r 1 <br />4. Provide minimum 5.7 square feet for egress window in bedroom B-104. (R310.2.1. IRC) <br />Window size has been revised to provide min. 5.7 S.f. please see sheet A3.1. <br />5. Specify tempered safety glass in hazardous location. Show on plans. (R308 IRC) <br />Tempered safety glass locations have been called out on floor plans, sheets A3.0, A3.1 & A3.2. <br />6. Provide minimum 36inch landing, measured in the direction of travel, at least as wide as the <br />stairs in room C-101. Show on plans. Landings have been dimensioned in room C-101 to be min. <br />36" please see sheet A3.1. <br />7. Provide stair details and sections for interior and exterior stairs. Specify all components and <br />connections including stringer to landing, (provide specific hanger at stringers) guard to stair etc. <br />Specify handrail size location and connection. Return ends to the wall. Show on plans. Verify 2 <br />stringers is adequate for the required design loads on stairs. <br />Please see stair, guard and handrail details that have been added to sheets A10.1 & A10.2. Also <br />see revised stair detail 13 on sheet A10.0. <br />8. Provide details(s) and/or section(s) for exterior and interior guards per section R312. Show all <br />connections including attachment to the deck or house as applicable. <br />Please see stair and guard details that have been added to sheets A10.1 & A10.2. <br />9. Specify all connectors for roof assembly. Show diameter and length of all screws used to attach <br />components of roof assembly. <br />Roof connectors have been added to detail 14/A10.0. <br />10. Provide detail for the fire -resistance rated wall assembly where stairs are back to back and the <br />wall framing is fullheight from the basement to the roof. <br />Please see detail 25 that has been added on new sheet A10.1. <br />11. Specify which whole house ventilation system you are choosing to use for each separate <br />townhome. Provide the code requirements for the whole house ventilation system, do not <br />simply reference the code section. <br />Whole house ventilation system specifics and notes have been added to sheet A0.1 for units A, B <br />& C. Location of whole house fans are called out on.Upper floor plan sheet A3.2 for units A, B & <br />C. <br />12. Show how all units are heated. Dwellings using electric zonal heating as the primary heat source <br />shall install an inverter driven ductless mini -split heat pump in the largest zone in the dwelling. <br />Show location of heat pump and heat exchanger on plans and site plan (cannot be located in <br />side or front yard setback). <br />