• <br /> 5.Future Tenant Space Con Sheet A1.00 appears to be intended as a storage <br /> occupancy based on the specified"300"occupant load factor. The space appears to <br /> have a total area of approximately 9,000 SF including the upper level, resulting in an <br /> occupant load of 30. The space requires separate male and female restrooms per <br /> IBC Section 2902.2(WAC). <br /> Response: <br /> This area is not intended to be a separate tenant area. It is an accessory <br /> storage area connected to the Tenant B space.The total occupant load for <br /> Tenant B and the storage area is below the 100 total occupants that would <br /> trigger separate restrooms for a Mercantile Occupancy.(Refer to IBC 2902.2.4 <br /> of the Washington State Amendments to the IBC) <br /> 6. Glazing Elevations 2/A3.10 and 3/A3.10 require safety glazing per IBC Section <br /> 2406.4. <br /> Response: <br /> An overlay has been added to the Glazing Elevations to denote the locations of <br /> required safety glazing. (See 2,3/A3.10) <br /> 7.A site plan has not been provided with the proposed project as required by IBC <br /> Section 107.2.5. Accessible spaces should be provided per IBC Section 1106.1. <br /> Response: <br /> Site Plan added to the set showing existing parking stalls and ADA parking <br /> area.Associated site details have been added to the set(See A2.00 and A6.01). <br /> Thank you, <br /> Dustin Thor akson AIA <br /> Principal <br /> FREIHEIT Architecture 1425-827-2100 <br /> 6700 108th Ave NE <br /> Intake Response Comments <br /> Page 2/2 <br /> Z) <br />