Laserfiche WebLink
W <br />0 <br />CJ <br />CITY <br />Public <br />OF EVERETT <br />Works Department <br />March 22, 2019 <br />Seth Terry <br />Johnson Braund, Inc. <br />15200 52"d Ave. South, Suite 300 <br />Seattle, WA 98188 <br />setht@johnsonbraund.com <br />Owner: Riverview I, LLC <br />Job Address: 1622 East Marine View Drive <br />Plan Check No: B1812-026, Building A <br />RE: Building Permit Review Letter <br />Dear Mr. Terry, <br />In response to the application for a building permit, the plans have been examined and you are <br />advised that revisions may be necessary before a permit can be issued. Please review and <br />respond to the comments below. <br />NON STRUCTURAL <br />General <br />1. Electric vehicle charging locations and infrastructure requirements should be shown on <br />the plans. Section 427 <br />2. The special inspector qualifications, required inspections and reporting requirements of <br />RCW 64.55 should be shown on the plans. <br />3. Smoke detectors should be noted to be interconnected within each unit. Section <br />907.2.11.5 <br />4. The smoke detector located in the hallway of unit types 1.2, 1.3, 3.2, 3.3 & 3.4 should be <br />shown to be minimum of 3' away from the bathroom doors. Section 907.2.11.4 <br />5. The insulation in floor/ceiling assembly 8D is not permitted to exceed 3" in thickness and <br />must be attached directly to the underside of the sub -floor unless an additional layer of <br />GWB is added per U.L. <br />6. The ceiling vents in details 8 &15/A500 are through one -hour fire -rated horizontal <br />assemblies and should either be shown with listed membrane fire -stops, sleeved by metal <br />O 3200 Cedar Street O 425.257.8810 (atlee@everettwa.gov <br />Everett, WA 98201 425.257.8857 fax everettwa.gov <br />