2015 Washington State Energyjie Compliance Forms for Commercial, R2 and R3 over dries and all R1 - Page 5 of 20
<br />2015 Washinaton State Enerov Code Compliance Forms for Commercial Buildings including R2 & R3 over 3 stories and all R1 Revised January 2017
<br />Project Title: SnoPUD7513C Date 18/02/27
<br />The following information is necessary to check a permit application for compliance with the mechanical systems and equipment requirements of the
<br />Washington State Energy Code, Commercial Provisions.
<br />Applicable
<br />Code Section
<br />Code Provision
<br />I
<br />Information Required - Must be in permit documents
<br />Location in
<br />Building Department
<br />JEL,no,nall
<br />Documents
<br />Notes
<br />Equipment - Sizing, Performance and Type
<br />Identify equipment to be used in manufacturing, industrial or commercial processes that do not
<br />na
<br />C403.1
<br />Exempt process equipment
<br />provide space conditioning; identify provisions applicable to this equipment per C403.1
<br />exception
<br />Provide load calculations performed per ASHRAE Std 183 or equivalent, using design
<br />NA
<br />C403.2.1
<br />Load calculations
<br />parameters per C302 and Appendix C; include load adjustments to account for energy
<br />recovery
<br />Equipment and system
<br />Indicate that output capacities of heating and cooling equipment and systems are no greater
<br />NA
<br />C403.2.2
<br />than the smallest available equipment size that exceeds the calculated loads; note exceptions
<br />sizing
<br />taken
<br />C403.2.3
<br />HVAC equipment
<br />Provide equipment schedules on plans or complete MECH-EQ forms indicating type, capacity,
<br />NA
<br />C403.2.3.2
<br />performance requirements
<br />rated and WSEC minimum efficiencies for all heating and cooling equipment; include supply
<br />C403.2.13.1
<br />(efficiency)
<br />and OSA cfms and operating hours for all air systems; identify heating and cooling equipment
<br />that does not have a corresponding WSEC minimum efficiency (manufacturer rated)
<br />List all motors >_ 1/12 hp (that are not integral to a rated piece of equipment) in the mechanical
<br />or electrical equipment schedules on plans; indicate hp, rpm, number of poles and rated
<br />NA
<br />C405.8
<br />Electric motor efficiency
<br />efficiency, or exception applied
<br />C403.2.14
<br />For fractional hp motors (1 /12 - 1 hp), indicate whether they are an electronically commutated
<br />motor, have rated efficiency of at least 70%, or exception taken
<br />For all HVAC fan systems that provide heating and / or cooling, provide system total
<br />nameplate hp in MECH-FANSYS-SUM form
<br />For all applicable HVAC systems with total fan motor hp > 5hp, verify fan system motor hp or
<br />NA
<br />C403.2.11.1
<br />Fan power limitation
<br />bhp complies with fan power limits per equations in Table C403.2.11.1(1), provide MECH-
<br />FANSYS form for each system
<br />na
<br />C403.2.11.2
<br />Motor nameplate hp
<br />For all applicable HVAC systems with total fan motor hp > 5hp, indicate fan motors specified
<br />are the smallest available motor hp size greater than fan bhp, note exceptions taken
<br />For all applicable HVAC systems with total fan motor hp > 5hp, identify in equipment schedule
<br />na
<br />C403.2.11.3
<br />Fan efficiency
<br />all fans required to comply with fan efficiency grade and indicate rated FEG is>_ 67, or
<br />exception taken; indicate these fans are sized so total efficiency is within 15 /o of the fan
<br />maximum total efficiency
<br />na
<br />C403.2.11.4
<br />Group R occupancy exhaust
<br />For all exhaust fans < 400 cfm in Group R occupancies, indicate in equipment schedule the
<br />fan efficacy
<br />fan flow rate and efficacy (cfm/watt), or exception taken; refer to Table C403.2.11.4 (CE-57)
<br />Variable flow capacity -
<br />For fan motors >_ 7.5 hp, indicate method of variable flow control (VSD or equivalent method) in
<br />na
<br />C403.2.13
<br />fans
<br />equipment schedule, or exception taken; for equivalent method for an HVAC system refer to
<br />HVAC System Controls for additional requirements
<br />na
<br />C403.2.3
<br />Maximum air cooled chiller
<br />For chilled water plants and buildings with > 500 tons of cooling capacity, indicate air-cooled
<br />capacity
<br />chiller capacity is < 100 tons, or exception taken
<br />Large capacity cooling
<br />For buildings with>_ 300 tons of cooling capacity, indicate method of multi -stage or variable
<br />na
<br />C403.4
<br />o
<br />capacity control (VSD, multiple staged compressors, or max capacity of any single unit < 66 /o
<br />systems
<br />of the total)
<br />Non-standard water-cooled
<br />For water-cooled centrifugal chillers not designed for operation at standard conditions, provide
<br />na
<br />C403.2.3.1
<br />centrifugal chillers
<br />calculations documenting maximum full load and part load rated equipment performance
<br />requirements
<br />C403.2.13.1
<br />Centrifugal fan open -circuit
<br />For open -circuit centrifugal fan cooling towers with � 1,100 gpm capacity, indicate cooling
<br />na
<br />C403.4.3.2
<br />cooling towers
<br />towers comply with efficiency requirements for axial fan open circuit cooling towers
<br />For single boilers with > 500,000 Btulh capacity, indicate multi -stage or modulating burner
<br />na
<br />C403.4.2
<br />Large capacity boiler
<br />For boilers stem (single or multiple) with > 1,000,000 Btulh capacity,
<br />y ( g p ) p y, indicate turndown ratio
<br />C403.4.2.5
<br />systems
<br />y
<br />per Table C403.4.2.5 and method (multiple single input boilers, modulating boilers, or
<br />combination)
<br />Variable flow capacity -
<br />For pump motors z 7.5 hp, indicate method of variable flow control (VSD or equivalent method)
<br />na
<br />C403.2.13
<br />in equipment schedule, or exception taken; for equivalent method for a hydronic system refer
<br />pumps
<br />to Hydronic System Controls for additional requirements
<br />NA
<br />C403.2.3
<br />Gas and oil -fired forced air
<br />For forced air furnaces with capacity z 225,000 Btulh and all unit heaters, indicate in
<br />furnace and unit heaters
<br />equipment schedule intermittent ignition or IID, flue or draft damper, and rated jacket loss
<br />NA
<br />C403.2.4.8
<br />Combustion heating
<br />For combustion heating equipment with output capacity > 225,000 Btulh, indicate modulating
<br />equipment
<br />or staged combustion control
<br />NA
<br />C403.2.3.3
<br />Packaged electric heating /
<br />Verify all packaged electric equipment with > 6,000 Btu/h cooling capacity and any amount of
<br />cooling equipment
<br />heating is a heat pump; include in equipment schedules
<br />na
<br />C403.2.12
<br />Heating outside a building
<br />Indicate systems providing heating in non -enclosed outdoor occupied spaces are radiant
<br />systems; refer to HVAC System Controls for additional requirements
<br />na
<br />C403.2.7.1
<br />Kitchen exhaust hoods
<br />Indicate on plans the type, duty and exhaust air rate of each kitchen hood, refer to HVAC
<br />System Controls for additional requirements
<br />Outdoor supply air, exhaust
<br />Indicate locations of OSA intake, and exhaust and relief outlet dampers on plans; indicate
<br />NA
<br />C403.2.4.3
<br />and relief dampers
<br />whether dampers are Class 1 motorized, or gravity and exception taken (include leakage
<br />rating, cfmisf); refer to HVAC System Controls for additional requirements for OSA dampers
<br />Indicate locations of return air dampers that are integral to economizer operation; verify
<br />na
<br />C403.2.4.3
<br />Return air dampers
<br />dampers are motorized; indicate whether dampers are Class 1, or within packaged.gquipment
<br />eligible for leakage rating exception (include leakage rating, cfm/sf) / 7
<br />
|