Laserfiche WebLink
0Riverview E I WSEC Air Barrier Testing Report <br /> L B V E • A• O <br /> Table 8: Zone "mid" Depressurized Test Results with Confidence Intervals <br /> Parameter Low Mid. High Limit Test <br /> Total Leakage @ 75 Pa 0.208 CFM/ft2 0.210 CFM/ft2 0.211 CFM/ft2 <0.25 CFM/ft2 PASS <br /> Pressure Exponent, n 0.629 0.649 0.669 0.45<n<0.85 PASS <br /> Leakage Coefficient, Co 223.91 242.71 263.09 --- --- <br /> ELA @ 75 Pa 1.810 ft2 1.823 ft2 1.835 ft2 --- --- <br /> Correlation Coefficient, ►z = >0.98 PASS <br /> Test Data <br /> The tables and figures list the supporting tables of measured and corrected data used to build a power law <br /> models and their accompanying figures visualizing leakage versus induced differential pressure. <br /> Table 9: Zone "ends" Pressurized Airflow Data <br /> Target dP(Pa) Corrected dP Measured Airflow(CFM) Leakage(CFM) <br /> 75.0 74.7 5,976 6,021 <br /> 70.0 69.8 5,666 5,709 <br /> 65.0 64.7 5,413 5,454 <br /> 60.0 59.7 5,127 5,166 <br /> 55.0 55.0 4,777 4,813 <br /> 50.0 49.5 4,427 4,460 <br /> 45.0 44.8 4,143 4,174 <br /> 40.0 39.7 3,770 3,799 <br /> Page 6112 <br />