• i <br /> SNO ISLE BENCH OVEN <br /> 30 DAY PEAK DEMAND CALCULATION WORKSHEET <br /> PANEL N <br /> NEC 220.87 AND WAC 296-46B-900(3)(j) <br /> 30-day demand study from : 4/14/2021 to 5/13/2021 <br /> Phase to Phase Voltage (Volts) : 208 <br /> Phases (1=Single Phase, 3=Three Phase) : 3 <br /> 30 Day Peak Demand On : 4/23/2021 = 15.31 Amps <br /> Apparent Peak Demand = 5.52 KVA <br /> NEC 220.87(2)adjustment factor X 1.25 KVA <br /> Adjusted Peak Demand = 6.89 KVA <br /> Seasonal adjustment factor X 1.00 KVA <br /> Seasonal adjustment peak demand = 6.89 KVA <br /> Occupancy adjustment factor X 1.00 KVA <br /> Occupancy adjustment peak demand = 6.89 KVA <br /> Other adjustement factor(s) X 1.25 KVA <br /> Measured Peak Demand with Adjustments = 8.62 KVA <br /> New Calculated Demand Load Added BENCH OVEN + 7.50 KVA <br /> Metered Demand Based <br /> CALCULATED DEMAND LOAD : 16.12 KVA <br /> CALCULATED DEMAND CURRENT : 45 AMPS <br /> 1 <br />