Laserfiche WebLink
410 • <br /> 607 Riverside Road <br /> B1909-009 <br /> City Review Comment Response <br /> 2. The "S-1"occupancy area shown in Egress Plan 1/A0.1 is anticipated to have high-pile storage. <br /> The exit doors shall be provided with both low and high exits signs to improve visibility. Where <br /> existing signs occur, they shall be indicated on the plans. See IBC Section 1013.1 and IEBC <br /> Section 801.3. <br /> Please see revised sheet A0.1 with revised exit legend and new general note: Racking solution is <br /> not known at this time - a separate, future racking permit will be submitted. Future racking permit <br /> will include additional exit signs required specific to racking layout. <br /> 3. Means-of-egress illumination shall be provided for the "S-1"occupancy area per IBC Section <br /> 1008.2. The construction drawings shall include a reflected ceiling plan indicating the egress <br /> lighting. The lighting shall specify a minimum 90-minute uninterrupted supply power per IBC <br /> Section 1008.3.4. Where existing systems occur, they shall be indicated on the plans. See IEBC <br /> Section 801.3. <br /> Warehouse lighting concept has been added, including egress lighting Please see revised sheet <br /> A0.1. <br /> 4. The "S-1"occupancy area requires a minimum of two exits per IBC Table 1006.2.1. Emergency <br /> means-of-egress illumination shall be provided for this area per IBC Section 1008.3. The <br /> construction drawings shall include a reflected ceiling plan indicating emergency egress <br /> lighting. The lighting shall specify a minimum 90-minute uninterrupted supply power per IBC <br /> Section 1008.3.4. Where existing systems occur, they shall be indicated on the plans. See IEBC <br /> Section 801.3. <br /> Warehouse lighting concept has been added, including egress lighting Please see revised sheet <br /> A0.1. <br /> 5. The "S-1"occupancy area requires a minimum of two exits per IBC Table 1006.2.1. The exterior <br /> landings providing egress for this area shall be provided with emergency lighting. The lighting <br /> shall specify a minimum 90-minute uninterrupted supply power per IBC Section 1008.3.4. See <br /> IBC Sections 1008.3.2 Item 5 and 1010.1.6. Where existing systems occur, they shall be <br /> indicated on the plans. See IEBC Section 801.3. <br /> Please see revised sheet A0.1, new keynote 14. <br /> 19-1011 I i <br /> g ac er peak-compasspermit review response letter draft <br />