Mr. John Hadley <br />EMA Investments, LLC <br />Plan Check Number: B1809-011, First Review <br />December 12, 2018 <br />distance between the doors and windows exceeds 24 inches, or the drawings shall <br />specify the window to be safety glazing. <br />22. No additional comment. <br />23. This comment has not been addressed. The Partial Floor Plan on Sheet 1-of-2 indicates the <br />presence of a hood and stove in the Kitchen. The response identifying the hood as a <br />deferred submittal is not sufficient. The following comments should be addressed: <br />a. Requirements for commercial kitchen hoods are governed by IMC Section 507. The <br />expected hood installation (i.e., Type I or Type II) should be specified in the drawings. <br />General Note 4 on Sheet 1-of-2 states that `ono deep frying or grease laden food" <br />cooking will occur. If a Type II hood is intended, additional documentation <br />substantiating that the proposed activity qualifies for use of a Type II hood shall be <br />submitted for review. Note that it is presumed the proposed activity will not qualify for <br />use of a residential hood per IMC Table 507.1.2. <br />b. The type of cooking appliance (e.g., medium duty, heavy duty, etc.) should be clarified. <br />The type shall be as indicated by the manufacturer's specifications on the appliance. <br />c. The requirements for grease ducts for commercial kitchens hoods are provided in IMC <br />Section 506. The requirements for the intended hood shall be specified in the drawings, <br />including but not limited to clearances. Note that the hood likely must be routed to the <br />exterior wall and run up the outside of the building. The proposed path for the duct <br />should be shown. <br />d. The tenant space is required to have a 1-hour separation from the remaining building. <br />The duct shall be located within a rated shaft where it penetrates rated assemblies. Fire <br />dampers are not allowed. See IBC Sections 717.5.3 Exception 5 and 717.6.2 Item 1. <br />24. This comment has not been addressed. The Kitchen may require the installation of a grease <br />trap. The response identifying the grease trap as a deferred submittal is not sufficient. <br />These documents have not been reviewed for the treatment of oil or grease that may enter <br />the City of Everett sewer system. Contact Inductrial Pretreatment at (425)257-8240 <br />regarding pretreatment or grease removal requirements. The drawings shall specify the <br />requirement to install a grease trap if required. See Everett Municipal Code Chapter 14.42. <br />25. No additional comment. <br />26. This comment does not appear to be addressed. The Reflected Ceiling Plan on Sheet 2-of-2 <br />indicates ceiling fans for the bathrooms that penetrate the rated ceiling membrane. The <br />following comments shall be addressed: <br />a. A note shall be provided requiring the fans to be provided with listed ceiling radiation <br />dampers per IBC Section 717.6.2 Item 2. The fan listing shall be specified. <br />b. A note shall specify a minimum ventilation rate of 50 CFM/FTz for each fan per IMC <br />Table 403.3.1.1. <br />(� 3200 Cedar Street 425.257.8800 everettpw@everettwa.gov <br />�/ Everett, WA 98201 425.257.8882 fax everettwa.gov <br />