CITY OF EVERETT SPECIAL PROVISIONS <br /> Provide traffic control and expose the water main at the connection allowing <br /> sufficient room for COE forces to make connection, expose the water main at <br /> the connection, including properly shoring and sheeting the excavation in <br /> accordance with requirements of WISHA, RCW 49.17 including WAC 296-155. <br /> Should City personnel determine the excavation and shoring and sheeting do <br /> not meet the requirements of WISHA, RCW 49.17, including WAC 296-155, <br /> City personnel will notify Contractor to make necessary modifications to bring <br /> the excavation and shoring into compliance prior to City personnel entering the <br /> trench. <br /> Repair damage to existing pipe caused by the Contractor's operations at <br /> Contractor's expense. <br /> Proceed continuously once Work is started on a connection without interruption <br /> and as rapidly as possible until completed. City will not permit shutoff of mains <br /> overnight, over weekends, or on holidays. <br /> Notify COE water customers affected by water shut off if the connection to the <br /> existing system involves turning off the water. Provide a minimum of 48-hours <br /> prior notice. The Engineer will advise which property owners to notify. <br /> Depending upon the number of water customers affected by a shut-off, <br /> Contractor may need to perform the connection during times other than normal <br /> working hours. Do NOT operate valves on the existing system. Only City <br /> Utilities Department personnel may operate water system valves. <br /> Refer to 7-12.3 of these Special Provisions for tapping assembly connections, <br /> if any. <br /> 7-09.3(21) Thrust Blocking <br /> Revise the first sentence of the first paragraph to read as follows: <br /> Place concrete thrust blocking, as noted on the Plans and described in these <br /> Special Provisions, at bends where new ductile iron pipe connects to existing cast <br /> iron pipe. 111 <br /> Supplement 7-09.3(21) by adding the following: <br /> Provide mechanical joint restraining devices in place of concrete blocking on all <br /> fittings connecting ductile iron pipe to ductile iron pipe. <br /> Where shown on the Plans or as allowed by the Engineer, provide concrete thrust <br /> blocking at bends, tees, plugs and crosses, including City installed fittings. Provide <br /> cast-in-place concrete thrust blocking having a minimum of 1/4-square foot bearing <br /> against the fitting and minimum two square feet bearing against undisturbed soil <br /> and be clear of joints so as to permit taking up or dismantling joint. Provide a <br /> minimum measurement of 12-inches between the pipe and the undisturbed bank <br /> for all poured in place concrete thrust blocking. Form concrete blocking and pour <br /> using commercial concrete. Place blocking between solid ground and the fitting to <br /> be anchored with the area bearing on the pipe and on the ground in each instance <br /> being as Shown or directed by the Engineer. Place the blocking, unless otherwise <br /> shown or directed, so that the pipe and fitting joints, including nuts and bolts, can <br /> be accessible for repair. <br /> 7-09.3(22) Blowoff Assemblies <br /> Revise the first paragraph under 7-09.3(22) to read as follows: <br /> Construct Blowoff Assemblies at the locations shown on the Plans and in <br /> accordance with COE Standard Drawing No. 511. <br /> 7-09.3(23) Hydrostatic Pressure Test <br /> Supplement 7-09.3(23) by adding the following: I <br /> Water Main Replacement"V" Division 7—STORM,SEWER,WATER April,2021 <br /> WO No.—UP3730 SP—174 ' <br />