• <br /> Mr. Michael Snitko <br /> Washington Flippers, LLC <br /> Plan Check Number: CW1910-001, First Structural Review <br /> December 13, 2019 <br /> Lateral System: <br /> 21.The framing layout on Sheet S1 appears to indicate that the roof construction at the west end <br /> of the building has been completely revised, including the roof diaphragm (i.e., sheathing). <br /> Details for the construction of the roof diaphragm, including the connections to the shear walls <br /> below, should be included in the structural drawings. See IBC Sections 1603.1 and 1604.4. <br /> 22. Continuing with the previous comment, calculations for the design of the roof diaphragm shall <br /> be submitted for review. See IBC Sections 1604.1, 1604.4, and 2306.1, and AWC SDPWS-15 <br /> Sections 4.1.1 and 4.2.1. <br /> 23.The proposed design includes a new deck projecting 15.5 feet from the south face of the <br /> building. The deck exceeds the maximum allowable projection for a horizontal cantilever per <br /> AWS SDPWS-15 Section 4.2.5.2 The deck should be provided with a second line of lateral <br /> resistance along the north side. The structural drawings should be revised to specify additional <br /> lateral elements. Sections and details should be provided to specify the required construction. <br /> Additional foundations may be required. Structural calculations substantiating the design shall <br /> be submitted for review. See IBC Sections 1603.1, 1604.1, 1604.4, and 2306.1. <br /> 24.The deck is laterally-supported in the north south direction by fastening it to the main building <br /> per Detail F/S1. Note that Detail F/S1 provides two different connections; see additional <br /> comments above. Calculations substantiating the lateral load path shall be submitted for <br /> review. At a minimum, the connection capacity should satisfy the requirements of ASCE 7-10 <br /> Section 12.1.3. Where the connection is subject to multi-axial loading (i.e., gravity loading and <br /> seismic loading in one or both orthogonal directions), the connection should be evaluated for <br /> concurrent loading per AWC NDS-15 Section 12.4. See IBC Sections 1604.1, 1604.4, and <br /> 2306.1. <br /> Miscellaneous: <br /> 25. Architectural Sheet 3-of-3 includes details for the guards around the deck. The following <br /> comments shall be addressed: <br /> a. The design of the guards, the supporting framing, and the connections to the supporting <br /> framing, should be designed to comply with IBC Section 1607.8.1. <br /> b. The details specify a design load and holdowns"per manufacturer". The make and model <br /> of the required holdowns should be specified in the drawings. <br /> c. The details specify a couple distance between the 1/2"through-bolts of 2"to 5". The <br /> minimum dimensions should be specified. Note that 2"does not appear adequate to <br /> provide the required resistance at the connection. <br /> a 3200 Cedar Street 0 425.257.8810 O everetteps@everettwa.gov <br /> Everett,WA 98201 425.257.8857 fax everettwa.gov/per ,... <br /> Page 6of7 <br />