-_ - TO VAULT
<br /> TO VAULT AEG -\ T
<br /> a)
<br /> (V22-12A & _2A &B) � SEE DWG. 40>21-E4 \ O T S �
<br /> SEE DWG. 40-21-E4e 9 G -\ -R A E
<br /> \ \ U
<br /> -
<br /> - © LOAD BREAK SW. \ -0- LOAD BREAK SW. 1. PANEL ID PREFIX: 4: 480V a.
<br /> 3: 480Y/277V -4-,
<br /> S , 3 S TAT I O #6-3 S J B S TAT I O\ 6 — L 2: 208/120V n--
<br /> VA J LT (v2 2—7 3) 15KV RM -�- o PRIMARY FUSE VAULT (v2 2— 7A) 15KV RM -�- - PRIMARY FUSE 2. (#) IN PANEL SYMBOL INDICATES BRANCH
<br /> SURGE ARRESTORS — SURGE ARRESTORS — CIRCUIT. ie. (7) 7abc OR 7,9,11
<br /> SPACES: B5,B6,B7,B8 — SPACES: A5,A6,A7,A8 I
<br /> 1500 KVA XFMR. 1500 KVA XFMR. 3. TRANSFORMERS DELTA-WYE UNLESS 1 -
<br /> 12.5 KV-480/277V 1.1 12.5 KV-480/277V OTHERWISE NOTED. S
<br /> rr
<br /> 30,4W,60N VOLTMETER AMMETER
<br /> AMMETER 30, ,60
<br /> 1 © P VOLTMETER t1.
<br /> 0 4. KVA LOADS SHOWN ARE 100%
<br /> '■) E M ) C © DEMAND FACTOR. MOTOR LOADS i
<br /> SHOWN ARE TOTAL HP WITH NO 0
<br /> VOLTMETER - 0 VOLTMETER DIVERSITY FACTOR.
<br /> � CT'S �- -� CT'S
<br /> AMMETER SWITCH AMMETER SWITCH =
<br /> SWITCH SWITCH 5. AUTOMATIC TRANSFER SWITCH IS A �
<br /> MAIN l MAIN SEPARATE PACKAGE LOCATED IN
<br /> 3000AF ) 3000AF VAULT 22-7 . RUN 2#10 TO GEN.
<br /> u 2100AT U 2100AT ROOM AT A6 ALONG WITH GEN.
<br /> FDR. TO PROVIDE EMERGENCY
<br /> 480 V BUS B1 B2 B3 B4 B5 B6 B7 B8 �> Al A2 A3 A4 A5 A6 A7 A8 480 V BUS STARTING CIRCUIT.
<br /> e • -- -- e 6 -- e • i • A « 8 - 41V - - m - 0 - 6 ® s i
<br /> TIE
<br /> 1600AF
<br /> T T T T ^ ^ ^ 1200AT T
<br /> 1600AF 1 1600AF 1 1600AF l 1600AF ) HDWR HDWR HDWR HDWR 1600AF l 1600AF l 1600AF 1 1600AF ) HDWR 1600AF ) HDWR HDWR —
<br /> 1000AT �/ 400AT �/ 600AT �/ 1000AT \/ 400AT , 600AT 600AT C 0 \ S T R 800AT , T I 0 \ \ 0 T-S
<br /> REPLACE TRIP UNIT IN EXISTING 200A BUS PLUG WITH
<br /> 70A TRIP UNIT.
<br /> 0 0 0 0 0 : 01 01 0 : 0 0 0 0 0 ' 0 0 * 0 •
<br /> 4V22- 3-3 1/2"C, 3#500 KCML & l#1/O GND EA
<br /> 7AC9
<br /> 800AMCB
<br /> 2-2"C, 3#3/0 & 1#2 GND EA
<br /> 4V22- 4V22- 4V22- R I -R \ CIE I V AG -
<br /> 3-1/2"G, 3#600kcmil/ (1)#3G 7AB9 7AB9.5-1 7AB9.5-2
<br /> 400AMCB 400AMCB 400AMCB
<br /> 140-022-2001-E302.TIF
<br /> SPARE 2-3 1/2"C,
<br /> 4#350kcmil EMERGENCY GENERATOR 3
<br /> 2-3"C,3#500kcmil ea. 3-3' . r JUNCTION BOX
<br /> C,3#500kcmil ea ' 2-3 1/2"C,
<br /> 3-1/2"C, 3#600kcmil/ (1)#3G TRENCH BUS 4#500kcmiL ea. EMER. GEN. 350 KW
<br /> 2-3 1/2"C,4#350kcmil ea. (SOURCED FROM V22-7B) 2-3 1/2"C,3#500kcmil ea. ., AUTO - F----1: . GEN. 438 KVA PRIME PWR.
<br /> TRENCH BUS (NTRA NSFE(V22R)) 1600A � 3 COL. A/6(SOURCED FROM V22-7A) ai 0,,
<br /> "'I: ,0;,, `� 2-3 1/2"C, Q LOAD TEST CB
<br /> CD
<br /> NEEDS 4#350kcmil ea. CD
<br /> CIRCUIT 1000A BUS ■
<br /> 1000A BUS MCC NO. 4 3V22- 4V22-D.2 4V22-7 MCC 3V22- X3V22-
<br /> ^a Z @ TRUSS LEVEL, D8 7BUD7D 10.5 D10 TRACED DUCT NO. 18 7AUD7-D 7AUD7D (2) 3"C, 3#350 kcmil &
<br /> 70A 'I' 70A 600A MCB ___ MCB 800A MCB 600A MLO 1 1 GND EA EMERGENCY GENERATOR 3
<br /> ;40250 j5i)3 1j2t9010) (1) (2) (1) (7) (8) LOAD TEST TERMINAL BOX
<br /> (1I0)(9}(1 (3X5)(8X6) (2) 3'C, 3#350 kcmil EA
<br /> 3/4"C,3#10 d d
<br /> 1"C,3#4,1#8G „--- , ' 1 1/4"C,3#4 (4) #10
<br /> 1 1/4 C,3#4 f' 1 1/4"C, 3#4
<br /> 1715kVA 4#500 MCM 1-1/2"C,(3)#1 (1)#6G ..
<br /> 1 1/2 C,3#1 2V22-
<br /> 3"C 4#4/0 ,--; r r, 7TBC5 �, 3/4»G (3)#8 (1)#loG
<br /> 40A MCB 3"C,4#4/0
<br /> 3V22- 3V22- 3V22- 3V22- X3V22- X3V22- X3V22- MCC MCC
<br /> 7BD6 7BUD6 7BD8 7BUD8 7ATE4 7ATD2 7ATD8 NO. 19 NO. 16
<br /> 225A MCE 225A MCE 225A MCE 225A MCE 300A MCB 300A MCE 300A MCE
<br /> 1"C - 3#4 1"C - 3#4 (7) (6) (7) (6) (6)(7X 11) 40A MCB 125A MCB
<br /> 2 1/2"C,4#2/0 r 1"C,3#6
<br /> 1»C 3#6 `� 1 1/4'C,3#2
<br /> '- -- 2 l/2"C,4#2/0
<br /> X3V22- X3V22- X3V22-
<br /> 7AUF2 7AUC1 7AUD11
<br /> 100A 100A MCE 100A MCE
<br /> D45KVA W45KVA (6) (6)(7)(8)
<br /> 3/4"C,4#8
<br /> 2"C-4#2,1#BGND -k. 3/4"C 3#8
<br /> 2"C 4#2/0f d 45KVA Di 45KVA El 75KVA El 45KVA ® 45KVA El 45KVA 0 75KVA 075KVA 15KVA T 45KVA 045KVA 2"C-4#2/0,1#4G 09KVA El9KVA 06KVA D 30KVA 0 30KVA 06KVA E 9KVA ©30KVA ❑T 30KVA ® 75KVA
<br /> 2"C 3#4/0 2 1/2 C,4#2/O 300 AF )”C,4#2/0
<br /> 200 AF 2 C,4#2
<br /> 1#4G 2#4/ON,#1/0G , '' 3#2 n - 2 ) 175 AT 175 AT h 3#12 1 C,4#8 \_
<br /> `� 3"C 4#4/O 2"C 4#1/0 l"C,4#6 - 2 1/2"C,3#2/0, 1"C 4#8 ,--' --. - 2 C,4#2
<br /> 2V22- 2V22- 12V22-7E 12V22-78 2V22- 2V22- 2V22- 2V22- 2V22- 2V22-7D.2 2V22-7 #350kcmil,#4G I2V22- I2V22- 2V22- 2V22- X2V22- X2V22- X2V22- X2V22- X2V22- X2V22- X2V22- X2V22- X2V22- X2V22- X2V22-
<br /> BD - VD9B VD9A 7BUD5-1 7BC7.5 7BUD5 7BD7 7BUD7 10.2 D10 7AUD5-1 7AUC5 7AUD6.75 7AUD7 7AD9 7AD6 7AF5 7AUF2 7AUC1 7AC5 7AD3 7AWC3 7AUD11 7ATD8.5a 7ATD8.5b
<br /> 1A 1A P_25A MCB 225A MCE 100A MCE 225A MLC 50A MCB 225A MCE 225A MCE 00A MLII 150A MCE 150A MCE 150A MCB 70A MCB 50A MCB 50A MCB 100A MLC 100A MCE 100A MCE 50A MCB 100A MCE 100A MCE 100A MCE 100A MCE
<br /> „8)(1)(14) -
<br /> CRANE
<br /> 0 2 1/2"C,4#2/0 1 1/2"C,4#2,#6G DISPATCH -- - -- --
<br /> OFFICE
<br /> 1 1/2'C,4#2 ., ;'
<br /> h
<br /> 2V22- P1 2V22-7D.2 LP-1 _ , #
<br /> 7BD5 10.2-1 mop
<br /> 225A MLC 100A MCE _ _ MLO e; nk
<br /> i __
<br /> www.brph.com Copyright©2019
<br /> � Architects Engineers, Inc.
<br /> S u B S TAT I 0 \ # 6 - /1 (V22 - 7A' 6 (V - B) 0 \ F I \ F A G R A 19020 33rd Ave W,Suite 530 State of Washington
<br /> Certificate of Authorization
<br /> SCALE: NTS Lynnwood,Washington,98036 Architecture
<br /> e No.603235512
<br /> 425-921-3500
<br /> 137
<br /> DRAWN DATE SUBTITLE CURRENT REVISION SYMBOL DATE
<br /> SYM REVISION BY APPROVED DATE SYM REVISION BY APPROVED DATE �RIE s. ACCEPTABILITY VTB 09/17/19 SUBSTATION #6-4 (V22®7A) & 6-3 (V22-7S) A 09/17/19
<br /> A Issue For Permit - 767 Rate Increase FA VTB SMS 09/17/19 ,� of wAs8-:-7/e, THIS DESIGN AND/OR SMS CHECKED 09/17/19 ONELINE DIAGRAM SHEET
<br /> w v � SPECIFICATION IS APPROVED_ 767 RATE INCREASE - FA
<br /> 0 s s- T �n SMS
<br /> 09/17/19 TITLE 4F
<br /> �„ ® II��� �/ APPROVED BY DEPT. DATE
<br /> � � i� / {_� � �� CHECKED
<br /> 'd,.. �, ,54014 O cfi APPROVED os BUILDING •®®21 JOB No. _ _ _ COMP NO.
<br /> GI8'10' �� EVE 18 30055 602 00033478
<br /> 6
<br /> S'SIONAL E� APPROVED DWG NO.
<br /> tom, ELECTRICAL MASTER EVERETT, WA 40-21 -E4F-602
<br />
|