James Bronder <br />From: <br />James Bronder <br />Sent: <br />Friday, October 4, 2019 11:34 <br />To: <br />Jeff Heilman <br />Subject: <br />C1908-021 Structural Correction Comments <br />Hi Jeff, <br />Architectural/Structural comment is as follows: <br />1. On Sheet A3.0, interior walls called out as 102.1 in the section cut, appear to be bearing walls. If these walls are <br />intended to be non -load bearing, please provide details de -coupling the walls from the trusses otherwise please <br />provide calculations and details justifying that the trusses members can withstand reactions from the bearing <br />walls as well as withstand lateral loads, as these appear to also be shear walls. Also, please note that it appears <br />that footings are to be provided if these interior walls are intended to be bearing/shear walls. IRC R301.1.3. <br />Thank you, <br />_ James Bronder, P.E., S.E. <br />Associate Engineer — Plans Examiner I Permit Services <br />425.257.8810 13200 Cedar Street, 2nd Floor, Everett, WA 98201 <br />EVERETT Hours: Monday — Friday 7:30am-12:OOpm and 1:OOpm-4:OOpm <br />everettwa.gov I Facebook I Twitter <br />Note: Emails and attachments sent to and from the City of Everett are public records and may be subject to disclosure pursuant to the Public <br />Records Act. <br />1 <br />