WELDING <br />PART2- PRODUCTS <br />2.1 <br />GENERAL <br />PART 3- EXECUTION <br />A. Gas cylinders shall be furnished by the Owner and installed by the Mechanical Contractor. <br />3.01 GENERAL <br />2.2 <br />Welding PIPING (acetylene, argon, c25, carbon dioxide, nitrogen) <br />A. Workmanship shall be first-class in every respect. The gas manifold systems shall comply with National Fire Protection Association Booklet, <br />NFPA No. 51, and local codes. <br />A. Schedule 40 black pipe and welding fittings. System shall be welded throughout with exception of fittings on individual drops for connection <br />of valves and regulators which shall be threaded. <br />3.02 CLEANING <br />1. P!pe Joints: All joints in the pipe, except those at valves and equipment requiring screwed connections, shall be welded. Suitable <br />A. Before erection all pipes, valves and fittings (except those supplied expressly cleaned for this service by the manufacturer) shall be <br />malleable iron fittings shall be employed for the installation of equipment provided with threaded connections, <br />thoroughly cleansed of oil, grease, or other combustible materials by washing in a hot solution of sodium carbonate or trisodium phosphate <br />2. Screwed Connections: A thin paste of litharge and glycerin shall be applied to the external threads only. Leave first thread clean if <br />mixed in the proportions of one pound to three gallons of water. Piping shall be thoroughly blown out after assembly to remove foreign <br />possible. Use of excess glycerin shall be avoided, <br />materials with oil -free air or oil -free nitrogen: <br />3. Fittin s: Where equipment requiring screwed connections is encountered, all fittings shall be threaded standard of extra heavy <br />3.03 PROCESS <br />malleable iron as required. Use of cast iron fittings is prohibited. <br />A. The welding shall be done by the oxyacetylene process. <br />2.03 <br />Welding PIPING (OXYGEN) <br />3.4 SECTION VALVES <br />A. Copper Tube: ASTM B 319, Type L, seamless, drawn temper that has been manufacturer cleaned, purged, and sealed for medical gas <br />A, Shall be installed in accessible locations and supported in such a manner that forces used in their operation shall not place strain upon the <br />service or according to CGA G-4.1 for oxygen service. Seals shall remain in place until final assembly. <br />pipe and joints. <br />1. General Requirements for Copper Fittings: Manufacturer cleaned, purged, and bagged for oxygen service according to CGA G-4.1. <br />3.05 SAFETY DEVICES <br />2. Wrought®Copper Fittings: ASME B16.22, MSS SP-73, with dimensions for brayed joints. Cleaned and capped for oxygen service. <br />A. When required, pipe line hydraulic arresters, bursting disc assemblies and relief valves shall be correctly installed and properly supported. <br />3. Copper Unions: ASME B16.22 or MSS SP-123, wrought copper or cast -copper alloy. <br />4, Brazing Filler Metals: AWS A5.3/A5.3M, SCuP Series, copper -phosphorus alloys for general -duty brazing unless otherwise Indicated. <br />3.06 HAZARDS <br />B. Schedule 40 black pipe and welding fittings. Order pipe, tubing and fittings from manufacturer as pre -cleaned and factory sealed for oxygen <br />A. Exposed piping conveying Fuel gas or Oxygen shall not be erected under or near high -voltage overhead power lines. Underground piping <br />use. System shall be welded throughout with exception of fittings on individual drops for connection of valves and regulators which shall be <br />conveying Oxygen shall not be installed in the same trench, duct or tunnel conveying power lines or fuel oil lines. <br />threaded, <br />3.7 ERECTION <br />1. P!pe Joints: All joints in the pipe, except those at valves and equipment requiring screwed connections, shall be welded. Suitable <br />A: All pipe shall be cut accurately to measurements obtained at the site of the system and shall be installed without springing or forcing. All <br />malleable iron fittings shall be employed for the installation of equipment provided with threaded connections. <br />piping shall be protected against mechanical injury in a manner satisfactory to authorities having jurisdiction. <br />2, Screwed Connections: A thin paste of litharge and glycerin shall be applied to the external threads only. Leave first thread clean if <br />possible. Use of excess glycerin shall be avoided. <br />3.06 TESTING <br />1 Fittin s: Where equipment requiring screwed connections is encountered, all fittings shall be threaded standard or extra -heavy <br />A. Joint Test; After erection of piping, but prior to the installation of the service or station outlet valves and safety equipment assemblies, the <br />malleable iron as required. Use of cast iron fittings is prohibited. <br />system shall be subject to a test pressure equal to twice the required working pressure by means of cylinder water -pumped nitrogen. This <br />test pressure shall be maintained until each joint has been thoroughly examined for leaks by means of soap suds or leak_ detecting solution. <br />2.04 <br />REGULATORS, VALVES & EQUIPMENT <br />Wipe joints clean after test. <br />A. Oxyq�n Station Drops: Shall be RexArc Part No. 2®04�16/0G. <br />1. All leaks shall be properly repaired and the system retested. <br />B. Acetylene Station Drops: Shall be PexArc Pan No.2-04-161 OR. <br />B. Joint Test: After installing service or station outlet valves and safety equipment assemblies, the system shall again be subjected to a test <br />Ca Argon Station Drops: RexArc Part No. 2-04-1603Y <br />pressure equal to 1_1/2 times the required working pressure by means of cylinder water pumped nitrogen. This test pressure shall be <br />maintained until each joint has been thoroughly examined for leaks by means of soap suds. Wipe joints clean after test. All leaks shall be <br />D. C25 Station Drops; RexArc Part No. 2-04-1603Y <br />properly repaired and the system retested. <br />E. CO2 Station Drops; RexArc Part No. 2-04-1600 <br />C. Final Test: Shall be a twenty-four hour standing pressure test with cylinder water -Pumped nitrogen at 1_1/2 times required working pressure <br />to check to completeness of prior joint pressure tests. <br />F. Flashback Arrestor: Provide flashback arrestor for fuel gas manifolds, provide with relief valve, shutoff valves, and vent thru roof. <br />3.09 PAINTING, PROTECTIVE COATING <br />G. Acetylene Manifold: Shall be RexArc Part No. 3-04-0543R-12. <br />A. Before painting, all piping shall be thoroughly wire brushed to remove all rust, scale, dirt, etc., that may have formed on the surface and shall <br />H. Oxygen Manifold; Shall be RexArc Part No. 3-04-0431 G-12 manifold for 6 cylinders; 3 usage and 3 standbys. <br />be covered or painted with a suitable corrosion_ resisting material. <br />1. Amon Manifold: ;Shall be RexArc Pan No. 3-04-0431A-3 <br />B. The service or station outlet drops or risers shall be identified by affixing a decal, with the name of the gas in the pipe. <br />J. C25 Manifold: Shall be RexArc Pan No. 3-04-0543Y-6 <br />K. COI Manifold: Shall be RexArc Pan No. 3-04-0431 C-8 <br />NOTESGENERAL / SPECIFICATIONS <br />1. <br />ALL WORK PERFORMED SHALL BE DONE IN STRICT ACCORDANCE TO ALL APPLICABLE MECHANICAL, BUILDING, ENERGY, FUEL GAS, AND <br />6. CONSTRUCT DUCTWORK ACCORDING TO WASHINGTON STATE ENERGY CODE SECTION C403.2.3.3. ALL DUCT WORK SHALL BE PRIMED <br />LOCAL CODES, WITH AMENDMENTS. <br />GALVANIZED SHEET STEEL, LOCK FORMING <br />QUALITY, FABRICATED IN ACCORDANCE TO SMACNA STANDARDS. <br />2. <br />WHERE USED, THE TERM "PROVIDE" SHALL MEAN "FURNISH AND INSTALL". <br />7; PROVIDE TURNING VANES IN ALL MITERED RECTANGULAR DUCT ELBOWS & TEES. <br />3. <br />COORDINATE EQUIPMENT CONNECTIONS WITH MANUFACTURERS' CERTIFIED DRAWINGS. COORDINATE AND PROVIDE DUCT AND PIPING <br />TRANSITIONS REQUIRED FOR FINAL EQUIPMENT CONNECTIONS TO FURNISHED EQUIPMENT, FIELD VERIFY AND COORDINATE DUCT AND <br />3. ALL SUPPLY AND RETURN DUCTWORK SHALL BE INSULATED PER WASHINGTON STATE ENERGY CODE SECTION C403.2.3.2. <br />PIPING DIMENSIONS BEFORE FABRICATION. <br />9. OUTSIDE AIR DUCTS SERVING INDIVIDUAL SUPPLY AIR UNITS LESS THAN 2300 CFM SUPPLY CAPACITY SHALL BE INSULATED TO R-7. <br />4. <br />LOCATIONS AND SIZES OF FLOOR, AND WALL OPENINGS SHALL BE COORDINATED WITH OTHER TRADES INVOLVED. INCLUDE IN THE COST <br />OF MECHANICAL WORK, CUTTING, CORING, PATCHING AND PAINTING OF EXISTING WALLS, CEILINGS, FLOORS AND ROOFS AS REQUIRED TO <br />10. PROVIDE TEMPORARY COVERS OVER OPEN ENDS OF EQUIPMENT AND DUCTWORK DURING CONSTRUCTION. <br />ACCOMMODATE WORK AS INDICATED IN THE MECHANICAL CONTRACT DOCUMENTS, UNLESS SPECIFICALLY SHOWN ON ARCHITECTURAL <br />11. DAMPERS SHALL HAVE A MAXIMUM LEAKAGE RATE OF 4 CFM PER SQUARE FOOT AT 1" W.C. <br />DRAWINGS. <br />12. PROVIDE EACH ZONE WITH THERMOSTATIC CONTROLS THAT PROVIDE A DEADBAND OF AT LEAST 5 DEGREES FAHRENHEIT IN WHICH <br />5. <br />CLEAN THE JOB SITE DAILY AND REMOVE FROM THE PREMISES ANY DIRT AND DEBRIS CAUSE BY THE PERFORMANCE OF THE WORK <br />HEATING OR COOLING ENERGY IS CAPABLE OF BEING SHUT OFF OR REDUCED TO A MINIMUM, THERMOSTAT SHALL BE CAPABLE OF <br />INCLUDED IN THIS CONTRACT. BEFORE SUBSTANTIAL COMPLETION, CLEAN EQUIPMENT, FIXTURES, EXPOSED DUCTS, PIPING AND SIMILAR <br />THERMOSTATIC SETBACK, AUTOMATIC SETBACK AND SHUTDOWN, AND AUTOMATIC START CAPABILITIES PER WASHINGTON STATE ENERGY <br />ITEMS. <br />CODE SECTION C403.2.4.2.] <br />6. <br />PROVIDE EQUIPMENT THAT FITS INTO THE SPACE ALLOTTED AND ALLOWS ADEQUATE ACCEPTABLE CLEARANCE FOR INSTALLATION, <br />13. PROVIDE DUCT ACCESS DOORS AT DUCT SMOKE DETECTORS, BACKDRAFT DAMPERS, MOTORIZED CONTROL DAMPERS, FIRE DAMPERS, <br />REPLACEMENT, SERVICING, AND MAINTENANCE, COORDINATE WITH OTHER TRADES TO ENSURE NO CONFLICT WITH REQUIRED <br />SMOKE DAMPERS, COMBINATION FIRE/SMOKE DAMPERS, DUCT MOUNTED COILS, DUCT AIRFLOW STATIONS AND LOUVER PLENUMS. <br />CLEARANCES. <br />NON-STRUCTURAL MECHANICAL COMPONENTS: <br />7. <br />CONTRACTOR SHALL OBTAIN & PAY FOR ALL PERMITS AND CONSTRUCTION FEES, FURNISH FINAL CERTIFICATE TO OWNER SHOWING <br />COMPLIANCE WITH CODE REQUIREMENTS. <br />1. HANGERS AND SEISMIC BRACING FOR THE MECHANICAL SYSTEMS SHALL BE DESIGNED AND PROVIDED BY THE MECHANICAL CONTRACTOR. <br />REFER TO CONTRACTOR SHOP DRAWINGS FOR LOCATIONS OF EQUIPMENT AND HUNG MECHANICAL SYSTEMS. THE MECHANICAL <br />3. <br />REFER TO TYPICAL DETAILS PROVIDED IN THIS DRAWING SET FOR DUCTWORK, PIPING, AND EQUIPMENT INSTALLATION, CONTRACTOR IS <br />CONTRACTOR SHALL COORDINATE THE SUPPORT SYSTEMS AND DESIGN LOADS FOR HUNG MECHANICAL SYSTEMS WITH THE GENERAL <br />RESPONSIBLE FOR CONFORMANCE WITH DETAILS, <br />CONTRACTOR AND OTHER TRADES THAT MAY BE IMPACTED. <br />9. <br />A SHORT DASH IN A SCHEDULE TABLE CELL INDICATES THAT THE COLUMN HEADING IS NOT USED OR NOT APPLICABLE TO THAT <br />DEMOLITION; <br />SCHEDULED ITEM. <br />1. EXISTING MATERIALS THAT ARE REMOVED SHALL NOT BE REUSED IN NEW SYSTEMS, EXCEPT WHERE INDICATED AS BEING RELOCATED. <br />10. <br />PROVIDE COMMISSIONING FOR MECHANICAL SYSTEMS. PROVIDE A COMMISSIONING PLAN OUTLINING ORGANIZATION, SCHEDULE, <br />NARRATIVE, RESPONSIBILITIES MATRIX, LIST OF EQUIPMENT TO BE TESTED, FUNCTIONS TO BE TESTED, CONDITIONS UNDER WHICH TESTS <br />2. CONTRACTOR SHALL REMOVE ALL PIPING, DUCTWORK, AND EQUIPMENT INCLUDING ALL ASSOCIATED INSULATION, HANGERS, VALVES, <br />SHALL BE PERFORMED, AND MEASURABLE CRITERIA FOR PERFORMANCE. COMMISSIONING SHALL BE PER C403 OF THE 2015 WSEC. <br />PLENUM WALLS, DAMPERS, WIREMOLD, WIRING, CONTROLS, AND APPURTENANCES ASSOCIATED WITH EACH PIECE OF EQUIPMENT, <br />11. <br />ALL PIPING & DUCTWORK IN FINISHED ROOMS OR SPACES SHALL BE CONCEALED IN A FURRED CHASE OR ABOVE THE HARD SUSPENDED <br />3. WHERE EXISTING ITEMS PENETRATE A WALL OR ROOF, CONTRACTOR SHALL PROVIDE INFILL AT (E) PENETRATIONS THROUGH WALL/ROOF <br />CEILING. COORDINATE WITH ARCHITECTURAL DOCUMENTS FOR FURRING & CHASE LOCATIONS & SIZES. <br />WITH LIKE MATERIALS. PATCH & REPAIR TO MATCH SURROUNDING SURFACES INCLUDING PAINT. <br />12. <br />ALL ELECTRICAL WORK SHALL BE PERFORMED IN ACCORDANCE WITH NFPA 70 STANDARDS AND LOCAL REQUIREMENTS, <br />4. CONTRACTOR SHALL PROVIDE TEMPORARY SUPPORT OF EXISTING MECHANICAL EQUIPMENT WHERE REQUIRED BY DEMOLITION OR <br />ALTERATION OF EXISTING STRUCTURE DURING CONSTRUCTION, COORDINATE WITH GC AND PROVIDE NECESSARY SUPPORTS AND <br />13. <br />ALL FIELD WIRING SHALL REQUIRE AN ELECTRICAL PERMIT AND SHALL BE PERFORMED BY A LICENSED ELECTRICIAN. <br />HANGERS TO MAINTAIN INTEGRITY, SAFETY AND PROPER OPERATION OF EXISTING MECHANICAL SYSTEMS. <br />14. <br />PROVIDE CLOSEOUT DOCUMENTATION PER WSEC. <br />5. MAINTAIN AND RESTORE (IF INTERRUPTED) ALL CONDUITS & CONDUCTORS, PIPING, & DUCTWORK PASSING THROUGH RENOVATED AREAS <br />AND SERVICING UNDISTURBED AREAS. <br />HVAC/SHEET METAL <br />6. REMOVE ALL ABANDONED DUCTWORK, PIPING, CONTROLS, WIRING, ETC., WHERE ACCESSIBLE IN RENOVATED AREAS. <br />1. <br />THE FIRST FIGURE OF DUCT SIZE CALLOUTS INDICATES DIMENSION OF FACE SHOWN OR INDICATED. DUCT SIZES ARE NET INSIDE <br />DIMENSIONS. PROVIDE ANY APPLICABLE DUCT LINING AND INSULATION PER THESE PLANS, <br />7. WHERE CONTROLS ARE DEMOLISHED, REMOVE WIRING BACK TO NEAREST CONTROL PANEL OR JUNCTION BOX. REMOVE ACCESSIBLE <br />CONDUIT, JUNCTION BOXES, ETC. <br />2. <br />DUCT SIZE NOT SHOWN SHALL BE SLED TO VELOCITIES NO GREATER THAN UP STREAM <br />SECTIONS USING SIMILAR ASPECT RATIOS: <br />3. OWNER SHALL HAVE FIRST RIGHT OF REFUSAL FOR ALL EQUIPMENT AND COMPONENTS REMOVED DURING. <br />3. <br />TOTAL STATIC PRESSURE NOTED IN SCHEDULES SHALL BE ASSUMED TO INCLUDE DUCT SYSTEM, TERMINAL UNITS, FILTERS, COILS, ETC. <br />9. CONTRACTOR SHALL PERFORM DEMOLITION IN NEAT AND SKILLFUL MANNER SO AS NOT TO DAMAGE OR DEFACE ANY CONSTRUCTION <br />THAT IS TO REMAIN. <br />4. <br />ALL SUPPLY AIR FILTERS SHALL BE MERVm3 RATED; <br />10. 1T IS THE CONTRACTOR'S RESPONSIBILITY TO INCLUDE ALL COSTS ASSOCIATED WITH NECESSARY DEMOLITION TO ALLOW NEW <br />5. <br />DUCTWORK SHALL BE 2.0" PRESSURE CLASS UNLESS OTHERWISE NOTED ON THESE DRAWINGS. <br />CONSTRUCTION SHOWN IN CONTRACT DOCUMENTS. <br />1 1 <br />INSTALL PER <br />!1 <br />CONNECTIONDIFFUSER <br />SCALE: DIAGRAMMATIC <br />WELD <br />23 37 00 <br />I TO BE DETERMINED <br />OVERHEAD <br />AT SITE <br />PIPE LINE <br />1/2" NON -RETURN <br />TYPE STATION VALVE <br />112Hx1/2"x1/2" M.I. <br />SCREWED TEE <br />HOSE <br />CONNECTION <br />PLUG CHAIN <br />NIPPLE <br />ASSEMBLY <br />(NOT IN USE) <br />STATION OUTLET <br />STATION DROP <br />LINE REGULATOR <br />DRIP LEG <br />4°-6" FROM <br />�V_1/2" M.I. PIPE <br />FINISHED FLOOR <br />CAP <br />WELD <br />STATION T"Y"PICAL DROP <br />nGAS <br />DIAGRAMMATIC <br />architect <br />MCGRANAHAN ARCHITECTS <br />mechanical engineer <br />BCE ENGINEERS <br />electrical engineer_ <br />ICE ENGINEERS <br />project_ <br />SNO-ISLE WELDING SHOP <br />client_ <br />MUKILTE0 SCHOOL DISTRICT NO.6 <br />Iocation_ <br />EVERETT, WA <br />issued_ <br />PERMIT 05 APR 21 <br />drawn_ <br />BH <br />checked_ <br />Sz <br />ORIGINAL SHEET IS 30" x 42" <br />copyright 2021 <br />all rights reserved <br />