledgers <br /> placed in cross-grain bending and tension loading of the diaphragm sheathing, both of <br /> which are not permitted. The detail shall be revised to clarify the construction and remove <br /> unpermitted framing configurations. <br /> b. The diaphragm shall be provided with subdiaphragms and crossties of sufficient depth to <br /> develop the wall loads into the diaphragm. <br /> c. Calculations substantiating the connections for out-of-plane loading, including but not <br /> limited to wind leeward pressures, shall be submitted for review. <br /> d. Plan 1/S3.0 shall be provided with references to Detail 4/S3.0. <br /> Miscellaneous: <br /> 35.The roof supports heavy mechanical equipment per Sheet S3.0. The equipment is expected to <br /> require supplemental structural framing (e.g., curbs) and anchorage to the roof structure. <br /> Details and calculations for the structural support of the equipment should be submitted for <br /> review. See IBC Sections 1603.1, 1604.1, and 1613.1, and ASCE 7-10 Section 13.6. See <br /> structural response letter <br /> 36. Continuing with the previous comment, the roof trusses support overturning loads from heavy <br /> mechanical equipment per Sheet S3.0. Concentrated vertical loads due to seismic overturning <br /> shall be specified in the drawings. The loads shall be applied in both directions. In addition, <br /> the drawings shall include a note requiring the top chords to be designed for flexure due to the <br /> loads in combination with other forces in the chords, or the note shall require additional web <br /> members to be provided at the connection points. See IBC Section 1603.1.8. See structural <br /> response letter <br /> This review has been performed for general compliance with the building codes as adopted and <br /> amended by the state of Washington and the city of Everett. Corrections and comments made <br /> during the review process do not relieve the project from compliance with code and permit <br /> requirements. The designers-of-record are responsible for a complete design in accordance with <br /> the laws of the state of Washington. <br /> If you have any questions or require additional clarification, please contact us. <br /> Respectfully, <br /> Drew Martin, P.E., S.E. <br /> Associate Engineer/ Commercial Plans Examiner <br /> (425)257-8813 <br /> dmartin@everettwa.gov <br /> S:\BMartin\2018\B1805-010_R1.docx <br /> Page 11 of /2 <br /> CITY OF EVERETT• 3200 Cedar Street• Everett, WA 98201 • (425) 257-8810 • Fax(425) ___� <br />