Mr. Mark Thunberg <br />Snohomish County Property Management <br />Plan Check Number: B1802-011, First Review (Structural) <br />June 18, 2018 <br />27. The building has reentrant corners at all levels (i.e., Sheets S-202 through S-206) resulting in a <br />Type 2 horizontal structural irregularity per ASCE 7-10 Table 12.3-1. The design forces for the <br />diaphragm connections to the shear walls and collectors, and the collectors and their <br />connections to the shear walls, shall be increased 25%. Calculations verifying the design <br />considering the increased loading shall be submitted for review. See IBC Section 1613.1 and <br />ASCE 7-10 Section 12.3.3.4. <br />28. The building has a reentrant corner at Grid F'/12.1 at all levels (i.e., Sheets S-202 through S- <br />206). The chord for the addition's diaphragms along Grid 12.1 should be developed into the <br />existing structure. Calculations substantiating the chord development should be submitted for <br />review. See IBC Section 1613.1 and ASCE 7-10 Section 12.10.1. <br />29. The concrete shear wall on Grid C/8-10.5 is discontinuous at the existing concrete -topped steel <br />decks per Details 9, 10, 14, 15, 19, and 20 on Sheet S-601. The wall changes thickness from <br />16 to 10 inches over its height. Elevation 6/S-301 indicates coupling beams are bisected by <br />the existing decks. The following comments should be addressed: <br />a. The shear strength of the shear wall at the decks should be substantiated per the shear - <br />friction criteria of ACI 318-14 Section 22.9.3 with µ=0.7k per Table 22.9.4.2. See IBC <br />Section 1901.2. <br />b. Detail 11/S-311 does not appear to represent the conditions for the coupling beams. A <br />detail representing the conditions should be included, indicating the installation of the shear <br />reinforcement and accounting for the changes in the wall thickness. <br />30. The structural calculations do not appear to include a design for the addition diaphragms. <br />Calculations substantiating the design, including load transfer to the shear walls, shall be <br />submitted for review. The connection loads to the shear walls and collectors shall be increased <br />per ASCE 7-10 Section 12.3.3.4. See IBC Section 1604.1 and 1613.1. <br />31. Calculations shall be submitted for review substantiating the design of the collectors for the <br />addition. Collectors appear to be provided on Sheets S-202 through S-206 on Grid 12.1. <br />Verify if collectors are required at other locations, including but not limited to Grids F, G, K, and <br />16.1. Calculations shall include the connections between the collectors and the diaphragms <br />and shear walls. The collectors and connections shall include the load increases per ASCE 7-10 <br />Sections 12.3.3.4 and 12.10.2.1. See IBC Sections 1604.1 and 1613.1. <br />32. Calculations shall be submitted for review substantiating the design of the collectors between <br />the existing structure and the new shear walls. Collectors are provided on Sheets S-201 <br />through S-206 on Grids C/5-15, F/5-21, 16.1/E-F, and 19.1/E-F. Calculations shall include the <br />connections between the collectors and the diaphragms and shear walls. Note that Details <br />12/5-601 and 9/S-602 appear designed to transfer tension only; the calculations shall clarify <br />the transfer of compression loads. The collectors and connections shall include the load <br />increases per ASCE 7-10 Sections 12.3.3.4 and 12.10.2.1. See IBC Section 1604.1 and 1613.1. <br />Page 8 of <br />CITY OF EVERETT • 3200 Cedar Street • Everett, WA 98201 . (425) 257-8810 • Fax (425) 257-8857 <br />