411 <br /> • Mr. McIivain <br /> CRM Architects&Planners, Inc. <br /> Plan Check Number: B1805-010, Second Review <br /> December 4, 2018 <br /> 36.This comment has not been addressed. The response is not sufficient. Continuing with the <br /> previous comment, the roof trusses support overturning loads from heavy mechanical <br /> equipment per Sheet S-2.1. Concentrated vertical loads due to seismic overturning and <br /> vertical load effects shall be specified in the drawings. The loads shall be applied in both <br /> directions. In addition, the drawings shall include a note requiring the top chords to be <br /> designed for flexure due to the loads in combination with other forces in the chords, or the <br /> note shall require additional web members to be provided at the connection points. See IBC <br /> Section 1603.1.8. <br /> See Structural Response letter <br /> Additional Comments: <br /> 37.The structural drawings appear to have numerous conflicting and unused details, both <br /> between and within the building and foundation drawing sets. Note that structural <br /> information also conflicts with the architectural drawings. The structural drawings should be <br /> revise to clearly show the required construction of the building. Reference should be <br /> provided clarifying the application of all details. See IBC Section 107.2.1. <br /> See Structural Response letter <br /> 38.The foundation and building drawings (i.e., the SF-series and S-series drawings) appear to <br /> have numerous incorrect references. For example, the Foundation Plan on Sheet S-2.0 <br /> references Details 7/51.2 and 10/S1.2 that do not show conditions at the foundation. Other <br /> examples have been noted in the comments above. The incorrect references identified in <br /> these review comments do not represent a comprehensive list of errors in the drawings. <br /> The construction drawings should be reviewed and revised to clearly show the required <br /> construction of the project. See IBC Section 107.2.1. <br /> See Structural Response letter <br /> 39.The Foundation Plan on Sheet S-2.0 shows nominal 6"stud-framed exterior walls at the <br /> building perimeter. Section A/S-3.1 shows a double-stud wall. The drawings are not <br /> consistent and should be revised. See IBC Sections 107.2.1 and 1603.1. <br /> See Structural Response letter <br /> 40. Detail 5/S-1.2 shows a metal stud wall. Metal stud walls do not appear to be used in the <br /> project. Material requirements do not appear on Sheet S-1.0. The detail should be <br /> removed. See also Note 3/S-2.1. See IBC Section 107.2.1. <br /> See Structural Response letter <br /> 41.The vertical framing for the parapets appears to be discontinuous at the roofline per Details <br /> 6/S-1.2 and 10/S-1.2, and rely on bracing per Sections A/S-3.1 and B/S-3.1. Calculations <br /> for the design of the braces and connections shall be submitted for review. Due to the <br /> angle of the braces, the connections to the roof shall consider concurrent shear and <br /> withdrawal loads. See IBC Sections 1604.1, 1604.4, and 2306.1. <br /> See Structural Response letter <br /> 0 <br /> 3200 Cedar Street 0 425.257.8800 O everettpw@everettwa.gov <br /> Everett,WA 98201 425.257.8882 fax everettwa.gov 7 -5 <br />