Laserfiche WebLink
5. Smoke dampers should be shown for the duct penetrations of smoke -wall assemblies <br />surrounding the incidental use areas. Section 509.4.2 <br />6. Please provide a reference to a detail for the wall to floor/ or roof/ceiling condition for <br />the walls capable of resisting the passage of smoke. Section 509.4.2 <br />7. The requirement for an approved carbon monoxide detection system should be noted <br />with the deferred submittals. Section 915.2.3 <br />8. A minimum of one bottle -filling station should be shown on each floor. Section <br />2902.5.4.1 <br />Egress <br />1. Please clarify how the egress widths are accommodated for the occupant load assigned <br />to Vestibule 170. Sheet G1.01 shows 202 occupants going into that room from the <br />Commons in Building 2. There are an additional 490 persons coming from the <br />Gymnasium in Building 1. It appears then that there are 692 occupants assigned to the <br />exterior exit doors (170c & 170d) however only 490 are shown. Section 1004.1 <br />a. There are no occupants from the 2d floor assigned to Doors 170 however there <br />are 173 assigned to the exterior exit doors (however their occupant load doesn't <br />accumulate per Section 1004.1.1.3). <br />2. Emergency egress lighting should be provided at all exterior landings serving an exit <br />door. Section 1008.3.2 <br />3. It should be verified that the elevator can accommodate a stretcher in a lay -down <br />position. City of Everett Ordinance revision to Section 3002.4 <br />4. Two-way communication should be shown at the 2nd-floor elevator landing in <br />accordance with Section 1009.8 <br />5. Please include the existing doors required to have panic hardware (as these will need to <br />be inspected) on the door schedule (includes doors #178, 178AA, 186A, 186B, 186C, <br />187, 187AA, 190 & 190AA). Section 1010.1.10 <br />6. The handrails serving the stage stairs should be shown with extensions past the top of <br />the stairs. Section 1014.6 <br />7. The handrail extension shown at the bottom of the stairs as shown in Section 2 on <br />Sheets A6.01 & A6.02 should be shown to continue at the same slope as the handrail. <br />Section 1014.6 <br />8. Please provide or direct us to a construction detail of the 2nd story guards. Section 1015 <br />9. Braille exit signs stating EXIT should be shown at each exit stairway and exit discharge. <br />Section 1013.4 <br />Accessibility <br />CITY OF EVERETT 9 3200 Cedar Street • Everett, WA 98201 • (425) 257-8813 • RageJ2) <br />