APPLICABLE CODES ALLOWABLE AREA CALCULATIONS EXISTING BUILDING & ADDITIONS OCCUPANCY CALCULATIONS <br /> 2015 INTERNATIONAL BUILDING CODE(IBC)WITH APPENDIX G, FLOOD RESISTANT CONSTRUCTION,AND • i' <br /> 1-2 OCCUPANCY EXISTING BUILDING SECTION"A" I-2 OCCUPANCY BUILDING ADDITION"E"(SOUTH ADDITION) NORTH ADDITION <br /> APPENDIX J,GRADING,AS ADOPTED BY THE CITY OF EVERETT. TABULAR ALLOWABLE AREA= 38,000 S.F. TABULAR ALLOWABLE AREA= 38,000 S.F. <br /> 2015 INTERNATIONAL EXISTING BUILDING CODE(IEBC) ALLOWABLE AREA ROOM NUMBER ROOM NAMES FUNCTION OF OCCUPANCY AREA NO. NO.OF NO.OF <br /> ALLOWABLE AREA AND USE SPACE LOAD B.F. OCCUPANTS EXITS EXITS <br /> ALLOWABLE AREA CALCULATED PER 2015 IBC 40,859 S.F. ALLOWABLE AREA CALCULATED PER 2015 IBC 40,080 S.F. <br /> 2015 INTERNATIONAL FIRE CODE(IFC) TABLE 506.2 with 506.2.1 and 506.3 MODIFICATIONS TABLE 506.2 with 506.2.1 and 506.3 MODIFICATIONS FACTOR REGt'D PROVIDED <br /> RES.ROOM A -INSTITUTIONAL SLEEPING 120 228 2 EACH 1 EACH 1 EACH ■ v 2015 INTERNATIONAL MECHANICAL CODE(IMC) RES.ROOM B INSTITUTIONAL SLEEPING 120 228 2 EACH 1 EACH 1 EACH <br /> A a = At + [ Ns * If ] A a = Allowable Area per/floor A a = At + [ N s * If ) A a = <br /> 40,859Allowable Area per/floor RES.ROOM C INSTITUTIONAL SLEEPING 120 393 3 EACH 1 EACH 1 EACHarcHILect ,) ,... <br /> 2015 INTERNATIONAL ENERGY CONSERVATION CODE(IECC) 40,0$0 <br /> 530/531 CORRIDOR INST. INPATIENT 240 1815 8 1 3 <br /> If = F * W - Tabular Areaperlfloor(SeeTable506.2) - F * W Tabular Area per/floor 131 CORRIDOR INST. INPATIENT 240 220 1 1 1 <br /> p Sea t I e Ave E., Ste A <br /> 2012 WASHINGTON STATE ENERGY CODE(WSEC) 1928P - 0.25 1 30 A t - 38,000 i f [ p - 0.25 j • 30 A t 38,000 132 STORAGE ACC.STORAGE/EQUIP. 300 41 0 1 1 Seattle ,a t t l e , WA 9 8 1 1 2 <br /> 400 * 30 _ Area Increase Due to Frontage _ 219 * 30 _ Area Increase Due to Frontage 133 STORAGE ACC.STORAGE/EQUIP. 300 29 0 1 1 <br /> 2009 ICC/ANSI A117.1 STANDARD"ACCESSIBLE AND USABLE BUILDINGS AND FACILITIES" i f = ( 726 0.25 7 30 1 f 0.300964 I f - [ 0.25 j I t - ( 2 0 6) 4 5 3 • 4 0 5 3 <br /> 467 30 0.218951 <br /> 540 LIVING ROOM INST. INPATIENT 240 288 1 1 1 s h o e s m i t h c o x. c o m <br /> WASHINGTON ADMINISTRATIVE CODE(WAC)388-97-NURSING HOMES I f = = Tabular Area for NonsprinkleredBullTiog(Table 506.2) 539 DINING ROOM INST. INPATIENT 240 418 2 1 2 <br /> [ 0.551 0.25 ) 1 N s 9,500 I f = [ 0.469 - 0.25 1 1 Na = Tabular Area for Nonsprinkiered Building(Table 606.2) 538 SERVING KITCHEN INST. INPATIENT 240 90 0 1 2 <br /> 2012 NATIONAL FIRE PROTECTION ASSOCIATION(NFPA)99 9,500 532 MED ROOM ACC.STORAGE/EQUIP. 300 74 0 1 1 <br /> I f = 0.30096 p = Building Perimeter = = Building Perimeter <br /> 533 NURSE BUSINESS ACC. 100 106 1 1 1 <br /> If 021890 p 467 534 TOILET INST. INPATIENT 240 57 0 1 1 <br /> ,/� Aa = 38,000 + = Building Perimeter 535 SHOWER INST. INPATIENT 240 72 0 1 1 <br /> IEBC C O M P L IA N C I y 1 T D [ 9,500 * 0.301 1 F 400 A a = 38,000 [ 9,500 * 0.219 j F = Building Perimeter open to Public Way or open space of 20'or greater 536 CLEAN UTILITY ACC.STORAGE/EQUIP. 300 55 0 1 1 <br /> 218 <br /> 537 SOILED UTILITY ACC.STORAGE/EQUIP. 300 118 0 1 1 <br /> A a = 38,000 + 2 g5g = Width of Public Way oropen space min.20feet,max.30 feet A a = 3$,000 + [ 2,0$0 ) W _ Way <br /> f 1 W _ Width of Public or open space min.20 feet,max.30 feet 541 DEN INST. INPATIENT 240 144 1 1 1 <br /> WORK WILL COMPLY WITH IEBC 301.1.2-WORK AREA COMPLIANCE METHOD AND INCLUDES: <br /> 30 543 CORRIDOR INST. INPATIENT 240 158 1 1 1 <br /> A a = 40,859 <br /> ADDITIONS PER IEBC 1101 Aa = 40,080 542 CONFERENCE BUSINESS ACC. 100 288 3 1 1 <br /> W = [(8`20)+(56*88)+(33*53)+(9*121)+(8*44)+(7*129)+(2T38)+(68`147)+(106*105)+(27*40)+(7*34)+(8*48)+(8*26)+(26*54)]/400 W = [(24*44)+(143.5*41)+(11'100)+(12.5'S2)+(28'88)]/219 TOTAL: ( 451 <br /> THE WORK INCLUDES CREATION OF TWO 1-2,TYPE V-A,SPRINKLERED ADDITIONS TO THE w = 86.6175 > 30 so value is 30 W = 50.9292 > 30 so value Is 30 <br /> EXISTING 1-2,TYPE V-A,SPRINKLERED NURSING HOME BUILDING. THESE ADDITIONS ARE <br /> Y SEPARATED FROM THE EXISTING CONSTRUCTION BY THE CREATION OF NEW 2-HOUR FIRE SOUTH ADDITION <br /> WALLS ALONG AN IMAGINARY PROPERTY LINE BETWEEN THE EXISTING BUILDING AND ACTUAL EXISTING BUILDING SECTION"A"AREA <br /> ADDITIONS PER CS1.02,CS1.03,WALL TYPE F/A10.01,AND ASSOCIATED DETAILS ON A8.03 17,019 S.F. ACTUAL SOUTH ADDITION"E"AREA ROOM NUMBER ROOM NAMES FUNCTION OF OCCUPANCY AREA OC EXI OF NO.OF <br /> AND USE SPACE LOAD S.F. OCCUPANTS EXITS EXITS <br /> AND A10.04. 6,901 S.F. <br /> A e = 17,019 A e = Actual Existing Building Area FACTOR REI 'D PROVIDED <br /> THE ADDITION DOES NOT INCREASE THE HEIGHT OF THE EXISTING BUILDING PER IEBC 1102.1. 17,019 A n - 6,901 A n -_ Actual New Building Area RES.ROOM A INSTITUTIONAL SLEEPING 120 228 2 EACH 1 EACH 1 EACH <br /> SEE AREA CALCULATIONS ON THIS SHEET FOR COMPLIANCE WITH IEBC 1102.2 6,901 RES.ROOM B INSTITUTIONAL SLEEPING 120 228 2 EACH 1 EACH 1 EACH <br /> 1-2 OCCUPANCY EXISTING BUILDING SECTION"B" RES.ROOM C INSTITUTIONAL SLEEPING 120 393 3 EACH 1 EACH 1 EACH <br /> THE ADDITIONS HAVE BEEN DESIGNED TO THE STANDARDS OF THE 2015 IBC PER IEBC 1103.1 TABULAR ALLOWABLE AREA= 38,000 S.F. REVIEW EW 642 STORAGE ACC.STORAGE/EQUIP. 300 54 0 1 1 630,631,632 CORRIDOR INST. INPATIENT 240 1844_ 8 1 2 <br /> B U I L D I N G CODE R <br /> THE ADDITIONS MEET THE MINIMUM REQUIREMENTS FOR ACCESSIBILITY AND ACCESSIBLE ALLOWABLE AREA 641 SERVING KITCHEN INST. INPATIENT 240 94 0 1 2 <br /> DWELLING UNITS AND SLEEPING UNITS PER IEBC 1105.1 AND 1105.2. ALLOWABLE AREA CALCULATED PER 2015IBC 36,965 S.F. 640 DINING ROOM INST. INPATIENT 240 317 1 1 2 II`' <br /> TABLE 506.2 with 506.2.1 and 506.3 MODIFICATIONS 639 LIVING ROOM INST. INPATIENT 240 204 1 1 1 • <br /> '' <br /> ALTERATIONS-LEVEL 2 PER IEBC 504 BETHANY SKILLED NURSING SECTION D(NORTH)ADDITION 638 NURSE BUSINESS ACC. 100 117 1 1 1 <br /> THE WORK INCLUDES RECONFIGURATION OF SMALL AREAS OF THE EXISTING BUILDING WHERE A a = At + [ Ns i f ] A a = Allowable Area per/floor Identify all use and occupancy classification ACCESSORY 637 MED ROOM ACC.STORAGE/EQUIP. 300 72 0 1 1 <br /> 36,965 group(s)In the Building(i.e.B,M,R-2,A-3,etc.) 1-2 B STORAGE IT ATTACHES TO THE NEW ADDITIONS. THIS SCOPE OF WORK INCLUDES ALTERATIONS TO636 TOILET INST. INPATIENT 240 68 0 1 1 <br /> NO per IBC 508.2.4 because these are AN EXISTING DAY ROOM, RESIDENT ROOM AND CONFERENCE ROOM TO CREATE EXIT CORRIDORS I f = [ r 0.25 W Tabular Areaperlfloor(See Table Separated Uses? 635 SHOWER INST. INPATIENT 240 76 0 1 1 • <br /> Accessory Occupancies 634 CLEAN UTILITY ACC.STORAGE/EQUIP. 300 39 0 1 1 •' • <br /> FROM THE NEW ADDITIONS AND THE RELOCATION OF WINDOWS IN ANOTHER RESIDENT ROOM. P30 A t 38,000 List Construction Type(s)used in the design: <br /> 102 30 Area Increase Due to Frontage (IA,11Jt3,VA,etc.): V-A 633 SOILED UTILITY ACC.STORAGE/EQUIP. 300 117 0 1 1 <br /> THE NEW ADDITIONS ARE DIVIDED FROM THE EXISTING BUILDING BY A 2-HOUR FIRE WALL AND I f = [ 723 -0.25 ] 30 If = -0.108921 <br /> SMOKE BARRIER TO KEEP THEM AS SEPARATE SMOKE COMPARTMENTS PER iEBC803.3Allowed Proposed C CORRIDOR INST. INPATIENT 240 395 2 1 2 <br /> [ 0.1411 -0.25 I 1 Na = Tabular Area for Nonsprinklered Building(Table 506,2) Number of Stories(per IBC Table 504.4) 1 1 TOTAL: I I 41" 2235 Lake Heights <br /> �e i h# rive <br /> . THE INTERIOR FINISH OF WALLS AND CEILINGS IN THE NEWLY CREATED EXITS AND CORRIDORS 1 f 9,500 fl <br /> SHALL COMPLY WITH THE REQUIREMENTS OF THE 2015 IBC PER IEBC 803.4 Is there a basement? NO <br /> Everett WA 98208 <br /> I f = 0.10892 p = Building Perimeter <br /> 723 <br /> AN APPROVED AUTOMATIC SPRINKLER SYSTEM IS INSTALLED THROUGHOUT THE EXISTING EXITING CALCULATIONS <br /> BUILDING. NEW SPRINKLER HEADS SHALL BE INSTALLED IN ALL RECONFIGURED SPACES PER Aa = 38,000 + [ 9,500 * -0.109 1 F = Building Perimeter open to Public Way or open space of 20'or greater <br /> IEBC 804. 102 Is an Automatic Sprinkler System Per NFPA 13 Provided Throughout? YES <br /> SEE CS1.02 AND 1.03 FOR COMPLIANCE WITH IEBC 805 A a = 38,000 + [ -1,035 _ Widih of Public Way or open spars min.20feet,max.30 feet Number of Exits Total <br /> j W _ 3p Are Quick Response Heads Provided Throughout? YES Occupancy Number of Exits Exit Width <br /> and Exit Width Occupant Stairs Other Egress Components <br /> Are Quick Res onse Heads Provided Per Occu anc YES from Each Level Type Load Required Provided Required Provided Required Provided <br /> A a = 36,965 p P I-2 40 12,0 _ 8.0 38"min.;88" <br /> Is an Automatic Sprinkler System Used in Place of 1-Hour Construction? NO NORTH ADDITION B 4 2 2 1.2 - <br /> N/A 0.8 at resident <br /> 1(20*110)+(8`20)+(48*102)+(8*20)+(20'110)]/102 <br /> Are Resistance of Exterior Walls <br /> STORAGE 1 0.3 0.2 corridors <br /> Based on Fire Separation Distance(per IBC Table 602 Opening Protection <br /> W = 94.2745 > 30 so value is 30 ) Rating (Table 705.8) Number of Exits Total 3 Wall and Fire Separation Distance: Exit Width <br /> and Exit Width Occupancy Occupant Number of Exits <br /> 1)North >_30' p Stairs Other Egress Components <br /> 0-hr UP,S-No Limit from Each Level Type Load Required Provided Required Provided Required Provided <br /> ACTUAL EXISTING BUILDING SECTION"B"AREA 1-2 38 11.4 7.6 36"min.;98" <br /> 12,838 S.F. 2)South 10's X<30' 1-hr UP,S-No Limit SOUTH ADDITION B 1 2 2 0.3 N/A 0.2 at resident <br /> Actual A e = 12,838 = Act Existing Building Area 3)East 10's X<30' 1-hr UP,S-No Limit STORAGE 1 <br /> A e dual 0.3 0.2 corridors : <br /> .fit.'• <br /> 4)West 2 30' 0-hr UP,S-No Limit ' 1 <br /> CONFERENCE ROOM ADDITION TO SECTION"B" <br /> 116 S.F. of the Northwest <br /> Fire Resistance Rating Requirements Assembly# <br /> A n = 116Actual New Building Area (per IBC Table 601) Rating Required Rating Provided (SEE A10.01) <br /> y A n = 116 Structural Frame 1 1 NIA EXITING NOTES No. DATE REVISION <br /> TOTAL AREA SECTION"B" Bearing Walls-Exterior 1 1 IBC Table 721.1(2)16- <br /> 12,954 S.F. 1.2 HABITABLE ROOMS SHALL HAVE AN EXIT ACCESS DOOR LEADING DIRECTLY TO A A03.29.2019 CITY RESPONSE#1 <br /> Bearing Walls-Interior 1 1 UL U344CORRIDOR PER 407.4.1. <br /> Nonbearing Walls&Partitions-Exterior 1 1 N/A THE DISTANCE OF TRAVEL BETWEEN ANY POINT IN AN 1-2 OCCUPANCY SLEEPING ROOM <br /> 1-2 OCCUPANCY EXISTING BUILDING SECTION"C" Nonbearing Walls&Partitions-Interior 0 0 AND AN EXIT ACCESS DOOR IN THAT ROOM SHALL NOT BE GREATER THAN 50 FEET PER <br /> TABULAR ALLOWABLE AREA= 38,000 S.F. 407.4.2. <br /> Floor Construction 1 1 <br /> N/A ALLOWABLE AREA SHARED LIVING SPACES,GROUP MEETING OR MULTIPURPOSE THERAPEUTIC SPACES <br /> ALLOWABLE AREA CALCULATED PER 2015 IBC 39,799 S.F. UL P545,IBC TABLE SHALL BE PERMITTED OPEN TO THE CORRIDOR WHERE ALL THE CONDITIONS OF 407.2.5 <br /> TABLE 506.2 with 506.2.1 and 506.3 MODIFICATIONS Roof Construction 1 1 712.1(3),30.1.1 AND ARE MET. <br /> ASTM E-119 <br /> NURSING HOME COOKING FACILITIES WITH DOMESTIC COOKING APPLIANCES SHALL <br /> Aa = At + [ Ns * If I A a = Allowable Area per/floor BETHANY SKILLED NURSING SECTION E(SOUTH)ADDITION BE PERM►TIED OPEN TO THE CORRIDOR WHERE ALL THE CONDITIONS OF 407.2.E ARE <br /> Identify all use and occupancy classification ACCESSORY MET. <br /> I f = I F 0.25 j * W A t = Tabular Area per/floor(See Table 506.2) group(s)in the Building(Le.B,M,R•2,A-3,etc.) 1-2 B STORAGE <br /> P 30 38,000 NO per IBC 508.2.4 because these are A 50'MAXIMUM DEAD END CORRIDOR IS ALLOWED PER IBC 1018.4,EXCEPTION 2, <br /> Separated Uses? <br /> 435 30 Accessory Occupancies BECAUSE THE BUILDING UTILIZES A NFPA 13 SPRINKLER SYSTEM <br /> I f = [ -0.25 1 * I f = Area Increase Due to Frontage List Construction Type(s)used in the design: <br /> 990 30 0.189394 9 <br /> (IA,NB,VA,etc.): <br /> V-A <br /> I f = * = Tabular Area for Nonsprinklered Building(Table 506.2) Allowed Proposed PROJECT MANAGER <br /> ( 0A394 -0.26 1 1 N s <br /> 9,500 <br /> P = Building <br /> Perimeter <br /> Number of Stories(per iBC Table 504.4) 1 1 PLUMBING FIXTURE CALCULATIONS J s <br /> If = 0.18939 g PROJECT ARCHITECT <br /> 990 NO <br /> Is there a basement? <br /> A a = 38,000 + [ 9,500 * 0.1894 ] F = Building Perimeter open to Public Way or open space of 20'or greater (WAC 51-50-IBC Chapter 29-Washington State Amendments) JS <br /> 435 <br /> PROJECT TEAM MEMBERS <br /> Width of Publicore enOccupancy 1-2 Nursing Home Type TS <br /> A a = 38,000 + [ 1,799 1 W = 30 Way P space win.20 feat,max.30 feet Is an Automatic Sprinkler System Per NFPA 13 Provided Throughout? YES Area Served (14 residents) CHECK <br /> Male Female <br /> A a = 39,799 Are Quick Response Heads Provided Throughout? YES Required 1 per room <br /> W = [(25`274)+(6*68)+(65`268)+(66'133)+(4'202)+(58*137)+(9*144)+(38`145)+(44`106)+(8`20)+(56`$8)+(33*53)+(9*2,)+(8*44)+(7*129)+(27*38)j/435 Are Quick Response Heads Provided Per Occupancy? YES Total Number of Water Closets Provided 13 <br /> Accessible 7 <br /> W = 144.798 > 30 so value is 30 is an Automatic Sprinkler System Used in Place of 1-Hour Construction? NO Required 1 per room <br /> ARCHITECT SEAL <br /> Are Resistance of Exterior Walls <br /> Opening Total Number of Lavatories Provided 15 <br /> ACTUAL EXISTING BUILDING SECTION"C"AREA Based on Fire Separation Distance(per IBC Table 602) Rating Protection(Table Accessible 15 <br /> Wall and Fire Separation Distance: 705.8) Required 1 per 15 7534 <br /> 23,043 S.F. Bathtub or Shower Provided 1 REGISTERED <br /> 1)North 10'S X<30' 1-hr UP,5-No Limit <br /> Actual Building Area Accessible 1 <br /> ___ ARCHITECT <br /> A c = 23,043 A = <br /> 23,043 2)South 3 30' 0-fir UP,S-No Limit <br /> / <br /> #Occupancy is determined based on 2015 International Building Code WAC 1-5- <br /> 3)East >_30' 0-hr UP,S-No Limit Section 2902.1 -� - - 1 <br /> 1-2 OCCUPANCY BUILDING ADDITION"D"(NORTH ADDITION) JOHN A. SHOESMITH <br /> 4)West 10'5 X<30 1-hr UP,S•No Limit STATE OF WASHINGTON <br /> TABULAR ALLOWABLE AREA= 38,000 S.F. <br /> ALLOWABLE AREA <br /> ALLOWABLE AREA CALCULATED PER 2015 IBC 41,187 S.F. Fire Resistance Rating Requirements Rating Required Rating Provided Assembly# <br /> TABLE 506.2 with 506.2.1 and 506.3 MODIFICATIONS (per IBC Table 601) (SEE A10.01) ACCESSIBILITY NOTES <br /> Structural Frame 1 1 <br /> N/A 1. INTERIOR FINISH MATERIALS SHALL COMPLY WITH IBC CHAPTER 8 FOR 1-2 . < 0 �� F..f _: <br /> A a = At + [ Na * If I A a = 41,18bleAreaper/floor Bearing Wails•Exterior 1 1 IBC Table 721.1(2) OCCUPANCIES AND WASHINGTON STATE DOH REQUIREMENTS FOR LICENSED f's 1; f' ;,?'^"''", i;. pr''t , <br /> 16-1.2 NURSING FACILITIES. ��' � �L.. L' l'-:`% :' t.)4 J `J1, k, '�i? <br /> if = [ F -0.25 1 * W At = Tabular Area per/floor(SeeTable506.2) Bearing Walls-Interior 1 1 UL U344 2. ALL INTERIOR AND EXTERIOR WALKING SURFACES MUST BE SLIP-RESISTANT <br /> P 38,000 <br /> Nonbearing Walls&Partitions-Exterior 1 1 FINISH. PROVIDE MANUFACTURERS LISTING INFORMATION TO INSPECTOR AT <br /> I f = 258.5 * _ Area Increase Due to Fronta N/A IC TITLE <br /> ( 441.5 0.25 ] 30 1 i - 0.335504 TIME OF INSPECTION. C-A117.1-09 CHAPTER 3 AND 4 AND IBC SECTION 1003.4. /� j� <br /> Nonbearing Walls&Partitions-Interior 0 0 3. PROVIDE ACCESSIBLE INFORMATION SIGNS PER IBC SECTION 1110. C O D I N F O RMAT I N <br /> I f = [ 0.5855 -0.25 ] 1 N a = Tabular Area for Nonsprinklered Building(Table 506.2) Floor Construction 1 1 4. PROVIDE ACCESSIBLE CONTROLS,OPERATING MECHANISMS AND HARDWARE <br /> 9,500 <br /> N/A <br /> Building Perimeter UL P545,IBC PER IBC SECTION 1109.13, INCLUDING THERMOSTATS,RANGE HOOD FAN AND <br /> I f = 0.3355 p = 441.5 Roof Construction 1 1 TABLE 712.1(3),30• LIGHT CONTROLS. <br /> 1.1 AND ASTM E- <br /> A a = 38,000 + ( 9,500 * 0.3355 I F = Building Perimeter open to Public Way or open space of 20'or greater <br /> 5. PROVIDE ACCESSIBLE STORAGE PER IBC SECTION 1109.9 <br /> 258.5 PROJECT NO. <br /> 6. SEATING AT TABLES,COUNTERS AND WORK SURFACES-WHEN PROVIDED- <br /> A a = 38,000 + [ 3,187 ] w = Width of Public Way or open space min.20 feet,max 30 foot SHALL REPRESENT AT LEAST 5%OF SUCH FACILITIES BUT NOT LESS THAN 18.03-01 <br /> 30 ONE PER IBC SECTION 1109.11 DATE <br /> A a = 41,1$7 7. SINKS-WHERE SINKS ARE PROVIDED,AT LEAST 5%BUT NOT LESS THAN ONE 12/21/2018 <br /> SHALL BE PROVIDED IN AN ACCESSIBLE SPACE PER IBC SECTION 1109.3 PROJECT NETWORK PATH <br /> W = ((104*44)+(11*74)*(12.5*55.75)+(28*83)+(12.5`65)+(,1*1p6.5)+(26`54)+(39.5*251)+(14*275)j/441.5 8. WHERE KITCHENS AND KITCHENETTES ARE PROVIDED IN ACCESSIBLE SPACES <br /> w = 57.9012 > 30 so value is 30 OR ROOMS THEY SHALL BE ACCESSIBLE PER IBC SECTION 1109.4. <br /> ACTUAL NORTH ADDITION"D"AREA <br /> SHEET NUMBER <br /> 7,336 S.F. <br /> A n = 7,335 A n = Actual New Building Area <br /> I <br /> 7,336 <br /> t <br /> COPYRIGHT©2019 shoesmith cox architects <br />