|
V
<br /> I ° ff! OCCUPANCY GROUPS KEYs\ / / _ ____, - ,.._, .,........_A,._
<br /> shoesmith
<br /> ® A - SKILLED NURSING I-2,CONDITION 1
<br /> f
<br /> ,H..
<br /> fT 0 �j O O O A O O 1.1 O 0.5 1 Old E1 E2 E3 BUSINESS B
<br /> C 0 X
<br /> -1/1
<br /> / J
<br /> f _ K - - - - _ __ ACCESSORY STORAGE ' c�
<br /> � - arculiectoci.=
<br /> f 12'6' 13'-0" 13'-6" 8'-6 3/4" 13-6" 13'-6" 13'-6" 13'-3 7/8" 14'-T LL 2B 5 " 8'-2" / 26'-51/8'
<br /> f
<br /> ........ i 2a -.. -- OCCUPANCY SEPARATION REQUIREMENTS
<br /> f I I I____te---_ .
<br /> II I ( 1 HOUR SEPARATION REQUIRED AT HAZARDOUS INCIDENTAL AREAS 1928 43rd Ave E., Ste A
<br /> f/ I I I EA I I I I _ ._.. ___, IBC TABLE 509 Seattle , WA 98112
<br /> a ' ( 206 ) 453 . 4053
<br /> �� f IL VIIII shoesmithcox . com
<br /> / 1 DS• DSO 1 DS II Ir- 2'. I GENERAL NOTES
<br /> / / . iir°` II ��' RESIDENT I I„ I 1. BUILDING IS FULLY SPRINKLED PER NFPA 13
<br /> // / '. �- - I r o1 © ( (- - ROOM 5010 NTH RESIDENT RESIDENT-1 D n r RESIDENT Q ROOM I ( I
<br /> 2. PORTABLE FIRE EXTINGUISHERS SHALL HAVE A MINIMUM
<br /> / / .` L - - - _I _ hi
<br /> LI 511 �jU U� - 509 ( I L 11-.I NMI lI 503 I )4�I U� �I I L " U.L.CLASSIFICATION OF 2 A 10 BC
<br /> / / r - \ / ( ,/ - \ / � '�; - \ - )y f 3. ALL FIRE EXTINGUISHERS SHALL BE HUNG IN A CONSPICUOUS
<br /> / °, 1 r CORRIDOR Imo -1 r 1 / - 1 LOCATION SO THEIR TOPS ARE 54-60 INCHES ABOVE
<br /> / .` N - \ 0 _ - - L 5 *� } ' I THE FINISHED FLOOR PER I.F.C.906.9.1
<br /> ' COMPANION 1- '
<br /> - - i
<br /> _ 4. TRAVEL DISTANCE TO ANY EXTINGUISHER SHALL
<br /> f o
<br /> ' ROOM ��^ I ( •� V , I I
<br /> I® 10O + 0 I C' L. - -� 1 ` - w NOT EXCEED 75' 0", MIN. 1 EXTINGUISHER FOR 6,000 SF
<br /> 2 RESIDENT I &MAX 150'APART IN CORRIDORS PER IBC 906.3
<br /> F 7- r II b I 1 b 3 m RESIDENT SENT t- ROOM
<br /> I' • -I 0 11 0 I. 0 hL---IIIIk o o ' W Q ,tr._a I - I L .• U 5. PORTABLE FIRE EXTINGUISHERS HAVING A MINIMUM
<br /> A \ 10 .„` - I k` " I U.L.CLASSIFICATION OF 40 POC SHALL BE PROVIDED
<br /> I_ -----1-16,1
<br /> I N CO WITHIN 30 FEET OF COMMERCIAL COOKING EQUIPMENT
<br /> I /` A� v �,�� ]�� 0 lO 0 8 a 1,-,, 6. FIRE EXTINGUISHER CABINETS LOCATED IN FIRE RATED
<br /> II o _ - - - - L J I - , ' CORR DO- 4 k,, _ i:1 11
<br /> CORRIDOR WALLS SHALL HAVE CONTINUOUS WRAP OF
<br /> - z O 0 5 j - - J o - O O O 4 m - © j TOP. m I 1[ GYP.BD. BEHIND CABINET. SEE DETAIL 3/A9.01
<br /> _ _ - © © e + '
<br /> - � � � � '� s?oR � 7. SEE A2.01 FOR LOCATION OF EXISTING SPACES REQUIRED BY
<br /> :® �� o\ J f/ I I� 1r%_17--7 )
<br /> J r SHOWER o r a ='-----
<br /> .� �� r o ���33 _ WAC 388 97 THAT SUPPORT THIS ADDITION BUT ARE LOCATED
<br /> I- -1 a I
<br /> 0 ) � 11I (� ® � II � `I=l' - J \ I � � - ELSEWHERE WITHIN THE EXISTING NURSING HOME
<br /> WARDROBE � -
<br /> ORRIDO
<br /> _ _ "�' �� 1.---t.- LJc�PA_d+IbN_ � II � �-
<br /> _, WARDROBEto ROOM -� _ - I N_UF:.E I I \I �iTIL� O .UT:L./ �, 00 ' OO (o a
<br /> � - � � F1 ,- HS!CPG. �
<br /> RESIDENT °® 11.0�18 � '�r' , 1) 33J I war �, T.
<br /> \ L 35 r . o f s37 `j 0
<br /> ROOM ° -� I, I M�J I \ - ■ `- _
<br /> I 1101 � � °, �.�'` `-�' �- 0 1 r- � I �32 Ali ,, _ i ! -� � .7.,
<br /> ----m- � - - - - SMOKE COMPARTMENTS
<br /> - ' ° L_ + - 1j �' , f SMOKE COMPARTMENT REQUIREMENTS(IBC 407.5 AND 709)
<br /> 3 Ds L --
<br /> I I BED N.
<br /> ° ,_ ) �R N - - _- - L -i- di, 6 2.'-9 1/2"<50'SO NO DEAD END CORRIDOR
<br /> beth a ny
<br /> ° • L _ Q -� 1 9 6ips°
<br /> i - - BEDSIDE TABLE `° f-lll 1512 I Ii \ °'` �© - V MAXIMUM TRAVEL PATH LENGTH ALLOWED=200' skilled nursing
<br /> tESiDE lv e RESIDENT MAXIMUM AREA ALLOWED=22,500 SF.
<br /> �o ROOM ROOM
<br /> I '` ` ( L - �U L 0 / ATIVITY 0 I- 6 ACTUAL MAXIMUM LENGTH= 85'AT SECTION C,THEREFORE OK additions
<br /> ° I - ,� 12 KI CHEN R:,.IDE 1T +/-1 -10"
<br /> -fie L�pp ` V538 1 111.1 + 'OOM' A' ACTUAL MAXIMUM AREA= 10,983 SF AT SECTION A,THEREFORE OK
<br /> I dL
<br /> 7 - - _ I� - -
<br /> BED OD °,°t I !..._..,
<br /> �- I.\ �� OI 0 ►�__ I- - - `, I D �I
<br /> I I DS _ --- ---- I I o .-.-_ I �lt
<br /> - - U� BEDSIDE TABLE c.a `° ♦ - - - �- - - - -
<br /> ', L - -N - - - -�- p - it I DS z 2235 Lake Heights Drive
<br /> 226 S.F SEABLE t T 0 �- J " J
<br /> `� � � o � II � � RATED ASSEMBLIES
<br /> ° ° 640 S.F./14 RESIDENTS= I (� �I I $�,LL w LL Ln Y }}
<br /> I a, t ♦ 46S.F./PERSON i ` n oo a0 coo t Everett WA �a�o�
<br /> O a°% DINING I 4}-� ffEESIDENT - - v LL I 11
<br /> kN o 1- o RESIDENT RESIDENT IBC WALL TYPE WALL ASSEMBLY DOOR RATING
<br /> co
<br /> ° IIII� 11 0 OOM o o N II v'fr ROOM CORRIDOR ROOM
<br /> USEABLE FLOOR AREA ', N 1 4 . I x A NB 1-HOUR SMOKE BARRIER PER 709 UL 344 45 MIN PER TABLE 716.5
<br /> e PER WAC 388-97-2240 "� - - - a 40 O
<br /> �� - - °ps nn ? C I v, 1-HOUR SMOKE PARTITION PER 710 UL 344 0 MIN.AT CORRIDOR WALLS PER 407.3.1
<br /> ,J''' " a , i I z RESIDENT RESIDENT
<br /> DS a I o - J z ROOM ROOM
<br /> Li-LL �� -` a d 1� I ,__ 1-HOUR FIRE BARRIER PER 707 UL 344 45 MIN.PER TABLE 716,5
<br /> BED o nr�l r--un ® I EoiC O ce
<br /> o o Q I o (_ ...-._..
<br /> BEDSIDE TABLE n PATIO ,'tei. I '� `�I <a LL I I I LL LL
<br /> o DO �r M <<o 0 0 2-HOUR FIRE WALL UL 301 90 MIN.PER TABLE 716.5
<br /> ° I 0 531 1 i1s, ` WEN I ¢a o +/-2'-10" Jr' LI OA
<br /> WARDROBE _ _ l°J RESI�ENT�� i..r;� a•---- ' _ + aao
<br /> CHAIR (NOT SHOWN) m 71�i Room-(11-IJ ``� X`° ( I �- I� - I I!
<br /> FURNISHED BY - L_I 511 u� ' I540 LIVING - I_ -3.=ey. I -1 [- i
<br /> RESIDENT ; °. Q - - - - - a - ri
<br /> KEY NOTES
<br /> 115 S.F.USEABLE % �� ' � DSff
<br /> DS 142 S.F. USEABLE I , a Bt y
<br /> AREA OF WALL=9'-3"X1 r a'=1oa s.F. I I I I I I - FIRE EXTINGUISHER CABINET
<br /> t ',8 A R E A O PENI N GS=21.25 SF. I I O
<br /> n e 0 �, I °k OF AREA=20%<45% A N 1 I� If e SEE DETAIL 3/A9.01
<br /> COMPANION %1 ,, SO OK i I _ I I RESIDENT = -`-- RESIDENT
<br /> ROOM - _ _j_ �i II TE _ ROOM ROM 0 of the Northwest
<br /> ILLUMINATED EXIT SIGN
<br /> 513 0 t` - - '•� DS° - - - - Ih NO. DATE REVISION
<br /> C r © ASSUMED U II I
<br /> ti ` i PROPERTY E q p- - 0 EXISTING EXIT SIGN
<br /> L� '� - -I t! t - - - --AN-- P 6 I I. 4 II= If -I RESIuLt4, RESIDENT
<br /> -1 4. r , • 0 N _ - ROOM ROOM DOOR WITH MAGNETIC HOLD OPEN/STANDARD CLOSER
<br /> I - I VI I '`' © 54N I �' -�� 1 'il li i MB 1 I I I II © DOOR CLOSING PER IBC 716.5.9 DOH CRS RESPONSE#1
<br /> 139S.F.U�EABLE OIL - - - - �_ 0 I 0 N -! I f ICII I = = SMOKE ACTIVATED AUTOMATIC CLOSING DOORS PER IBC 716.5.9.3A01.28.2019
<br /> l
<br /> 1 = O DOOR WITH STANDARD CLOSER 03.07.2019 DOH CRS RESPONSE#2
<br /> I
<br /> A
<br /> p ,
<br /> _ A I O 10 0 I 0 1 0
<br /> l�J ],\ )L V I 1 ASSUMED PROPERTY LINE o °Ds e I° 0,0 0 DOOR WITH ELECTRONIC FREE ARM CLOSER
<br /> ____ ..., .... ____ ____ A�, 03.29.2019 CITY RESPONSE#1
<br /> r _ 4 SMOKE BARRIER 90 AREA OF OPENINGS AREA OF AL= = (3 x8'=384 384 S.F.
<br /> 37.5 S.F. EXISTING SM.... OKE BARRIEL7- Pin
<br /> R n 4 EXIISSTIIING SMOKE BARRIER
<br /> O PANIC HARDWARE EXIT DEVICE
<br /> *� , A , 0 /oOF AREA= 36/°<45/oSOOK TUB DOR 19-14 RESPONSE
<br /> ' (' _ 0EXISTING � � 1 HOUR FIRE BARRIER AT INCIDENTAL USESUNIT INFORMATION d TABLE509A04.10.2019
<br /> e 1 I e I I O PER IBC 05.30.2019 CITY RESPONSE#2
<br /> SECTION A(NORTH)ADDITION SECTION C(SOUTH)ADDITION ; I CONFERENCE ' RESSI'"I` RESIDENT RESIDENT I I I 0 CORRIDOR WALL TO BE CONSTRUCTED AS SMOKE PARTITION PER IBC 710
<br /> 1` RESIDEN 1'
<br /> Kai I R ROOM ROOM ISOLATION OFFICE S.UTIL. ROOM
<br /> PRIVATE 10 PRIVATE 10 , I0 1-HOUR FIRE WALL CONSTRUCTED FOR EXPOSURE BOTH SIDES PER IBC
<br /> COMPANION 2 COMPANION 2 a I roll
<br /> IBC 705.3,705.5&705.8
<br /> TOTAL 12 TOTAL 12 0
<br /> -
<br /> 0 1 CLEAN LIN. co 2-HOUR FIRE WALL AT AREA SEPARATION PER IBC 706 3
<br /> 50%BUT NOT LESS THAN ONE OF EACH TYPE ARE REQUIRED TO BE FULLY �' , I7 NURSE WALL DOUBLES AS SMOKE BARRIER PER IBC 709.4.1
<br /> ' STATION OM �� PROJECT MANAGER
<br /> ACCESSIBLE UNITS PER WAC 51-50-1107.5.2.1,THE REMAINDER ARE REQUIRED I OFF I I I I I I
<br /> TO BE TYPE B UNITS PER 1107.5.2.2 ; z- € --- I I PANTRY HSKPG , A= a CO
<br /> I • To :E •- N TO CORRIDOR PER IBC 407.2.5
<br /> I I I MED IL I PROVIDE THE FOLLOWING: JS
<br /> , I EXISTING e PROJECT ARCHITECT
<br /> 9
<br /> 24 x.05=12 UNITS REQUIRED TO BE FULLY ACCESSIBLE I a- a) WALL AND CEILING CONSTRUCTION AS REQUIRED FOR CORRIDORS
<br /> 1 I b) AUTOMATIC FIRE DETECTION SYSTEM INSTALLED PER IBC SECTION 907 AT JS
<br /> 12 FULLY ACCESSIBLE TYPE A UNITS ARE PROVIDED(UNITS 507,509,511-514 AND 8'2" 21'-0" rilTHE SHARED LIVING SPACE AND CORRIDORS ONTO WHICH THE SPACES OPEN
<br /> e90 - _ h PROJECT TEAM MEMBERS
<br /> UNITS 613,615,617-620).THESE UNITS HAVE REQUIRED GRAB BARS AND CLEARANCES. ' I ` p
<br /> CORRIDOR WITHIN THE SAME SMOKE COMPARTMENT.
<br /> ' ,._" ' CORRIDORc) CLEAR ACCESS TO THE REQUIRED EXITS. TS
<br /> SEE PLANS AND 2/A7.01. � I �----
<br /> I 2.9 0 NA
<br /> CHECK
<br /> THE REMAINDER OF THE UNITS ARE B-TYPE UNITS AND HAVE SWING UP GRAB BARS i OFFICE °EXISTING ® COOKING FACILITY PERMITTED TO BE OPEN TO THE CORRIDOR PER IBC 407.2.6
<br /> PROVIDE THE FOLLOWING:
<br /> SEE 3/A7.01.
<br /> I t a) A DOMESTIC COOKING HOOD INSTALLED AND CONSTRUCTED IN '
<br /> A
<br /> r ACCORDANCE WITH SECTION 505 OF THE IMC OVER A DOMESTIC COOKING
<br /> LOCKABLE RESIDENT STORAGE PER WAC 388 97-2560 IS PROVIDED IN THE TOILET ROOM o 10 EXISTING APPLIANCE. THIS DOMESTIC COOKING HOOD SHALL BE EQUIPPED WITH AN
<br /> OF EACH UNIT. SEE 2&3/A7.01 fi4I - SHOWER AUTOMATIC FIRE-EXTINGUISHING SYSTEM TESTED IN ACCORDANCE WITH ARCHITECT SEAL
<br /> T UL300A AND LISTED AND LABELED FOR THE INTENDED APPLICATION.
<br /> WARDROBES ARE PROVIDED IN EACH RESIDENT ROOM PER WAC 388-97-2580. SEE I b) A MANUAL ACTUATION DEVICE FOR THE HOOD SUPPRESSION SYSTEM
<br /> INTERIOR DESIGN DRAWINGS FOR LOCATIONS AND SPECIFICATIONS. I 51-10wER INSTALLED IN ACCORDANCE WITH 904.12.1 AND 904.12.2 7534
<br /> I OFFICE I. I c) AN INTERLOCK DEVICE SUCH THAT UPON ACTIVATION OF THE HOOD REGISTERED
<br /> , -.a . L.,-_ _ I SUPPRESSION SYSTEM,THE POWER OR FUEL SUPPLY TO THE DOMESTIC ARCHITECT
<br /> DEFERRED SUBMITTALS li - -I II RESIDEN-1 RESIDENT RESIDENT _ � COOKING APPLIANCE WILL BE TURNED OFF.
<br /> 7-1
<br /> - ROOM ROOM ROOM LOUNGE _ d) A SWITCH OR STAFF CONTROL LOCATED IN ADJACENT CABINET THAT WILL \
<br /> , , LsT i DEACTIVATE THE DOMESTIC COOKING APPLIANCE WHENEVER NOT UNDER
<br /> I' r � { e I II -LSIDL=NT L _ STAFF SUPERVISION.SWITCH TO BE ON 120 MINUTE TIMER JOHN A. SHOESMITH
<br /> FIRE ALARMiI " �', e) AD
<br /> PORTABLE FIRE EXTINGUISHER INSTALLED IN ACCORDANCE WITH IFC STATE OF WASHINGTON
<br /> FIRE SPRINKLER ,' ' 1,
<br /> A .
<br /> I OFFICE 0i E' REST STATE
<br /> `
<br /> NURSE CALL , - J EXISTING i' Roc
<br /> ' , _ (-1 SECTION 906.
<br /> I - I - ® TOILET ROOM
<br /> CONTRACTOR TO SUBMIT STAMPED AND SIGNED DRAWINGS AND CALCULATIONS , ' U
<br /> J
<br /> FOR DEFERRED SUBMITTALS TO ARCHITECT FOR REVIEW PRIOR TO SUBMITTING '' , I !'!!: = i , - I i'i, 14 EXISTING EGRESS PATH LIGHTING AT BUILDING EXTERIOR LANDINGS
<br /> THEM TO DEPARTMENT OF HEALTH CONSTRUCTION REVIEW AND CITY OF EVERETT `, �' I �� 1-- -
<br /> _- - - ,.,.. .I��T�1,T„rVl[TIAII r.�rr+�- .Irr�eTr.n CITY OF EVERETT
<br /> BUILDING DEPARTMENT.CONTRACTOR MUST OBTAIN DEPARTMENT OF HEALTH , , EXISTING I -- ,ins
<br /> CONSTRUCTION REVIEW AND CITY OF EVERETT BUILDING DEPARTMENT APPROVAL , �I L --I - �'� LEGEND REVIEWED FOR PERMIT
<br /> PRIOR TO INSTALLATION. ' , tf
<br /> _ _n FFIC€
<br /> r I I 10 -.,,� e :µ$r
<br /> t - ..1 EXISTING EXISTING
<br /> j �, - I 17:-; NON-RATED CORRIDOR DOOR ASSEMBLYTITLE
<br /> EXITING NOTES ..~ - :: I . ee.._ PER IBC 407.3.1 CODE PLAN
<br /> I- I I
<br /> 4 ._ I COURTYARD HABITABLE ROOMS SHALL HAVE AN EXIT ACCESS DOOR LEADING DIRECTLY TO A C- ,W .- ,- I
<br /> , r
<br /> CORRIDOR PER 407.4.1. A 14 1a 1a © I CHAPEL 10 I 1.---45
<br /> _ 2e I- - 45 MIN.RATED DOOR ASSEMBLY
<br /> THE DISTANCE OF TRAVEL BETWEEN ANY POINT IN AN I-2 OCCUPANCY SLEEPING ROOM p� -J �� ' r I
<br /> AND AN EXIT ACCESS DOOR IN THAT ROOM SHALL NOT BE GREATER THAN 50 FEET PER I PROJECT NO.
<br /> 407.4.2. ' I IIII - ." [W.
<br /> 18.03-01
<br /> I „ - - - - 90 MIN. RATED DOOR ASSEMBLY
<br /> SHARED LIVING SPACES,GROUP MEETING OR MULTIPURPOSE THERAPEUTIC SPACES ,°� ,'' �� fir'' ''� g�' -I L J I _ �- -- q -
<br /> -7 s! IE -1I -11- F _ _ DATE
<br /> SHALL BE PERMITTED OPEN TO THE CORRIDOR WHERE ALL THE CONDITIONS OF 407.2.5 � � ® .r
<br /> ARE MET. . ,, \\ I 1-HR. RATED EXIT CORRIDOR(PER IBC 407.3)ALL 12/21/2018
<br /> ' • I(-- -'r` - - -�- -IL - L. \ / II I OPENINGS TO LIMIT THE PASSAGE OF SMOKE AND PROJECT NETWORK PATH
<br /> I 1111 / BE POSITIVE LATCHING EXCEPT WHERE REQUIRED
<br /> NURSING HOME COOKING FACILITIES WITH DOMESTIC COOKING APPLIANCES SHALL ', •
<br /> r �.� � -I(- II- I
<br /> BE PERMITTED OPEN TO THE CORRIDOR WHERE ALL THE CONDITIONS OF 407.2.6 ARE , s II �� `` / II A RATING PER 716.5.
<br /> MET. . os IL_ ��L_ __IL � OFFICEl ... RECEPTION � /
<br /> s
<br /> I� �I`��--1 i // II I EXIT DOOR W/PANIC HARDWARE AND
<br /> A 50'MAXIMUM DEAD END CORRIDOR IS ALLOWED PER IBC 1018.4, EXCEPTION 2, / IL II JL II EXIT SHEET NUMBER
<br /> BECAUSE THE BUILDING UTILIZES A NFPA 13 SPRINKLER SYSTEM It-" �F -1 \ / I CLOSER(OR POWER OPERATING DOOR
<br /> II 11 / V COMPLYING W/IBC 1017.2
<br /> ; T I)
<br /> CODE PLAN - NORTH ADDITION 0 EXITSIGNCS1 ■
<br /> 02
<br /> 1 3/32" = 1-0"
<br /> ACOPYRIGHT©2019 shoesmith cox architects
<br />
|