Laserfiche WebLink
7. All headers shall be insulated with minimum R-10 rigid insulation per Table R402.1.1 <br />WSEC. Show on plans. <br />Response: See Sheet AO 2015 WSEC requirements. See additional Detail 21A3.0 <br />8. The Washington State Energy Code option #4 requires "To qualify to claim this credit, the <br />building permit drawings shall specify the option being selected and shall specify the <br />heating equipment type and shall show the location of the heating and cooling equipment <br />and all the ductwork." Show the location of all ductwork on the plans. <br />Response: We have Change concept to 1 a, 3a, 5a and 5c to qualify and see Sheet A2.0 <br />9. A minimum of 75% of lamps in permanently installed lighting fixtures shall be HIGH - <br />EFFICACY lamps. <br />Response: See Sheet AO 2015 WSEC requirements. <br />10. The slab -on -grade in the garage shall slope to the main vehicle entry doorway. <br />Response: Added Note <br />11. Provide minimum 36-inch landing not more than 7-3/4 inches below the finished floor at <br />all entrance/exits. Show on plans. <br />Response: Added to Floor Plan <br />12. Provide minimum 36-inch landing to the top and bottom of all stairs. Show on plans. <br />Response: Added to Floor Plan <br />13. Provide minimum 100 CFM exhaust fan in the Kitchen. Please show size and location on <br />floor plans. <br />Response: Added to floor Plan A2.0 <br />14. Show water heater equipment type, minimum equipment efficiency and location on plans. <br />Response: Added to Floor Plan in Garage sheet A2.0 "Navien Tankless Water Heater 97% <br />Todd Borseth, Architect <br />