• Mr. Mcllvain <br /> CRM Architects&Planners, Inc. <br /> Plan Check Number: B1805-010, Second Review <br /> December 4, 2018 <br /> c. Detail 5/S-1.3 specifies 12"square base plates in 6"exterior walls on Grids 1 and 4. The <br /> base plates will not be concealed within the walls and therefore will be exposed to <br /> weather. <br /> d. Detail 5/S-1.3 references Detail 6/S3.0 which does not exist. <br /> e. Detail 5/S-1.3 specifies Column "B"which does not appear to be used in the project. <br /> See Structural Response letter <br /> 13.This comment has not been completely addressed. The sill bolting requirements are not <br /> clear. Details 7, 9, and 11 (previously 1, 3, and 5) on Sheet SF1.2 show anchor bolts <br /> connecting the walls to the foundations, and reference Sheets S1.3 and S2.0 for additional <br /> information. Sheet S2.0 does not appear to provide information on the anchor bolts. <br /> Details 7/S-1.3 and 11/S-1.3 reference Detail 3/S1.2, which does not specify sill bolting. <br /> Detail 3/S-1.1 referenced Sheet S1.0 for anchoring requirement, but does not provide a <br /> specific detail reference. Detail 8/S-1.0 specifies bolting requirements that are not <br /> consistent with Detail 3/S-1.3. Detail 3/S-1.3 does not specify the required length and <br /> grade for the sill bolts. Other incorrect or conflicting details may occur. The design of the <br /> anchor bolts should be reviewed and revised. It is recommended that the anchorage only <br /> be specified in one location. See IBC Section 107.2.1. <br /> See Structural Response letter <br /> Gravity System: <br /> 14.The following comment has not been completely addressed. See IBC Sections 107.2.1 and <br /> 1604.1. The following comments should be addressed: <br /> a. Sheet S-2.1 specifies glulam beams in the roof framing. Glulam grades are not specified <br /> in the wood notes on Sheet S-1.0. <br /> b. Sheet S-2.1 specifies headers in the roof framing as DF #2. The wood notes on Sheet <br /> S-1.0 specify beams as DF #1. <br /> See Structural Response letter <br /> 15.This comment has not been completely addressed. The original comment addressed the <br /> design of the headers. Revised drawings and calculations have been submitted. See IBC <br /> Sections 107.2.1, 1603.1, 1604.1 and 1604.4. The following comments should be <br /> addressed: <br /> a. No additional comment. <br /> b. No additional comment. <br /> c. The design does not include horizontal wind loading concurrent with the vertical loads. <br /> The headers support out-of-plane wall loads from both the wall framing and window <br /> glazing. The headers should be evaluated for biaxial bending per NDS-15 Section 3.9.2 <br /> and considering IBC Equations 16-12 and 16-13. Wind loads shall be determined by <br /> ASCE 7-10 Chapter 30. The highest pressures on the building surface shall be used in <br /> the design. The headers should also consider concurrent out-of-plane loading due to <br /> canopy thrust loads. See IBC Section 1609.1. <br /> d. No additional comment. <br /> e. The headers shall be provided with out-of-plane connections to transfer loads to the <br /> supporting king studs. <br /> OV 3200 Cedar Street 0 425.257.8800 0 everettpw@everettwa.gov// <br /> Everett,WA 98201 O 425.257.8882 fax O everettwa.gov d <br />