Laserfiche WebLink
I <br /> Riverview E I WSEC Air Barrier Testing Report <br /> NO l E V E 0 <br /> Table 6: Zone "ends" Depressurized Test Results with Confidence Intervals <br /> Parameter Low Mid. High Limit Test <br /> Total Leakage @ 75 Pa 0.174 CFM/ft2 0.178 CFM/ft2 0.181 CFM/ft2 <0.25 CFM/ft2 PASS <br /> Pressure Exponent, n 0.634 0.692 0.750 0.45<n<0.85 PASS <br /> Leakage Coefficient,Co 196.40 248.36 314.07 --- --- <br /> ELA @ 75 Pa 2.199 ft2 2.244 ft2 2.290 ft2 --- --- <br /> Correlation Coefficient,r2 >0.98 PASS <br /> Table 7: Zone "mid" Pressurized Test Results with Confidence Intervals <br /> Parameter Low Mid. High Limit Test <br /> 9.7 <br /> Total Leakage @ 75 Pa 0.272 CFM/ft2 0.273 CFM/ft2 0.274 CFM/ft2 < 0.25 CFM/ft2 <br /> above <br /> Pressure Exponent, n 0.717 0.727 0.737 0.45 < n<0.85 PASS <br /> Leakage Coefficient, Co 216.82 225.99 235.56 --- --- <br /> ELA @ 75 Pa 2.363 ft2 2.372 ft2 2.380 ft2 --- --- <br /> Correlation Coefficient,? ra >0.98 PASS <br /> Page 5 1 12 <br />