STEAM TRAP SCHEDULE DIFFUSER, GRILLE, AND REGISTER SCHEDULE
<br /> UNIT MAX PRESSURE MAX. TRAP ACTUAL ORIFICE CONNECTION MAX. OPERATING MAX. SIZE (INCHES)
<br /> NO. TRAP TYPE DIFFERENTIAL CAPACITY SIZE (IN.) PRESSURE ALLOWABLE MFR. & MODEL MARK MOUNTING MANUFACTURER/
<br /> GPM NUMBER
<br /> . PSIG LBS./HR. IN -OUT PSIG TEMP. °F TYPE MATERIAL AIR FLOW INLET SIZE FACE SIZE NOTES
<br /> NUMBER LOCATION MODEL NUMBER
<br /> A FREE FLOAT 50 270 0.6 14 1/2" 1/2" 200 428 TLV MODEL J3S-X SCREWED
<br /> B FREE FLOAT 50 375 0.8 14 1/2"- 1/2" 200 428 TLV MODEL J3S-X SCREWED
<br /> SSR GRILLE DUCT PRICE 620 ALUMINUM SEE PLAN FOR SIZES SEE PLAN FOR SIZES - 1, 4, 5, 6
<br /> C FREE FLOAT 50 500 1.0 14 3/4"-3/4" 200 428 TLV MODEL J3S-X SCREWED
<br /> SD-1 DIFFUSER LAY-IN PRICE ASCD ALUMINUM 1 - 100 CFM 6" DIA 24x24 3,4,5,7
<br /> D FREE FLOAT 50 42 0.1 14 1/2"- 1/2" 200 428 TLV MODEL J3S-X SCREWED 101 280 CFM 8" DIA
<br /> 281 -430 CFM 10" DIA
<br /> E FREE FLOAT 50 42 0.1 14 1/2"- 1/2" 200 428 TLV MODEL J3S-X SCREWED 431 -550 CFM 12" DIA
<br /> 551 -730 CFM 14" DIA
<br /> F FREE FLOAT 50 42 0.1 14 1/2"- 1/2" 200 428 TLV MODEL J3S-X SCREWED
<br /> SD-2 DIFFUSER SURFACE PRICE ASPD ALUMINUM 1 - 100 CFM 6" DIA 12x12 1,3,4,5,9
<br /> G FREE FLOAT 50 53 0.1 14 1/2"- 1/2" 200 428 TLV MODEL J3S-X SCREWED 101 -280 CFM 8" DIA
<br /> H FREE FLOAT 50 42 0.1 14 1/2"- 1/2" 200 428 TLV MODEL J3S-X SCREWED 0-800 CFM 12x10 14x12
<br /> SG-1 GRILLE SURFACE PRICE 22DAL ALUMINUM 1,3,4,5,9
<br /> J FREE FLOAT 50 928 2.0 5 3/4"-3/4" 150 428 TLV MODEL J3S-X SCREWED 801 - 1501 CFM 14x12 16x14
<br /> 1501 -2700 CFM 24x14 26x16
<br /> 2701-6000 CFM 36x20 38x22 •
<br /> NOTES:
<br /> • 1. TRAP SIZE, CAPACITY AND GPM FLOW BASED ON SYSTEM OPERATING LOADS. RD-1 DIFFUSER DUCT PRICE ARCD ALUMINUM 30" DIA 67.5" DIA 1, 4, 5, 6
<br /> 2. ALL TRAPS SHALL BE NPT SCREWED CONNECTIONS WITH ALL STAINLESS STEEL INTERNAL COMPONENTS, HARDWARE, FLOATS, ORIFICE PLUGS, SPRING CLIPS, DRAIN
<br /> PLUGS, VENT SEATS AND ASSEMBLIES. RD-2 DIFFUSER DUCT PRICE ARCD ALUMINUM 10" DIA 22.5" DIA 1, 4, 5, 6
<br /> LD-1 LINEAR DIFFUSER LAY-IN PRICE TBDI350 ALUMINUM 6" DIA 24x1-1/2 24 3,4,5,7
<br /> LD-2 LINEAR DIFFUSER SURFACE PRICE SDBI50 ALUMINUM 5" DIA - - 1,3,4,5,6,10
<br /> LD-3 LINEAR DIFFUSER SURFACE PRICE SDBI100 ALUMINUM 8" DIA - - 1,3,4,5,6,11
<br /> LD-4 LINEAR DIFFUSER SURFACE PRICE SDBI100 ALUMINUM 10" DIA - 1,3,4,5,6,12
<br /> RG-1 GRILLE LAY-IN PRICE 630 ALUMINUM 1 -900 CFM 10x22 12x24 4, 5, 6,7
<br /> 901 - 1800 CFM 22x22 24x24
<br /> RG-2 GRILLE SURFACE PRICE 630 ALUMINUM 1 -900 CFM 10x22 12x24 1, 4, 5, 6
<br /> 901 - 1800 CFM 22x22 24x24
<br /> RG-3 GRILLE SURFACE PRICE 630 ALUMINUM 1 -700 CFM 14x12 16x14 1, 4, 5, 6
<br /> 701 - 1600 CFM 26x16 28x18
<br /> 1601 -2800 CFM 32x22 34x24
<br /> RG-4 GRILLE SURFACE PRICE 630 ALUMINUM 6001 - 12000 CFM 48x42 - 1, 4, 5, 6
<br /> 12001 -24000 CFM 96x42
<br /> RR-1 REGISTER SURFACE TITUS 350ZFS ALUMINUM 60,000 CFM - 48x144 1, 2, 4, 5, 6
<br /> TG-1 GRILLE SURFACE PRICE 630 ALUMINUM 1 -500 CFM 12x12 14x14 1, 4, 5, 6
<br /> 501- 1200 CFM 28x12 30x16
<br /> •
<br /> TG-2 GRILLE SURFACE/LAY-IN PRICE 630 ALUMINUM 1 -500 CFM 12x12 18x18 4, 5, 6,7
<br /> 501 - 1900 CFM 22x22 24x24
<br /> TG-3 GRILLE SURFACE PRICE 630 ALUMINUM 2000-6000 CFM 30x36 30x36 1, 4, 5, 6
<br /> TG-4 6001 - 12000 CFM 72x30 72x30
<br /> EG-1 GRILLE SURFACE PRICE 630 ALUMINUM 1 - 180 CFM 8x8 8x8 1, 4, 5, 6
<br /> EG-2 181 -280 CFM 14x6 14x6
<br /> EG-3 281 -800 CFM 22x10 22x10
<br /> EG-5 801 -2000 CFM 24x16 24x16
<br /> EG-6 2001 -6000 CFM SEE PLAN FOR SIZE -
<br /> EG-4 GRILLE SPIRAL DUCT PRICE SDGER ALUMINUM 1200 CFM 12x24 12x24 1
<br /> SURFACE
<br /> DL DRUM LOUVER DUCT PRICE HCD ALUMINUM SEE PLAN FOR SIZES SEE PLAN FOR SIZES - 2
<br /> NOTES: (NOT ALL NOTES USED ON THIS SCHEDULE)
<br /> CEILING MOUNTED DEVICES SHALL HAVE WHITE FINISH.
<br /> 1. PROVIDE BORDER FOR SURFACE MOUNTING ON HARD CEILINGS OR WALL OR DUCT MOUNTING.
<br /> 2. PROVIDE WITH OPPOSED BLADE DAMPER.
<br /> 3. INSULATE BACK OF DIFFUSERS AND SA PLENUM BOXES.
<br /> 4. PERFORMANCE SELECTION FOR NOISE CRITERIA SHALL NOT EXCEED THE FOLLOWING:
<br /> SHALL NOT EXCEED A MAXIMUM OF NC=25-30 FOR EXEC. OFFICES AND CONFERENCE ROOMS.
<br /> SHALL NOT EXCEED A MAXIMUM OF NC= 30 35 FOR PRIVATE OFFICES COLLABORATION ROOMS.
<br /> SHALL NOT EXCEED A MAXIMUM OF NC =35-40 FOR OPEN-PLAN OFFICES AND LIBRARIES.
<br /> SHALL NOT EXCEED A MAXIMUM OF NC=40-45 FOR COMPUTER ROOMS, FACTORY OFFICES, FACTORY SHOPS AND CONTROL ROOMS.
<br /> SHALL NOT EXCEED A MAXIMUM OF NC =65 FOR FACTORY MANUFACTURING AREAS.
<br /> 5. SEE ARCHITECTURAL SPECIFICATIONS AND DRAWINGS FOR FINISH REQUIREMENTS.
<br /> 6. TRANSITION AS REQUIRED TO MATCH SIZE OF REGISTER OR GRILLE INLET OR OUTLET SIZE.
<br /> 7. PROVIDE BORDER TYPE FOR LAY-IN CEILINGS.
<br /> 8. RUNOUT TO DIFFUSER IS TO BE SAME SIZE AS DIFFUSER, GRILLE INLET SIZE.
<br /> 9. PROVIDE FOR ABOVE HARD CEILINGS REMOTE CONTROL SYSTEM FOR BALANCING DAMPER ADJUSTMENT EQUAL TO ZIPSET SYSTEM MODEL ZSA-1 FOR DAMPER ACTUATOR AND MODEL
<br /> CR-1 CEILING RECEPTACLE BRACKET TO CONTROL BALANCING DAMPER POSITION DURING T&B OPERATIONS. COORDINATE CEILING RECEPTACLE MOUNTING LOCATION WITH ARCHITECTURAL.
<br /> 10. PROVIDE 1 SLOT LINEAR DIFFUSER: 1/2" SLOT WIDTH, 60" LONG, FACTORY INSTALLED INSULATION.
<br /> • 11. PROVIDE 2 SLOT LINEAR DIFFUSER: 1"SLOT WIDTH, 60" LONG, FACTORY INSTALLED INSULATION.
<br /> 12. PROVIDE 4 SLOT LINEAR DIFFUSER: 1"SLOT WIDTH, 48" LONG, FACTORY INSTALLED INSULATION.
<br /> • ::514=1:1L,'"I : ' 1 1 1 t ...4#4.\). ..' #-...1‘-1:1'j.:4;:ss,4 I::.-.40'.7k,\44.......
<br /> itl fit,,,,i,--1 ''• .,, t, ii ' „ .i:iii:'zz. ill,,-.4 ss,';, Z,::::i:
<br /> www.brph.e om copyright 0 2018 .r:;i;i:Iri::,-.:5:-..1...°N;SA;.:TI.;:-.Y:::41;14•4:Ail::::**
<br /> iii . f ,/Architects Engineers, Inc. P,,,, �'4,c , wt roAvew.s+itat 7teecW L i*ova,we rn,s �o-r a s2Y4 1$500 No.3137 .a ' Q
<br /> O
<br /> F.fM REVISION BY APPROVED DATE SYM REVISION BY APPROVED DATE
<br /> WAS ACCEPTABILITY DRAWN DATE SUBTITLE CURRENT REVISION SYMBOL DATE Lr?
<br /> H, JXK 06/12/18 SCHEDULES W2548317 0 06/12/180 ISSUE FOR CONSTRUCTION JXK JLC 06/12/18 (7;;--
<br /> ti�'o THIS DESIGN AND/OR JEWKED06/12/18 SHEET SPECIFICATION IS APPROVEDARCHITECTS ENGINEER TITLE o
<br /> .. ® Boeing 777X CWC BUILDING
<br /> NEeRs INC• APPROVED BY DEPT. DATE JLC 06/12,18 M2h-a
<br /> NO.3137 CHECKED BUILDING I
<br /> ,�'F\ / o APPROVED BUILDING 40-58 JOB NO. COMP NO. 6
<br /> / P 40-58-M2h-a
<br /> `'TF 0f AU1H��`ti APPROVED MECHANICAL MASTER EVERETT,WA DWG NO. 40-58-M2h-a
<br />
|