ELECTRICAL GROUNDING SPECIFICATIONS <br />t GROUNDING SHALLCOMPLYWITH ARTICLE 250OF <br />THE NATIONAL ELECTRICAL CODE CURRENTLY IN <br />EFFECT FOR THE AUTHORITY HAVING <br />JURISDICTION. <br />2. ALL GROUNDING DEVICES SHALL BE U.L. LISTED <br />FOR THEIR INTENDED USE. <br />3. GROUND WIRES SHALL BE TINNED #2 AWG BARE <br />SOLID COPPER UNLESS OTHERWISE NOTED. <br />4. CONNECTIONS OF ALL GROUND WIRES TO THE <br />GROUND RING SHALL BE EXOTHERMIC <br />(CAD -WELDED), UNLESS OTHERWISE NOTED. AND <br />SHALL BE INSTALLED IN ACCORDANCE WITH <br />MANUFACTURER'S RECOMMENDATIONS AND <br />T-MOBILE WIRELESS BROADBAND STANDARDS. <br />5. GROUNDING CONDUCTORS SHALL BE ROUTED <br />ALONG THE SHORTEST AND STRAIGHTEST PATH <br />POSSIBLE. WHEN REQUIRED, GROUND LEADS <br />SHALL BE BENT TO A MINIMUM OF 8' RADIUS. <br />6. WHERE GROUND WIRES ARE ROUTED FROM ANY <br />CONNECTION ABOVE GRADE TO THE GROUND RING. <br />INSTALL WIRE IN 3/4" HEAVY WALL LIQUID TIGHT <br />FLEXIBLE CONDUIT FROM CONNECTION POINT TO 5- <br />BELOW GRADE AND SEAL THE TOP WITH SILICONE <br />SEALANT. <br />7. ALL GROUND BARS SHALL BE TINNED. 1/4- COPPER, <br />SECTOR BARS Y, COLLECTOR AND MGB BARS 4". <br />OF SUFFICIENT LENGTH TO ACCOMMODATE ALL <br />REQUIRED CONNECTIONS WITHOUT DOUBLING <br />LUGS, AND EACH INSTALLED WITH ISOLATORS. <br />WHEN CONNECTING GROUND BARS (WITHIN 10 <br />FEET OF GRADE) DIRECTLY TO THE GROUND RING, <br />2 EA #2 SOLID DOWNLEADS SHALL BE CAD -WELDED <br />TO THE GROUND BAR, 1 AT EACH OPPOSITE <br />BOTTOM CORNER. AND EACH SHALL RUN IN 3/4' <br />HEAVYWALL LIQUID TIGHT FLEXIBLE CONDUIT <br />FROM GROUND BAR DOWN TO THE GROUND RING. <br />WHEN CONNECTING SECTOR GROUND BARS, <br />DAISY -CHAIN THE GROUND BARS AND RUN 1 EA #2 <br />AWG STRANDED COPPER WIRE WITH THWN <br />INSULATION FROM THE MIDDLE GROUND BAR TO <br />THE GROUND RING AND CAD -WELD TO THE RING. <br />8. WHEN ATTACHING STRANDED GROUND LEADS TO <br />THE GROUND BARS, 2 HOLE COMPRESSION LUGS <br />SHALL BE USED, PROTECT WITH WEATHERPROOF <br />HEAT SHRINK, AND WITH A THIN COAT OF'KOP'R <br />SHIELD' OR EQUIVALENT PROPERLY APPLIED AND <br />ATTACHED ONLY WITH STAINLESS STEEL <br />HARDWARE. <br />9. WHEN GROUNDING EQUIPMENT ENCLOSURES, <br />PANELS, FRAMES. AND OTHER METAL APPARATUS, <br />A #8 AWG STRANDED COPPER WIRE WITH TH WN <br />INSULATION SHALL BE ATTACHED UTILIZING A 2 <br />HOLE COMPRESSION TYPE LUG, PROTECTED WITH <br />WEATHERPROOF HEAT A CLEAN AND CORROSION <br />FREE METALLIC SURFACE UTILIZING STAINLESS <br />STEEL SELF -TAPPING SCREWS AS NOTED IN NOTE <br />10 BELOW. <br />10. PREPARE ALL BONDING SURFACES FOR GROUND <br />CONNECTIONS BY REMOVING ANY AND ALL PAINT <br />AND CORROSION TO SHINY METAL. FOLLOWING <br />CAD -WELDED CONNECTIONS TO NON -COPPER <br />SURFACES, APPLY ONE COAT OF ANY <br />ANTI-0XIDIZING PAINT,'COLD GALW OR <br />EQUIVALENT. <br />11. GROUND RODS SHALL BE COPPER -CLAD STEEL <br />5/8'00', SPACED NO LESS THAN 10' ON CENTER. <br />12. ALL GROUND SYSTEM CONDUCTORS AND <br />CONDUITS SHALL BE SECURED UTILIZING ONLY <br />NONMETALLIC, NON-CONDUCTIVE, UV RATED <br />CLAMPS, BRACKET, AND OR SUPPORTS. <br />13. WHEN REQUIRED, THE CONTRACTOR SHALL <br />ENGAGE THE SERVICES OF AN INDEPENDENT <br />TESTING FIRM TO VERIFY, UTILIZING A MEGGER <br />TEST, THAT THE RESISTANCE TO EARTH OF THE <br />NEW GROUND SYSTEM IS EQUAL TO OR LESS THAN <br />5 (OHMS). A COPY OF THE COMPLETE TESTING <br />REPORT SHALL BE PROVIDED TO THE T-MOBILE <br />REPRESENTATIVE. <br />14. ALL MATERIALS AND HARDWARE SHALL BR <br />INSTALLED IN A WORKMAN -LIKE MANNER IN <br />ACCORDANCE WITH MANUFACTURER'S <br />RECOMMENDATIONS, AND DEFINED IN NFPA-70 AND <br />APPROVED BY A,H,J, <br />LEGEND <br />■ <br />EXOTHERMIC CONNECTION <br />• <br />MECHANICAL CONNECTION <br />EQUIPMENT GROUND BAR <br />ANTENNA GROUND BAR (AS REQUIRED) <br />#2 AWG GROUND LEAD (AS REQUIRED) <br />NOTE. <br />1 CONTRACTOR TO REPLACE ALL MISSING GROUND BARS <br />AND GROUNDING CONNECTIONS AS REQUIRED. <br />NOTES & LEGEND <br />NEW #6 AWG FROM CABINET 4 <br />I <br />-- <br />TO (E) GROUND BAR (TYP.) G-2 <br />I <br />I <br />I <br />I <br />I <br />I <br />I <br />(------------ <br />I <br />-4- <br />I <br />_ <br />�I <br />I <br />NEW MECHANICAL LUG 2 <br />CONNECTION (TYP.) G-2 <br />(E) GROUND BAR (FIELD e <br />I <br />IL <br />I <br />I <br />I I <br />VERIFY LOCATION) G-2 <br />- - <br />- <br />- <br />(TYP) <br />LANDLORD SIGNATURE <br />EQUIPMENT GROUNDING i Sc—AsE 2 <br />N T <br />3 (E) <br />SECTOR GRC <br />(FIELD VERIFY LI <br />G-2 (TYP) <br />2 NEW MECHANIC,.____ <br />G-2 CONNECTION (TYP.) <br />11ANTENNA GROUNDING GROUNDING <br />NEW 06 AWG FROM ANTENNA 3 <br />TO (E) SECTOR GROUND BAR (TYP.) 57-2 <br />NEW #8 AWG FROM AHLOA 3 <br />TO (E) SECTOR GROUND BAR (TYP.) 1,G2 <br />3 <br />NOVJASiz <br />un <br />7 R 54777 Q Q' <br />?o ISTti.'`" <br />S'S'/ONAL tNv� <br />07.08.19 <br />IT IS A VIOLATION OF LAW FOR ANY PERSON, UNLESS THEY <br />ARE ACTING UNDER THE DIRECTION OF A LICENSED <br />PROFESSIONAL ENGINEER, TO ALTER THIS DOCUMENT <br />• ••-Mobiles <br />19807 NORTH CREEK PARKWAY NORTH <br />BOTHELL, WA 98011 <br />Technology Associates <br />PNW MARKET OFFICE <br />650 SOUTH ORCAS STREET, STE. R-103 <br />S EATTLE. WA 98108 <br />Technology Associates <br />ARCHITECTURE & ENGINEERING <br />2851 CAMINO DEL RIO SOUTH, STE. 200 <br />SAN DIEGO, CA 92108 <br />0]NJ13019 <br />ISSUED FORIW%Lfi00 CD <br />MGM <br />DfilO5I1019 <br />ISSUED FOR L60p B0%CD <br />EDMM <br />REV <br />I DATE <br />DESCRIPTION <br />BV <br />SE01845A <br />CASCADE HIGH <br />SCHOOL N. <br />WATER TANK <br />7410 OLYMPIC DRIVE <br />EVERETT, WA 98203 <br />WATERTANK <br />JURISDICTION APPROVAL STAMP <br />DEPARTMENT FOR LAND USE <br />DEPARTMENTFORBUILDING A CONSTRUCTION <br />SHEET TITLE <br />GROUNDING <br />PLANS <br />SHEET NUMBER <br />G=1 <br />