<br /> -J _ _ SEQUENCE OF OPERATION
<br /> A A 1.NITROGEN VAPORIZER CONDENSATE RECEIVER WITH DUPLEX PUMPS
<br /> THE EXISTING CONDENSATE RECEIVER(OCP-900E)COLLECTS THE OVER FLOW FROM THE(2)STEAM
<br /> SPARGED NITROGEN VAPORIZERS, ONE OF WHICH IS EXISTING.THE SYSTEM IS COMPRISED OF(1)400
<br /> I ji� 1 8"HPS 1 GALLON(OPERATING VOLUME)HORIZONTALLY MOUNTED RECEIVER TANK,(2)CONDENSATE PUMPS,PIPED
<br /> IN A PARALLEL ARRANGEMENT,AND ALL ASSOCIATED APPURTENANCES AND DEVICES DEPICTED ON THE
<br /> 4
<br /> VG;., CONTROL SYSTEM DIAGRAM. VAPORIZER A STEAM INLET NOZZLE VAPORIZER B STEAM INLET NOZZLE ,.� F --.
<br /> I CONNECTION, N13,2-1/2" 150#FLG ' te; CONNECTION,N13,2-1/2" 150#FLGN 1
<br /> - - — T -�- J ' A.RUN CONDITIONS: 111 '_
<br /> T \ — — THE CONDENSATE PUMPS SHALL BE AVAILABLE TO RUN 24 HOURS A DAY,365 DAYS A YEAR TO SUPPORT
<br /> HPS DRIP " II 71
<br /> HPS DRIP 7 HPS DRIP THE REQUIREMENTS OF THE NITROGEN VAPORIZERS INDEPENDENT FROM THE NITROGEN VAPORIZER / C HPS DRIP I C HPS DRIP
<br /> K A LEG 1 I (-. ) LEG C , LEG CONTROL PANELS.THE CONDENSATE PUMPS SHALL BE ENABLED/DISABLED BY THE EMCS. \ LEG ' LEG
<br /> VAPORIZER A STEAM TRAIN DRIP - � VAPORIZER B STEAM TRAIN DRIP _ -
<br /> TRAP CONNECTION,N15,3/4"NPTFIll`'` TRAP CONNECTION, N15,3/4"NPTFIlitir-
<br /> B.STAGING ORDER: .,
<br /> THE CONDENSATE PUMPS ARE IN A LEAD/LAG/STANDBY TYPE CONFIGURATION INCLUDING FAILOVER.THE
<br /> DOUBLE BLOCK& DESIGNATED CONDENSATE LEAD PUMP AND LAG PUMP SHALL ROTATE UPON ONE OF THE FOLLOWING
<br /> BLEED W/INTEGRAL CONDITIONS(USER SELECTABLE): j
<br /> BY-PASS,TYPICAL 7MANUALLY THROUGH A SOFTWARE SWITCH
<br /> • IF PUMP RUNTIME OF 168 HOURS(ADJ.)IS EXCEEDED
<br /> X i • MONTHLY
<br /> - VAPORIZER A VAPORIZER B
<br /> C.FAILOVER EXISTING BY OTHERS •
<br /> --DC J I— THE EMCS SHALL MONITOR EACH CONDENSATE PUMP'S STATUS AND IF ANY CONDENSATE PUMP FAILS,
<br /> — THE FAILED PUMP SHALL BE DISABLED AND THE LAG CONDENSATE PUMP SHALL BE ENABLED.AN ALARM
<br /> T - SHALL BE SENT TO THE OPERATOR'S WORKSTATION AND THE FAILED PUMP SHALL BE LOCKED OUT OF j
<br /> THE CONTROL SEQUENCE UNTIL AN OPERATOR HAS RESOLVED THE ISSUE AND SHALL THEN RESET THE
<br /> C `\ HEPCS DRIP ALARM AT THE EMCS. tiki
<br /> D.OPERATION/CONTROL 'y
<br /> .41 THE EMCS SHALL CONTINOUSLY MONITOR THE WATER LEVEL VIA A WATER LEVEL TRANSMITTER IN THE J i
<br /> CONDENSATE RECEIVER TANK. THE EMCS SHALL HAVE THREE SET WATER LEVELS,THE HIGH-HIGH LEVEL, j c..> 0HIGH LEVEL AND LOW LEVEL AS DETERMINED BY TEST AND BALANCE. IF THE RECEIVER TANK REACHES _ = a
<br /> w THE HIGH WATER LEVEL MARK THEN THE EMCS SHALL ENABLE THE LEAD CONDENSATE PUMP. IF THE * _
<br /> �`„
<br /> =1 RECEIVER TANK WATER LEVEL CONTINUES TO RISE ABOVE THE HIGH WATER LEVEL MARK OR THE HIGH CO `' "
<br /> FULL PORT / w - HIGH LEVEL(HHL)HAS BEEN REACHED,THE EMCS SHALL ENABLE THE LAG PUMP. IF THE HIGH-HIGH LEVEL
<br /> J
<br /> GATE VALVE o �I HAS BEEN REACHED,AN ALARM SHALL BE SENT TO THE OPERATOR'S WORKSTATION.WHEN THE WATER N.O.
<br /> oo = LEVEL IN THE RECEIVER TANK REACHES THE LOW LEVEL(LL),ALL PUMPS ENABLED SHALL BE DISABLED. VAPORIZER A OVERFLOW NOZZLE -' }4
<br /> VAPORIZER B OVERFLOW NOZZLE __.
<br /> o _ I CONNECTION,N8,6" 150#FLG I CONNECTION,N8,6" 150#FLG
<br /> a. S E.ALARMS
<br /> ALARMS SHALL BE PROVIDED TO THE EMCS FOR THE CONDENSATE RECEIVER AND PUMPS AS FOLLOWS: '
<br /> a. ` i \ /
<br /> M ,V HIGH HIGH LEVEL - - - - - -
<br /> • PUMP FAILURE >`
<br /> •
<br /> OA 6"OVERFLOW
<br /> 1"HPC N.C.
<br /> 1"HPC -'
<br /> - - - - - - - 1�I - - 8"HPS
<br /> / / 4"HPS
<br /> 8„HPS n
<br /> ►/
<br /> 2"PUMPED 3"PUMPED CONDENSATE _ X
<br /> CONDENSATE ----. - - - - - - - V't - 1"HPC - - - - - - - - - T
<br /> - - - - - - �- HPS DRIP C �
<br /> - \ \ LEG \ � >
<br /> / 2„VENT
<br /> VENT TO ROOF- ,--�' I / ;
<br /> SEE PROJECTIV i
<br /> PLANS FOR — -I \ CS _ -II" CS
<br /> 2" CONTINUATION _ I \ �' n' ; LT _
<br /> �F' VFD -I� II- VFD �� aAiiik
<br /> 1/2"CA 1 e .A 6"VENT/ W —..
<br /> 90 PSI - m m II / / 13 GAL „
<br /> a o w a o w t
<br /> 3
<br /> 0 w 0 F- 0 w v i- l w FLASH �- 1 1/2 LOW
<br /> LU ' LL rn v~i w U. cn O IO TANK / PRESSURE
<br /> _ w m w a O O 6"X 4" L CONDENSATE
<br /> VENT FULL SIZE z a L.,-, z ¢ z a Z a 1/4" 1/4" �����n
<br /> _ ¢ REDUCER V V N
<br /> w COcn vy w cn a w °' COCO '- aNI OF OUTLET o o _ _ _ EMCS / 1
<br /> �t-� V /�\ VX- /-\� /�\ 0 1-1/2"HPC J _ \l\
<br /> • .
<br /> A A rt- OVERFLOW 1 N.O.
<br /> L- - - --X1- TO DRAIN EMCS EMCS , HHL — �I 6"OVERFLOW
<br /> SXCP-05 400 GAL RECEIVER
<br /> 2-1/2" TANK HL_
<br /> \ CAP OR PLUG COLD WATER
<br /> OVERFLOW OCP —I \ INLET CONNECTION(NOT USED)
<br /> PRESSURE REFER TO PLUMBING SHEETS 900E b I N \
<br /> 2"DRAIN
<br /> POWERED 1 M110-39 AND SCHEDULE M2K _ T / N
<br /> PUMP FOR FLOOR SINK - LL 2"LOW POINT PROVIDE HOSE •
<br /> AUTOCLAVE PIT/GRADE LEVEL L - r r wG I - CONNECTION
<br /> INFORMATION,TYP. -- I _1 DRAIN '
<br /> 1 \\ .,,
<br /> GENERAL NOTES CONSTRUCTION NOTES REFERENCE DRAWINGS \- ROUTETOADJACENT
<br /> 101110.- REMOVE EXISTING BLIND FLANGE FROM EXISTING 6"GATE VALVE AND CONNECT 6"OVERFLOW PIPE 1. REFER TO APCI DRAWINGS FOR EXISTING VAPORIZER. DRAIN AND TERMINATE `
<br /> 1. SEE STEAM TRAP SCHEDULE ON SHEET M2h-a FOR TRAP TYPE - ID FROM VAPORIZER B(POC N8B). 2, REFER TO M543a FOR INTERFACE SCHEDULE TO NITROGEN EQUIPMENT. DISCHARGE WITH 45°CUT
<br /> 3, REFER TO SPECIFICATION SECTION 23 2213-"STEAM AND CONDENSATE PIPING"FOR STEAM AND , _N. F `,,\::::Ar
<br /> 2. SEE SHEET M513a FOR STEAM PIPING AND SPECIALTIES DETAILS. © REMOVE EXISTING BLIND FLANGE FROM EXISTING 3/4"GATE VALVE AND CONNECT 3/4" HPC PIPE FROM CONDENSATE PIPING ON THIS DIAGRAM. ''; )ii v off•
<br /> VAPORIZER B(POC N15B),
<br /> 3. EQUIPMENT,PIPING, ETC.THAT IS GREYED OUT IS EITHER EXISTING OR TO BE ,• ,'' o
<br /> INSTALLED WITH SUBSEQUENT AUTOCLAVES AT A LATER DATE. REFER TO AUTOCLAVE EXISTING I FLANGE AND CONNECT 4"HP PIPE FROM VAPORIZER B(POC N13B VIA : -,f Q © REMOVE EX ST NG BLIND FLA G CO C S ( 0 )SUBSYSTEM SCHEDULES FOR INDICATION OF INSTALLATION PHASE. FLANGE. www,brpli.corn
<br /> Copyright 0 2018
<br /> Architects Engineers, Inc. f-- ��o� �,�5147 g�� �A, .
<br /> stet otwao on �: GISTS ,\ ib
<br /> AntltectweNo. f3235512 SS j VAL y�
<br /> E25-2t3500 y •wining. 2
<br /> aliment;No,2133 Q
<br /> r
<br /> DRAWN DATE SUBTITLE CURRENT REVISION SYMBOL DATE �?
<br /> SI'M REVISION BY APPROVED DATE SYM REVISION BY APPROVED DATE of WASH ACCEPTABILITY JXK 06/12/18 STEAM AND CONDENSATE
<br /> W2548317 0 06/12/18
<br /> �` r THIS DESIGN AND/OR CHECKED r F;
<br /> 0 ISSUE FOR CONSTRUCTION JXK JLC 06/12/18 5P SPECIFICATION IS APPROVED JEW 06/12/18 FLOW AND CONTROL DIAGRAM SHEET
<br /> ., ® co
<br /> BRPHARCHITECTS ENGINEER TITLE Boeing777X CWC BUILDINGo
<br /> l' i1/� 1 31\—a N
<br /> eNciNR wc• APPROVED BY DEPT. DATE JLC 06/12/18 -J `
<br /> _ .
<br /> No.3137 CHECKED
<br /> BUILDING 40-58
<br /> `p,F\ tiP�� APPROVED JOB No. COMP No. 40-58-M313A-a x
<br /> qTF OF A„���R` APPROVED MECHANICAL MASTER EVERETT, WA DWG No. 40-58-M313A-a