Laserfiche WebLink
PARAMETER POOL RECIRCULATION SPA RECIRCULATION SPA JETS GENERAL NOTES REVISIONS <br /> • <br /> A CONFORMANCE SUMP OPENING (INCHES) 8 ROUND 12 SQUARE / \ ' <br /> ENERGY CODE <br /> 3 6 All material and construction methods shall conform to Chapter 246-260 WAC, Provide pool/spa equipment, covers, piping insulation, motors, etc. in A <br /> D - MANIFOLD PIPE DIAMETER (INCHES) "Water Recreation Facilities" published by the Washington State Department accordance with the applicable portions of WSEC Sections C404.11.1 ^ <br /> of Health, KingCountyTitle 14 - "Water Recreation Facilities", 2015 through C404.11.4 /.\ <br /> B - SUMP DEPTH (INCHES) 2 MIN. (4.5 PREFERRED) 6 • <br /> International Buildingode, International Electrical Code and International C404.10.1 Heaters. Heat <br /> pump pool heaters shall have a minimum <br /> SUMP TYPE FIELD FABRICATED LAWSON MLD-SG-1212 Mechanical Code, 2009 ICC A117.1, 2010 ASCE 7-10, 2015 Washington State COP of 4.0 determined in accordance with ASHRAE Standard 146. <br /> Energy Code, latest editions, as modified by the local agency having jurisdiction. Other pool heating equipment shall comply with the applicable <br /> SUCTION COVER PARAMOUNT SDX2 LAWSON MLD FG 1212 Comply with IBC Sections 1910.4.3, 1910.5, 1910.9 and 1910.10. efficiencies in Section C404.2. <br /> COVER OPEN AREA (SQ. INCHES) 43.2 81.3 CONCRETE The electric power to all heaters shall be controlled by a readily <br /> Gunite: 1 part cement, 4-1/2 parts sand, based on dry and loose volume; accessible on-off switch that is an intergral part of the heater, <br /> NUMBER OF COVERS 2 FLOOR 2 FLOOR 2,500 psi @ 28 days. or external to and within 3 feet of the heater. Operation of such <br /> Portland Cement Type I or II, ASTM C-150, seven sack mix. switch shall not change the setting of the heater thermostat. Such <br /> TOTAL COVER OPEN AREA (SQ. INCHES) 86.4 162.E switches shall be in addition to a circuit breaker for the power to <br /> CERTIFIED MAXIMUM FLOW CAPACITY (GPM) 188 365 REINFORCEMENT the heater. Gas fired heaters shall not be equipped with constant <br /> burning pilot lights. <br /> Reinforcing steel, deformed intermediate grade, fy = 40,000 psi, ASTM A-15. <br /> DESIGN FLOW (GPM) (100% PER COVER) 80 80 120 Lap splices 40 diameters; support on concrete blocks and tie with 16 gage C404.10.2 Time Switches. Time switches or other control method <br /> minimum cover between earth and steel. <br /> APSP-7 DESIGN FLOW (100% PER COVER) (GPM) 80 80 + 120 = 200 annealed wire; 2" that can automatically turn off and on heaters and pump motors <br /> Non-contact splices minimum 2 inch clear between bars. Contact splices according to a preset schedule shall be installed for heaters and <br /> --- --- <br /> MANIFOLD VELOCITY @ 50% FLOW (FPS) must be constructed with the bars aligned so that a line through the center pump motors. Heaters and pump motors that have built in time <br /> VELOCITY AT APSP-7 FLOW THROUGH COVER (FPS) 0.59 0.79 of the two spliced bars is perpendicular to the surface of the surface of the switches shall be in compliance with this section. <br /> surface of the shotcrete work. <br /> Exceptions <br /> MANIFOLD VELOCITY AT APSP-7 FLOW (FPS) 3.5 2.2 rn <br /> 1. Where public health standards require <br /> CONSTRUCTION 24-hour pump operation. >- � r- j' <br /> Maximum length of pool without control joint is 60'-0". Gunite is to be cn (NI <br /> placed monolithic and pneumatically. 2. Pumps that are required to operate solar- <br /> NOTES: a d-waste-heat-recovery pool heating w Q 1 °, <br /> 1. CONTRACTOR TO CONFIRM PUMP FLOWS AFTER COMPLETION OF WORK BARRIERS Y r LO "' <br /> TO VERIFY VALUES ABOVE ARE NOT EXCEEDED. Barrier protection shall be provided to prevent unauthorized access to pool a z �' N <br /> 2. MANIFOLD EXTENDS FROM COVER CONNECTION TO COVER CONNECTION INCLUDING facilities including: C404.10.3 Covers. Heated pools and in-ground permanent spas shall o <br /> A. Owners shall provide barriers to prevent unauthorized persons from be provided with a vapor-retardant cover on or at the water surface. - u <br /> THE TEE FITTING. Pools heated to more than 90'F shall have a pool cover with a <br /> gaining access to pools. Spray pool facilities without standing water minimum insulation value of R-12, and the sides and bottom of the <br /> are exempt from barrier requirements of this section. pool shall also have a minimum insulation value of R-12. <br /> B. Barriers at limited use pools must be at least sixty inches high. <br /> C404.10.4 Heat Recovery. Heated indoor swimming pools, spas or hot <br /> C. Barriers at general use pools must be at least seventy-two inches high. <br /> tubs with water surface area greater than 200 square feet shall <br /> D. Barriers, including windows, (see Figures 031.1 and 031.2) may not: provide for energy conservation by an exhaust air heat recovery <br /> NOTES: (i) Have spaces between vertical members greater than a width of one system that heats ventilation air, pool water or domestic hot water. <br /> and three-quarter inches if the distance between the tops of The heat recovery system shall be configured to decrease the exhaust <br /> NOTE: 1. ASSEMBLY SHALL BE ASME A112.1 UCTUR07 horizontal members are spaced less than forty-five inches apart. air temperature at design heating conditions (80'F indoor) by 36°F <br /> COVER MANUFACTURER DOES NOT REQUIRE COMPLIANT. FASTEN FRAME TO STRUCTURE WITH (10°C)• <br /> A SUMP FOR ANSI/APSP-16 (2011) WATERPROOF ADHESIVE & MANUFACTURER E. Solid barriers may not have indentiations or protrusions, other than Exception: Pools, spas or hot tubs that include <br /> COMPLIANCE SUPPLIED 316SS ANCHORS AS REQUIRED. USE MAIN DRAIN COVER normal construction tolerances and masonry joints. <br /> system(s) that provide equivalent recovered <br /> MANUFACTURER SUPPLIED FASTENERS TO & FRAME. AS SHOWN F. Barriers must have self-closing, self-latching gates or doors that provide energy on an annual basis through one of the <br /> STRUCTURE <br /> SECURE COVER TO FRAME. IN EQUIPMENT SCHEDULE. either: following methods: <br /> 3,_ <br /> PARAMOUNT SDX2 (i) A mechanism that uses a continuously locked latch, coded lock or 1. Renewable energy; <br /> PLASTER <br /> COVER W/ other equivalent access control system that always requires a key 2. Dehumidification heat recovery; <br /> FRAME PLASTER or code to enter pool area. If the latch is less than sixty inches 3. Waste heat recovery; or <br /> ,r, i �. STRUCTURE from the ground, the barrier must have an eighteen-inch radius of 4. A combination of these system sources <br /> solid material around the latch (see Figure 031.2) to preclude a child capable of and configured to provide at <br /> mii on the outside of the barrier from reaching through the gate or least 70 percent of the heating energy <br /> - A barrier and opening the latch and entering the pool; or required over an operating season. <br /> II I (ii) A latch height of sixty inches or more from the ground. (.1111:°°16,10NLIII-LIC:4-711111111ALV)11-(:):01:1-11-:c., <br /> C404.13 Service water-heating system commissioning and completion <br /> G. Restricted area service entrances are exempt from door or gate requirements. Service water-heating systems, swimming pool water- <br /> D o requirements provided that no public access is available. heating systems, spa water-heating systems and the controls for those <br /> � H. Lifeguarded pools are not required to have a self-closing, self-latching systems shall be commissioned and completed in accordance with <br /> J_I- gate during the period a pool is in use. Facility gates shall be closed Section C408. <br /> SUCTION PIPE and locked during nonuse periods. `�• SUCTION PIPEQ � `' '�I. Barrier heights are measured on the side outside the pool enclosure area PIPING W�4L� , ►oOwners shall ensure that surrounding ground levels, structures, or Plastic, 1-1/2" minimum diameter unless otherwise noted; Type 1 PVC `' '1` ' 'y'HYDROSTATIC VALVE landscaping do not reduce the effective height of the barrier. Schedule 40, solvent weld. All piping must be bedded and backfilled per the AS REQUIRED manufacturer's recommendations. ``STEPSii; e �,Edge of pool steps shall be of contrasting color from body of pool Steps HOSE BIBBS e-0- 'C - / Tshall be of non-slip tread finish. Steps shall have a minimum twelve inch Provide bibbs with vacuum breakers adjacent to walks. (By Others) �� <br /> MAIN DRAIN DETAIL 1 MAIN DRAIN DETAIL AIL unobstructed, horizontal tread depth and a minimum two hundred forty <br /> square inch surface area. Pool risers shall have an uniform height between WASTE WATER 07-11-19 <br /> POOL NTS SPA NTS032 <br /> 7.5 inches (preferred) and 10 inches, except for the bottom riser which To be disposed of through air gap. The air gap shall be a minimum of <br /> ®� may be plus or minus 2 inches of the uniform height. Spa risers shall two times the filter waste pipe diameter. <br /> be similar to those for the pools, except for the bottom riser which may <br /> be less than uniform height. See Pool/Spa Section or Step Detail for step FLOOR DRAW <br /> requirements. Provide floor drain or equal with trap. Provide drain for backwash line to c, <br /> terminate above grate, as noted above. N <br /> BONDING <br /> All metallic components of the pool shall be bonded and grounded in MAKE-UP WATER w <br /> conformance to the National Fire Protection Association Electrical Code Section If not otherwise provided for in the drawings, make-up water shall be ~ <br /> 680.26(B). provided by hose bibb located in pool deck area by Owner. Vacuum breaker zz ccn <br /> protection shall be provided. Provide water supply to equipment room protected <br /> OPERATION OF POOL with state approved reduced pressure backflow prevention device. c5~. w ' <br /> It is the owner's responsibility to operate in compliance with rules and cK o <br /> regulations of the Washington State Department of Health. LIGHTING 1 N co <br /> Provide not less than 30 foot-candles intensity measured at the surface of z N. <br /> "STAFF ONLY SIDS 4X4 KEY DISABILITY ACCESS co <br /> indoor pools and spas; 10 foot-candles for outdoor facilities; 10 foot-candles o Q ,-- <br /> ACCESS ON BOTH SIDES. 4X4X1 3/8" Provide "person with disability access per applicable regulations. for pool deck; 20 foot-candles for locker rooms, equipment rooms I <br /> METAL BOX HOUSING AT HARDWARE and restrooms. Provide protective shielding. Indoor pools shall have z w w <br /> co <br /> PENETRATION LOCATION. ATTACHED TO Z <br /> GATE FRAME. COORDINATE GATE WIDTH DRINKING FOUNTAINS emergency lighting per UL 924. (By Others) d <br /> 2 GATE HINGES 1- O <br /> TOP AND BOTTOM WITH FRAME WIDTH. Provide drinking fountains per Architectural Plans. (By Others) o J j <br /> 45" MIN. VERTICAL DIS VENTILATION/HEATING/COOLING (As Applicable) L`W o w N <br /> DISTANCE. 3 -0 NOTE: Provide ventilation conforming to the ASHRAE pool facility standards for = co <br /> f/ / FIRE DEPARTMENT KNOX BOX AT See Architectural Plans for Building, Fence, Electrical, Ventilation and indoor facilities. Provide heating and cooling per state energy code and other w <br /> ALL ENTRY GATES' Mechanical Details. agencies. <br /> I (By Others - See Mechanical Plans) 0 <br /> O 3 BACKFLOW PREVENTION SHOWER FACILITY <br /> - Provide non-atmospheric backflow prevention devices on plumbing fixtures Provide means to prevent maximum temperature from exceeding 110° F. <br /> SOUR PANELS ATTACHED connected to the potable water system which serve the pool related facilities. (By Others) <br /> . TO GATE FRAME, PLATE, <br /> AND VERT PICKETS. <br /> INSULATION EMERGENCY EQUIPMENT <br /> During the period the facility is open for use, the following is <br /> Provide insulation on exposed recirculation system within the contained Z <br /> PANIC HARDWARE ON INSIDE OF required: W <br /> _ space per WSEC Section 403.2.9 for pools and spas heated to greater W <br /> A ALL POOL GATES, PROVIDE ALL A. Telephone within one minute access. 1--- <br /> POOL ENTRY GATES WITH TENANT 95° F. Pool design temperature = 83°F. �C <br /> { B. Standard 16 unit first-aid kit and blanket reserved for emergency I - CO <br /> KEYED ACCESS AND ADA LEVER Spa design temperature = 103'Ft and not to exceed 104'F per use. Z <br /> o \ HANDLE ON THE OUTSIDE. Chapter 246-260 WAC, C. Provision of a clearly marked emergency shut off switch for turning <br /> TENANT ACCESS TO BE UNITED off all pumps. Switch shall be equipped with an audible alarm Q ' <br /> TO DAYLIGHT HOURS ONLY. <br /> to alert others at the. area of the facility. The switch shall be W� � <br /> accessible to the public and located within 15 feet of the spa. W W - I <br /> I SIGNAGE AND TESTING EQUIPMENT Li L <br /> i j <br /> '") RECEDDED STRIKE FLUSH Provide signage and testing equipment in conformance with applicable W c <br /> WITH FRAME POOL & SPA SYSTEM COMMISSIONING <br /> regulations. <br /> DESCRIPTION EQUIPMENT/FEATURE TEST BY EQUIPMENT <br /> CC <br /> Proper housing to protect equipment shall be provided. Provide combustion air F- <br /> I 1 \ qf.\\ I and venting of combustion gassesper manufacturer's requirement and codes w <br /> 3/32X9X36' PLATE ATTACHED CONTINUOUS OPERATION (By Others - See Mechanical Plans. 3 <br /> "' TO GATE FRAME WITH HOLES POOL & SPA RECIRCULATION PUMPS RECIRCULATION PUMPS POOL CONTRACTOR w <br /> FOR HARDWARE ATTACHMENTS. DESIGN FLOW RANGE ° <br /> a <br /> SELF CHEMICAL STORAGE DATE <br /> CLOSING Store chemicals in accordance with the manufacturer's requirements to minimize <br /> Q d TIMED OPERATION 15 MINUTE TIMER 07-1 1 -19 <br /> SPRING METAL FRAME ,IAMB, ATTACHED SPA JET PUMP JET PUMP ( ) POOL CONTRACTOR health and safety risks. Ensure proper hazard placards are posted on the <br /> 1" SQUARE PAINTED IRON HINGE To POST, BOTH SIDES. PROVIDE DESIGN FLOW RANGE exterior door to the chemical storage area. Provide separate room from DRAWN <br /> rn STOPS, BUMPERS AND SILENCERS. pool equipment room when feasible. (By <br /> PICKETS AT 4' o.c. (TYP) PILOT & SWITCH OPERATOR ACCESSIBLE Others) J.M.A. <br /> T <br /> POOL AND SPA HEATING POOL & SPA HEATERS POOL SET POINT TEMP = 82'F POOL CONTRACTOR DESIGNED <br /> SPA SET POINT TEMP = 103'F <br /> h. 8„ CONCRETE SUPPORT CONTROLS INACCESSIBLE TO BATHERS APPROVED J.J.D. <br /> o <br /> POOL AND SPA COVER COVERS PROVIDED & CUT TO FIT POOL CONTRACTOR J.J.D. <br /> • <br /> PROJECT NO. <br /> 0 <br /> N EXTERIOR FENCE DETAIL <br /> ol <br /> NTS NOTE 2192061 <br /> N SHEET NO. <br /> rn REFERENCE WSEC SECTION 408 FOR COMMISSIONING. <br /> o cp VI <br /> cv <br /> s <br /> J <br /> O <br /> 5 of 5 Sheets <br />