CAUTION- IF THIS" " IT IS A REDUCED PRINT <br />1. SEE ELECTRICAL ENGINEERING DRAWINGS FOR SPECIFICATIONS OF LIGHT FIXTURES, <br />SWITCHES, EXIT SIGNS, ETC. <br />2. CONTRACTOR TO VERIFY COMPATIBILITY OF LIGHT FIXTURES WITH THE CEILING <br />SYSTEM. <br />3. ALL REPLACEMENT FLUORESCENT LAMPS TO MATCH BUILDING STANDARD OR <br />ADJACENT EXISTING CONSTRUCTION -- SAME COLOR AND MANUFACTURER. <br />4. FIELD VERIFY EXISTING CEILING GRID LOCATION AND NOTIFY ARCHITECT OF ANY <br />DISCREPANCIES ON PLANS, <br />5. CONTRACTOR TO PROVIDE APPROPRIATE SIZED CUTOUTS ABOVE CEILINGS WHERE <br />NON -RATED PARTITIONS EXTEND TO SLAB ABOVE AS NECESSARY FOR RETURN <br />AIR CIRCULATION. <br />6. WHERE DISCREPANCIES IN LOCATION OF LIGHT FIXTURES, AIR DIFFUSERS, GRILLES, <br />ETC. OCCUR ON THE ELECTRICAL PLANS, THE ARCHITECTURAL PLANS SHALL <br />GOVERN. NOTIFY ARCHITECT OF ANY DISCREPANCIES FOR CLARIFICATIONS. <br />7. FIELD VERIFY ALL CLEARANCES OF DUCTS, PIPES, SPRINKLERS, ETC. AND NOTIFY <br />ARCHITECT OF ANY CONFLICTS PRIOR TO INSTALLATION OF LIGHTS ETC. <br />8. PLACEMENT OF LIGHT FIXTURES IN AREAS INHERE MAIN DUCTS MAY CAUSE <br />INTERFERENCE MUST BE APPROVED BY ARCHITECT PRIOR TO INSTALLATION. <br />9. CONDUIT ABOVE CEILING MUST BE A MINIMUM OF 12" ABOVE THE CEILING GRID. <br />10, NO COMBUSTIBLE MATERIALS SHALL BE USED IN THE PLENUM SPACE, INCLUDING <br />ALUMINUM FLEX, ALUMINUM CONDUIT AND POT METAL CONNECTORS. <br />11. ALL JUNCTION BOXES AND MECHANICAL EQUIPMENT REQUIRING ACCESS FOR <br />SERVICE SHALL BE LOCATED OVER ACOUSTICAL .CEILINGS. NO ACCESS HATCHES <br />SHALL BE INSTALLED IN GYPSUM BOARD CEILINGS WITHOUT PRIOR APPROVAL BY <br />ARCHITECT. (NO EXCEPTION). <br />12. ALL SPRINKLER HEADS AT HARD -LID CEILINGS ARE TO BE FULLY RECESSED AND <br />CONCEALED. HEADS ARE TO BE CENTERED BETWEEN LIGHTS IN A UNIFORM <br />ARCHITECTURAL PATTERN, G,C TO PROVIDE A SUBMITTAL WITH SPRINKLER HEAD <br />LOCATIONS FOR ARCHITECT'S APPROVAL PRIOR TO INSTALLATION. <br />13. ALL SPRINKLER HEADS PLACED IN WHITE CEILING TILE OR WHITE GYPSUM BOARD <br />TO BE WHITE. ALL SPRINKLER HEADS IN COLORED CEILINGS ARE TO BE CUSTOM <br />COLOR TO MATCH ADJACENT CEILING. <br />14. LOCATE RECESSED DOWN LIGHTS, WALL WASHERS, SMOKE DETECTORS, EXIT SIGNS, <br />SPEAKERS, FIRE SPRINKLERS, ETC. IN CENTER OF 24%24" CEILING TILES OR IN <br />CENTER OF 24%24" PORTION OF 24%48" CEILING TILES. UNLESS OTHERWISE <br />NOTED. <br />15. PROVIDE SWITCHES AND LIGHT SENSORS FOR OPEN AREAS AND PRIVATE OFFICES. <br />ACTUAL LOCATION OF ALL SWITCHES TO BE DETERMINED BY ARCHITECT. <br />16. PROVIDE FIRE DAMPERS AT ALL SUPPLY AND RETURN AIR OUTLETS, INLETS OR <br />DUCTS PENETRATING FIRE RATED ASSEMBLIES, ENCLOSURES, WALLS, FLOORS OR <br />SURFACES, AS REQUIRED BY LOCAL CODES AND FIRE DEPARTMENT. REFER TO <br />MECHANICAL ENGINEERING DOCUMENTS FOR SPECIFIC REQUIREMENTS. <br />17. CONTRACTOR SHALL PROVIDE EMERGENCY LIGHTING, STROBE LIGHTS, <br />AUDIO-VISUAL ALARMS AND OCCUPANCY SENSORS TO MEET ALL APPLICABLE <br />CODES. <br />18. CONTRACTOR SHALL PROVIDE LAMPS WITH TYPE IC RATED HOUSING WHERE <br />FIXTURES COME IN DIRECT CONTACT WITH INSULATION, <br />19. ALL EXIT SIGN LOCATIONS SHALL BE COORDINATED WITH THE ARCHITECT. <br />20 EXIT SIGNS SHALL BE INTERNALLY OR EXTERNALLY ILLUMINATED AT ALL TIMES <br />AND SHALL BE CONNECTED TO AN EMERGENCY POWER SYSTEM (BATTERIES, UNIT <br />EQUIPMENT OR AN ON -SITE GENERATOR) THAT WILL AUTOMATICALLY ILLUMINATE <br />THE EXIT SIGNS FOR A DURATION OF NOT LESS THAN 90 MINUTES. <br />1. NO FINISH SUBSTITUTIONS MAY BE MADE UNLESS APPROVED BY ARCHITECT. <br />2. CONTRACTOR MUST NOTIFY THE ARCHITECT OF ANY (DISCREPANCY IN PLANS. <br />FINISH ITEMS CLEARLY SHOWN IN PLANS, BUT OMITTED FROM SCHEDULES OR <br />LEGENDS MUST STILL BE PROVIDED AND INSTALLED BY CONTRACTOR. <br />CONTRACTOR TO VERIFY OMITTED FINISHED WITH ARCHITECT PRIOR TO ORDERING <br />PRODUCTS, <br />3. INSTALL MATERIALS ACCORDING TO MANUFACTURER'S SUGGESTED INSTALLATION <br />AND PREPARATION/MAINTENANCE SPECIFICATIONS OR BETTER, UNLESS <br />OTHERWISE APPROVED OR NOTED. <br />4. APPLICATION OF CONTROLLED INTERIOR FINISHES SHALL BE IN CONFORMANCE <br />WITH STATE & LOCAL CODES. <br />5. DECORATIVE MATERIALS SHALL BE MAINTAINED IN FLAME-RETARDANT CONDITION. <br />6, SUBMIT THE FOLLOWING SAMPLES FOR ARCHITECT'S APPROVAL: <br />a. THREE (3) 12" X 12" SAMPLES FOR ALL PAINT, WALL COVERING FINISHES <br />AND COLORS APPLIED TO A SUBSTRATE WHICH IS REPRESENTATIVE OF THE <br />SURFACE TO BE FINISHED. SUBMIT PAINT SAMPLES FROM THE PAINT LOT <br />OR LOTS INTENDED FOR APPLICATION. <br />b. ONE (1) 24" X 24" MOCK-UP WITH SAMPLE SEAM (CENTERED) OF ALL <br />WALL COVERING FINISHES AND COLOR, <br />C. THREE (3) 12" X 12" SAMPLES OF ALL FLOOR COVERING. <br />d. SUBMIT ACTUAL CUTTINGS OF EACH PRODUCT FOR COLOR/QUALITY <br />CONTROL. <br />7. WHERE MATERIALS ARE NOT RETURNABLE, SUBMIT SAMPLES TO ARCHITECT AND <br />SECURE APPROVAL BEFORE PLACING FULL ORDERS. <br />8. SUBMIT SEAMING PLAN FOR CARPET TO ARCHITECT FOR APPROVAL PRIOR TO <br />CARPET ORDER. <br />9. NOTIFY ARCHITECT IMMEDIATELY OF ITEMS WITH LONG LEAD TIMES. <br />10. ALL PAINT FINISH OF METAL PARTS OF DOORS, HANDRAILS, PERIMETER <br />ENCLOSURES, ETC. , SHALL BE SEMI -GLOSS, UNLESS NOTED OTHERWISE. <br />11. WHERE PAINT COLORS CHANGE, CORNERS ARE TO BE CUT -IN FREE OF <br />OVERLAPPING. <br />12. PRIOR TO THE INSTALLATION OF WALL COVERINGS, SURFACES SHALL BE <br />PROPERLY PREPARED WITH SEALER PER MANUFACTURER'S RECOMMENDATIONS. <br />13. CONTRACTOR TO VERIFY CONDITION AND LEVEL OF FLOOR SO AS TO RECEIVE <br />NEW FINISHES WITHOUT BOWING AT FLOOR OR WALL BASE, CONTRACTOR IS <br />RESPONSIBLE FOR ALL FLOOR PREPARATION. <br />14, ALL CARPETING SHALL BE INSTALLED WITH GLUE DOWN METHOD, UNLESS NOTED <br />OTHERWISE. <br />15, ALL RESILIENT FLOORING TO BE INSTALLED WITH FULL TILE FROM THRESHOLD <br />STRIP AND FULL TILE FROM WALL ADJACENT TO DOOR SWING, U.N.O. <br />16, PROVIDE AND INSTALL SPECIFIED BASE FOR ALL AREAS TO RECEIVE FLOORING. <br />17. CONTRACTOR SHALL PROVIDE PRE -FORMED RUBBER BASE CORNERS. DO NOT <br />CUT OR BEND STRAIGHT BASE TO MAKE CORNERS. <br />18. MILLWORK LOWER CABINETS ARE NOT TO RECEIVE WALL BASE UNLESS INDICATED <br />ON MILLWORK DETAILS. <br />19. FLOOR FINISHES TO CONTINUE UNDERNEATH "OPEN FLOOR" AREAS OF MILLWORK, <br />INCLUDING SINK AREA AND AT ALL UNDER --COUNTER EQUIPMENT AREAS WHICH <br />ARE OPEN TO THE FLOOR. <br />20. FLOORS SHALL BE SLOPED TO FLOOR DRAINS. COORDINATE WITH PLUMBING AND <br />STRUCTURAL DRAWINGS. IN RATED FLOOR CONDITIONS, CONFIRM REMAINING <br />FLOOR THICKNESS STILL CONFORMS TO MINIMUM RATING REQUIREMENT. <br />21, CONTRACTOR TO RUN CALCIUM CHLORIDE TEST ON ALL EXISTING OR NEW <br />CONCRETE SLABS PRIOR TO INSTALLING ANY FLOORING AND COMPARE RESULTS <br />WITH FLOORING MANUFACTURE'S RECOMMENDED MAXIMUM CONTENT FOR <br />WARRANTIES AND ADHESIVE PRODUCTS. <br />22. PRIOR TO NEW FLOORING INSTALLATION REMOVE EXISTING FLOOR FINISHES. <br />PATCH AND REPAIR SUB --FLOOR AS REQUIRED. PREPARE FLOORS AND <br />TRANSITIONS AS REQUIRED FOR SMOOTH AND LEVEL FINISH PER APPLICABLE <br />BUILDING CODES. <br />23. ALL FLOORING TRANSITIONS AMONG DIFFERING FLOORING MATERIAL ARE TO BE A <br />FLUSH TRANSITION!, U.O.N. <br />24. FEATHER SUB -FLOOR UP FOR TILE FLOORING TO CARPET CONDITIONS AND <br />RESILIENT FLOORING TO CARPET CONDITIONS FOR FLUSH INSTALLATION(. <br />25, NSTALL METAL TRANSITION STRIPS WHERE TILE MEETS ALL OTHER FLOORING <br />TYPES. PROVIDE LOW PROFILE TRANSITION STRIP WHERE ALL OTHER DIFFERENT <br />FLOOR TYPES MEET, VERIFY COLOR WITH ARCHITECT. <br />26, FLOOR COVERING INSTALLER TO FOLLOW MANUFACTURER'S SPECIFIED CARPET <br />INSTALLATION INSTRUCTIONS. USING ADHESIVES AND INSTALLATION METHOD TO <br />MAINTAIN PRODUCT'S WARRANTY. CONTACT CARPET SALES REPRESENTATIVE <br />WITH QUESTIONS PRIOR TO PROCEEDING <br />27. FLOOR COVERING INSTALLER TO FOLLOW MANUFACTURER'S SPECIFIED CONTOURED <br />RUBBER BASE INSTALLATION INSTRUCTIONS USING ADHESIVES AND INSTALLATION <br />METHODS REQUIRED TO MAINTAIN PRODUCT'S WARRANTY. <br />28. FLOOR COVERING INSTALLER REQUIRED TO PROVIDE MINIMAL SEAMS/JOINTS AT <br />ALL LOCATIONS FOR FLOOR AND WALL BASE MATERIAL INSTALLATION. PROVIDE <br />LOW VOC, BUT HEAVY DUTY ADHESIVES TO ENDURE HEAVY FOOT TRAFFIC, <br />CARTS AND TO MAINTAIN PRODUCT'S WARRANTY <br />29. PRIOR TO PAINTING, WALLS MUST BE PATCHED AND REPAIRED, CLEAN AND DRY <br />AS 1-0 LEAVE NO EVIDENCE OF PATCHING OR REPAIRS. ALL SCREW AND NAIL <br />HEADS MUST BE SET AND SPACKLED. ALL JOINTS MUST BE TAPED AND <br />COVERED WITH JOINT COMPOUND. JOINTS THAT ARE FILLED TO BE SANDED <br />SMOOTH AND DUST REMOVED PRIOR TO RECEIVING NEW PAINT FINISH <br />APPLICATION. <br />30. PRIOR TO PAINTING OVER WALL COVERING, SECURELY GLUE DOWN ANY LIFTING <br />OR BUCKLING AND HIDE ALL SEAMING OR BUMPS. <br />31. WALLS TO HAVE AT LEAST ONE COAT OF COLORED PRIMER AND TWO COATS OF <br />SPECIFIED PAINT FINISH TYPE. PAINT TO BE A LOW VOC UNLESS U.O.N. HIGH <br />TRAFFIC/WEAR ABILITY WITH GOOD SCRUB AND CLEANING ABILITY. VERIFY ALL <br />WITH TENANT OR OWNER PRIOR TO PURCHASING PAINT. <br />32. PAINT ANY UNFINISHED SPEAKER COVERS AND HVAC GRILLS IN GYPSUM BOARD <br />WALLS AND CEILINGS TO MATCH ADJACENT PAINT COLOR AS SPECIFIED. <br />33. ALL EXPOSED MECHANICAL, ELECTRICAL, PLUMBING AND FIRE PROTECTION <br />DUCTWORK AND PIPING IS TO BE PAINTED TO MATCH THE CEILING. <br />34. ALL NEWLY INSTALLED, PATCHED WORK AND ALL AFFECTED AREAS SHALL BE <br />PAINTED, ALL PAINTING WORK SHALL BE PERFORMED TO COVER THE ENTIRE <br />HORIZONTAL OR VERTICAL SURFACE TO THE CLOSEST CORNER IN ALL FOUR <br />DIRECTIONS. <br />35. PRIOR TO INSTALLING WALL TILES AND WALL BASE TILE, WALLS MUST BE <br />PATCHED AND REPAIRED, CLEAN AND DRY AND BE PROPERLY MEMBERED AND <br />ALIGNED, SO, AS TO LEAVE NO EVIDENCE OF PATCHING OR REPAIRS, ALL <br />SCREW AND NAIL HEADS MUST BE SET AND SPACKLED. ALL JOINTS MUST BE <br />TAPED AND COVERED WITH JOINT COMPOUND. JOINTS THAT ARE FILLED ARE TO <br />BE SANDED SMOOTH AND BUMP FREE WITH DUST REMOVED PRIOR TO RECEIVING <br />MORTAR BED/BOND COAT AND WALL TILES. <br />36. ALL WALL TILES ARE TO HAVE A MORTAR BED/BOND COAT THICKNESS TO <br />ACCOMMODATE THE VARYING THICKNESSES OF ALL MATERIAL TYPES OF TILE <br />SPECIFIED FOR WALL INSTALLATION WITH A FLUSH FRONT FACE. <br />37. ALL TRANSLUCENT GLASS TILE SPECIFIED ARE TO RECEIVE UNIFORM COVERAGE <br />BY BACK BUTTERING TILES AND TROWEL RIDGES FLATTENED PRIOR TO SETTING. <br />38. FLOORS OF TOILETS, BATHING AND SHOWER ROOMS SHALL HAVE A SMOOTH, <br />HARD, NONABSORBENT SURFACE. THE INTERSECTION OF SUCH FLOORS WITH <br />WALLS SHALL HAVE A SMOOTH, HARD, NONABSORBENT VERTICAL BASE AS <br />SPECIFIED IN FINISH PLANS OR RESTROOM ELEVATIONS. BASE SHALL EXTEND <br />UPWARD ONTO THE WALLS NOT LESS THAN 4 INCHES. <br />39. WALLS AND PARTITIONS WITHIN 2 FEET OF SERVICE SINKS, URINALS AND WATER <br />CLOSETS SHALL HAVE A SMOOTH, HARD, NONABSORBENT SURFACE TO A HEIGHT <br />OF NOT LESS THAN 4 FEET ABOVE THE FLOOR. <br />1. DRAWINGS OF EXISTING CONDITIONS HAVE BEEN COMPILED FROM EXISTING DATA <br />SUPPLIED BY THE OWNER TO THE ARCHITECT, THE ARCHITECT MAKES NO <br />WARRANTY, EITHER EXPRESS OR IMPLIED, FOR THE ACCURACY OF THE <br />COMPLETENESS OF THE EXISTING INFORMATION RECORDED. THE CONTRACTOR <br />SHALL FIELD VERIFY ,ALL EXISTING CONDITIONS AND NOTIFY THE ARCHITECT <br />IMMEDIATELY OF ANY DISCREPANCIES OR CONFLICTS THAT MIGHT ARISE IN THE <br />COURSE OF THE DEMOLITION WORK, <br />2. VERIFY LOCATIONS OF EXISTING MECHANICAL, PLUMBING AND ELECTRICAL <br />UTILITIES. LOCATE AND PROTECT UTILITIES TO REMAIN. DISCONNECT, REMOVE <br />BACK TO NEAREST JUNCTION BOX OR PANEL, AS REQUIRED, AND CAP <br />DESIGNATED UTILITIES WITH( T DEMOLITION <br />N THE DEM L TION AREA. REFER TO THE <br />MECHANICAL, PLUMBING AND ELECTRICAL DRAWINGS FOR ADDITIONAL INFO, <br />3. EXISTING ELECTRICAL AND TELEPHONE OUTLETS LOCATED ON DEMOLISHED WALLS <br />ARE TO BE REMOVED INCLUDING CONDUIT AND WRING BACK TO JUNCTION BOX. <br />LOCATIONS ARE TO BE PATCHED AND REPAIRED TO BE FLUSH WITH ADJACENT <br />WALL SURFACE, <br />4. WHERE PLUMBING FIXTURES ARE BEING REMOVED OR WHERE EXPOSED PLUMBING <br />PIPES OCCUR, CAP LINES BEHIND FINISHED SURFACES. PATCH AND REPAIR AS <br />REQUIRED. <br />5. ALL EXISTING CONSTRUCTION WHERE INDICATED INCLUDING ELECTRICAL, <br />TELEPHONE, PLUMBING AND MECHANICAL DEVICES NOT OTHERWISE INDICATED ON <br />THESE CONSTRUCTION DRAWINGS SHALL BE REMOVED IN A CAREFUL MANNER SO <br />AS NOT TO DAMAGE ADJOINING CONSTRUCTION. <br />6, IT SHALL BE THE RESPONSIBILITY OF THE CONTRACTOR TO LOCATE ALL EXISTING <br />UTILITIES WHETHER SHOWN HEREON OR NOT AND TO PROTECT THEM FROM <br />DAMAGE. THE CONTRACTOR SHALL BEAR ALL EXPENSE OF REPAIR OR <br />REPLACEMENT OF UTILITIES OR OTHER PROPERTY DAMAGED BY OPERATIONS IN <br />CONJUNCTION WITH THE EXECUTION OF HIS WORK. <br />7. ALL EXISTING BUILDING UTILITIES SHALL REMAIN IN OPERATION DURING <br />CONSTRUCTION. PROVIDE REROUTING OF UTILITIES SERVING ADJACENT AREAS <br />THAT ARE TO MAINTAIN UNINTERRUPTED SERVICE, ANY TEMPORARY SUSPENSION <br />OF SERVICE SHALL BE COORDINATED AND APPROVED BY THE FACILITY MANAGER, <br />NOT LESS THAN 24-HOURS IN ADVANCE. <br />8. THE CONTRACTOR WILL VERIFY AND CONFORM TO ALL REQUIREMENTS OF ALL <br />UTILITY COMPANIES UNLESS OTHERWISE NOTED IN THE PLANS AND <br />SPECIFICATIONS. <br />9, THE DEMOLITION PLAN KEYNOTES ARE DIAGRAMMATIC AND GENERAL IN NATURE. <br />THE INTENT IS TO ILLUSTRATE THE COMPLETE DEMOLITION OF THE SPACES <br />INDICATED UNLESS NOTED OTHERWISE. FIELD VERIFICATION OF EXISTING <br />CONDITIONS AND SPECIFIC QUANTITIES IS THE RESPONSIBILITY OF THE <br />CONTRACTOR. <br />10. REMOVAL AND DISPOSAL OF DEMOLITION DEBRIS IS THE RESPONSIBILITY OF THE <br />CONTRACTOR. VERIFY THE HAULING ROUTE THROUGH THE BUILDING, THE <br />DEMOLITION STAGING AREA, AND THE LOCATION OF THE DUMPSTERS WITH THE <br />OWNER PRIOR TO THE START OF DEMOLITION. DISPOSAL OF RUBBISH SHALL BE <br />DONE IN A LEGAL MANNER. <br />11. THE OWNER RESERVES THE RIGHT TO SALVAGE ANY DEMOLISHED ITEM. VERIFY <br />ITEMS TO BE SALVAGED WITH THE OWNER PRIOR TO THE START OF DEMOLITION. <br />REMOVE, PROTECT, CLEAN, REPAIR FOR REUSE AND TURN OVER SUCH ITEMS AS <br />DIRECTED BY THE OWNER. <br />12. IN ORDER TO INSTALL SOME OF THE NEW WORK (INCLUDING, BUT NOT LIMITED <br />TO MECHANICAL, PLUMBING OR ELECTRICAL) IT WILL BE NECESSARY FOR THE <br />CONTRACTOR AND HIS SUBCONTRACTORS TO REMOVE AND REPLACE (OR <br />REFINISH) EXISTING WALLS, FLOORS, OR CEILING IN THE AREAS OF THE BUILDING <br />NOT SHOWN ON THESE PLANS. THE CONTRACTOR SHALL INCLUDE ALL RELATED <br />COSTS IN HIS BASE BID, WHETHER SHOWN ON THESE PLANS OR NOT. <br />13, PROTECT ADJACENT SPACES NOT SCHEDULED FOR DEMOLITION. PATCH AND <br />REPAIR DAMAGED FINISHES, ITEMS AND FIXTURES TO REMAIN AND/OR REPLACE <br />IN KIND TO MATCH EXISTING FROM DAMAGE DURING THE PROGRESS OF THE <br />WORK, PROVIDE TEMPORARY SAFETY BARRIERS REQUIRED BY CODE AND AS <br />INDICATED TO INSURE PUBLIC SAFETY AND TO ALLOW BUILDING OCCUPANCY. <br />CONTRACTOR TO SUBMIT FOR APPROVAL, BARRIER LOCATIONS, AND METHOD OF <br />CONSTRUCTION TO THE ARCHITECT PRIOR TO INSTALLATION. <br />14. NO STRUCTURAL ELEMENTS ARE INCLUDED IN THIS SCOPE OF WORK. <br />15. PROVIDE DUST BARRIERS AROUND OPENINGS, TO AND FROM THE CONSTRUCTION( <br />AREA. PROVIDE ALL MEANS NECESSARY TO INHIBIT DUST FROM ENTERING <br />OTHER PORTIONS OF THE FACILITY. SUBMIT BARRIER LOCATIONS TO THE <br />ARCHITECT FOR APPROVAL, PRIOR TO INSTALLATION(. <br />16. PROVIDE ADEQUATE SHORING, BRACING, BARRICADES AND PROTECTIVE MEASURES <br />AS REQUIRED TO SAFELY EXECUTE THE WORK IN THE CONSTRUCTION AREA AND <br />THE AREAS ADJACENT TO THE CONSTRUCTION AREA. CEASE OPERATIONS AND <br />NOTIFY THE ARCHITECT IMMEDIATELY IF THE STRUCTURE APPEARS TO BE <br />ENDANGERED, DO NOT RESUME OPERATIONS UNTIL CORRECTIVE MEASURES HAVE <br />BEEN TAKEN. <br />17, CONTRACTOR SHALL MAINTAIN REQUIRED MEANS OF EGRESS AND ENSURE THAT <br />EXIT ROUTES ARE SIGNED, LIGHTED AND PROTECTED IN ACCORDANCE WITH CODE <br />REQUIREMENTS. RELOCATE EXISTING AND/OR PROVIDE SMOKE PROTECTORS AND <br />LIFE SAFETY EQUIPMENT FOR ADEQUATE COVERAGE, <br />18. PROVIDE TEMPORARY NON-COMBUSTIBLE CONSTRUCTION BARRIERS WHERE <br />REQUIRED BY CODE AND THE GOVERNING FIRE AUTHORITY. MINIMUM <br />REQUIREMENTS: <br />A. FULL HEIGHT WALL FROM FLOOR TO CEILING. <br />B. STUDS AT 24" O.C., WITH 5/8" TYPE 'X' GYPSUM BOARD. <br />C. NON-COMBUSTIBLE ACCESS DOOR WITH (3) HINGES AND SPRING CLOSER. <br />19. SURVEY EXISTING FLOORS AND CLEARLY MARK ON FLOOR SURFACE THE <br />LOCATIONS OF ALL BEAMS AND JOISTS. MARK ALL CORE DRILL PENETRATIONS <br />AND RECEIVE STRUCTURAL ENGINEER'S APPROVAL PRIOR TO DRILLING CONCRETE. <br />20. CUT RIGID MATERIALS USING MASONRY SAW OR CORE DRILL. PNEUMATIC TOOLS <br />ARE NOT ALLOWED WITHOUT PRIOR APPROVAL. <br />21. ALL CORE DRILLING OR OTHER NOISY WORK SHALL BE SCHEDULED 48-HOURS IN <br />ADVANCE WITH THE OWNER. <br />22. APPLY CEMENT BASE FLOOR PATCH AS REQUIRED TO FILL DINGS, NAIL HOLES, <br />CHIPS AND CRACKS. <br />23, AT FLOOR AREAS SCHEDULED TO RECEIVE NEW FLOOR COVERING, REMOVE <br />EXISTING FLOOR COVERING AND PREPARE SUBSTRATE FOR NEW FLOOR COWERING <br />PER SPECIFICATIONS AND MANUFACTURER'S REQUIREMENTS. <br />24. AT ABANDONED PENETRATIONS OF FIRE RATED WALLS, CEILING OR FLOOR <br />CONSTRUCTION, COMPLETELY SEAL VOIDS WITH FIRE RATED MATERIAL TO FULL <br />THICKNESS OF THE PENETRATED ELEMENT. ALL PATCHING OF EXISTING WORK TO <br />REMAIN SHALL MATCH FINISH PER SCHEDULE OR WHERE UNSCHEDULED TO <br />MATCH EXISTING FINISHES TO REMAIN, AND SHALL MEET OR EXCEED FIRE RATING <br />INDICATED ON FLOOR PLAN AND AS REQUIRED BY THE FIRE/LIFE SAFETY <br />INSPECTOR. <br />25. COORDINATE EXISTING SPRINKLER LINE AND HEAD LOCATION WITH NEW PLAN. <br />SUBMIT SPRINKLER SHOP DRAWINGS TO ARCHITECT FOR REVIEW WITH THE CITY <br />FIRE DEPARTMENT. <br />26. CONTRACTOR IS RESPONSIBLE FOR BUILDING SECURITY DURING DEMOLITION <br />PHASE. PROTECT ALL OPENINGS FROM WEATHER CONDITIONS AND SECURE THEM <br />TO PREVENT VANDALISM. <br />27, DO NOT PERFORM ANY WORK THAT WILL VOID WARRANTIES OF EXISTING <br />WEATHER EXPOSED OR MOISTURE RESISTANT ELEMENTS WITHOUT PRIOR <br />APPROVAL FROM THE OWNER. <br />28. ARCHITECT ASSUMES NO RESPONSIBILITY RELATING TO ANY TOXIC MATERIALS, <br />INCLUDING ASBESTOS, AND ASSUMES NO RESPONSIBILITY TO ITS EXISTENCE OR <br />REMOVAL, THE OWNER WILL TAKE ACTION FOR DIRECTLY CONTRACTING WITH A <br />CONSULTANT OR SPECIALIST, LICENSED BY THE STATE, FOR SUCH SERVICES <br />SHOULD THOSE SERVICES BE REQUIRED ON THE PROJECT. <br />29. IF THE EXISTING BUILDING CONSTRUCTION IS CLASSIFIED SUCH THAT <br />FIREPROOFING INSULATION IS PRESENT, THEN THE CONTRACTOR, PRIOR TO <br />STARTING ANY WORK, SHALL VERIFY THE CURRENT FIRE -RESISTANCE RATING(S) <br />OF THE EXISTING BUILDING ELEMENT(S). IF THE EXISTING FIREPROOFING <br />INSULATION IS DAMAGED/AFFECTED DURING THE COURSE OF THE WORK, AS <br />DEFINED BY THIS PROJECT SCOPE, THEN THE CONTRACTOR SHALL PATCH/REPAIR <br />THE FIREPROOFING INSULATION TO A CONDITION THAT SHALL MATCH OR EXCEED <br />THE ORIGINAL FIRE -RESISTANCE RATINGS) OF THE EXISTING BUILDING <br />ELEMENT(S). <br />30. CONTRACTOR TO RELOCATE AND REUSE EXISTING DOORS AND HARDWARE WHERE <br />POSSIBLE. <br />31. EXISTING DOORS TO REMAIN U.O.N. <br />32. ALTERNATE CONSTRUCTION WASTE DISPOSAL -RECYCLING OF ACOUSTICAL TILES <br />A. CEILING MATERIAL BEING RECLAIMED MUST BE KEPT DRY AND FREE FROM DEBRIS. <br />B. BEFORE DISPOSING OF CEILINGS, CONTACT THE ARMSTRONG RECYCLING CENTER <br />AT 877-276-7876, SELECT OPTION #4 TO TALK TO A CONSULTANT, THEY WILL <br />VERIFY THE CONDITION OF THE MATERIAL AND THAT IT MELTS THE ARMSTRONG <br />REQUIREMENTS FOR RECYCLING. CONSULTANT WILL PROVIDE ASSISTANCE TO <br />FACILITATE THE RECYCLING OF CEILING MATERIAL, <br />1. CONTRACTOR MUST NOTIFY BUILDING OWNER/MANAGER OF ANY DISCREPANCY IN <br />PLANS. FINISH ITEMS CLEARLY SHOWN IN PLANS, BUT OMITTED FROM SCHEDULES <br />OR LEGENDS MUST STILL BE PROVIDED AND INSTALLED BY CONTRACTOR. <br />CONTRACTOR TO VERIFY OMITTED FINISHES WITH BUILDING OWNER/MANAGER <br />PRIOR TO ORDERING PRODUCTS, <br />2. SHOP DRAWINGS MUST BE PROVIDED FOR APPROVAL PRIOR TO FABRICATION ANY <br />SUBSTITUTIONS MUST BE APPROVED BY THE ARCHITECT PRIOR TO FABRICATION. <br />3. MILLWORKER TO COORDINATE & VERIFY WITH CONTRACTOR FINAL LOCATION FOR <br />CANTILEVERED COUNTERS FOR IN -WALL SUPPORT BRACKETS, PRIOR TO GYPSUM <br />BOARD FINISHING OF WALLS. ALL FINAL INSTALLATION HEIGHTS FOR IN -WALL <br />SUPPORT BRACKETS MUST MEET ALL APPLICABLE ACCESSIBILITY CODES AND <br />STANDARDS WITH COUNTERTOP MATERIAL THICKNESS INCLUDED. <br />4. MATERIAL COLORS NOT LISTED SHALL BE REQUESTED FROM THE ARCHITECT ON <br />SHOP DRAWING SUBMITTALS OR VIA RFIs, <br />5. ALL UPPERS TO BE LAMINATED TO MATCH BASE CABINETS. BOTH UPPERS <br />LOWER CABINETS IN WET AREAS TO HAVE MATCHING PVC EDGE, ALL OTHERS TO <br />HAVE PLASTIC LAMINATE EDGE BANDING U.O.N. <br />6. ALL CABINETS AND DOORS SHALL BE CONSTRUCTED FROM 3/4" THICK MATERIAL, <br />U.O.N. ON DETAILS. <br />7. BASE CABINETS ARE NOT TO RECEIVE WALL BASE UNLESS INDICATED ON FINISH <br />PLANS OR ELEVATIONS, <br />8. ALL INTERIORS OF CLOSED CABINETS TO BE WHITE MELAMINE/POLYESTER OR <br />APPROVED EQUAL, UNLESS OTHERWISE SPECIFIED. <br />9, ALL OPEN CABINETS OR SHELVES TO HAVE PLASTIC LAMINATE TO MATCH <br />EXTERIORS. <br />10. NO 3/4" THICK SHELF SHALL SPAN LONGER THAN 32" WITHOUT SUPPORT. <br />11. ALL SHELVING TO BE ADJUSTABLE UNLESS OTHERWISE SPECIFIED, <br />12. ALL FILE PEDESTALS ARE TO BE CONFIGURED FOR "FRONT TO BACK" FILING AND <br />BE ABLE TO ACCEPT METAL HANGERS TO ACCEPT PENDAFLEX TYPE FILE <br />FOLDERS, UNLESS NOTED AS LATERAL. <br />13, ALL COUNTER TOPS TO BE 24" DEEP, UNLESS OTHERWISE SPECIFIED. WHERE NO <br />BACKSPLASH IS SPECIFIED, COUNTER TOPS TO BE SCRIBED TIGHTLY TO BACK & <br />SIDE WALLS. <br />14. ALL BACKSPLASHES TO BE SCRIBED TO WALLS, AND MUST BE FLUSH TO EDGE <br />OF BASE, UNLESS OTHERWISE SPECIFIED. ALL COUNTER TRANSITION SEAMS MUST <br />BE CAULKED SEALED, VERIFY EITHER MATCHING COLOR CAULK OR CLEAR <br />SILICONE. <br />15. PROVIDE SIDE SPLASHES AT LOCATIONS ADJACENT TO WALLS OR WINDOWS, <br />ESPECIALLY FOR SINKS U.O.N. <br />16. FACES OF PIGEONHOLES TO MATCH WORK SURFACE LAMINATE. COLOR OF EDGE <br />BANDING ON ALL DOORS TO MATCH FACE MATERIAL. <br />17. IF PROVIDED, SEE SPECIFICATIONS/PROJECT MANUAL FOR ADDITIONAL <br />REQUIREMENTS. <br />18, COUNTERTOPS SHALL HAVE A NOSING OF COUNTERTOP MATERIAL AT LEAST 3" <br />DEEP, WHEREBY THE COUNTER MATERIAL EXTENDS INTO THE INSIDE OF THE <br />CABINET, I.E. OVER THE DOOR (WHEN PRESENT). <br />19. END PANELS AND FRONT EDGES OF EDGE PANELS WHICH ARE PROUD OF THE <br />INTERIOR CABINET SHALL BE FACED TO MATCH DOOR FRONTS. <br />20. ALL HINGED DOORS TO HAVE CLEAR SILENCERS TOP AND BOTTOM ON DOOR (NOT <br />CABINET). <br />21. ALL DRAWERS GLIDES SHALL HAVE SILENCERS BUILT INTO THE GLIDE AND NOT <br />INSTALLED ON THE DRAWER OR DRAWER FRONT. <br />22. ALL DRAWER GLIDES SHALL BE FULL EXTENSION(. <br />23. PROVIDE FULL OVERLAY HINGES THAT OPEN ±105 EXCEPT WHERE CABINETS ARE <br />ADJACENT TO THE WALLS. PROVIDE HINGES WHICH LIMIT THE DOOR SWING TO <br />KEEP THE DOOR PULL FROM DAMAGING THE WALL. <br />y <br />z <br />4 <br />U- <br />0 <br />I`- <br />z <br />ui <br />2 <br />ui <br />U <br />z <br />Ld <br />0 <br />U <br />0 <br />0 <br />x <br />a <br />ro <br />m <br />0 <br />0 <br />x <br />0 <br />U <br />0 <br />z <br />LJ <br />F <br />0 <br />F- <br />x <br />0 <br />a <br />0 <br />x <br />m <br />m <br />�c <br />v <br />z <br />Ld <br />Ld <br />0 <br />a <br />r <br />z <br />a <br />t <br />a <br />0 <br />Ld <br />z <br />z <br />0 <br />a <br />Ld <br />u_ <br />cr <br />ui <br />Ld <br />ca <br />a <br />z <br />z <br />A <br />z <br />0 <br />Ld <br />M <br />a <br />0 <br />W <br />cn <br />x <br />0 <br />U <br />z <br />w <br />U <br />a <br />H <br />x <br />z <br />0 <br />U) <br />z <br />W <br />0 <br />v <br />ry <br />�c <br />F- <br />z <br />w <br />a <br />w <br />w <br />0 <br />r <br />F_ <br />c <br />ui <br />0 <br />w <br />W <br />y <br />EY <br />w <br />x <br />0 <br />a- <br />z <br />a <br />V <br />Ld <br />as <br />�n <br />0 <br />z <br />a <br />z <br />4 <br />Lm <br />m <br />0 <br />0 <br />bi <br />0 <br />C2 <br />0- <br />0 <br />U <br />a <br />z <br />Lu <br />W <br />0 <br />CL <br />W <br />z <br />0 <br />d <br />0 <br />Ld <br />a <br />a <br />z <br />0 <br />�c <br />a <br />W <br />cn <br />i <br />F- <br />ce <br />E <br />0 <br />c�9 <br />o <br />v b,0 <br />"o <br />so, <br />41 <br />N NO <br />a; <br />> <br />o <br />•� <br />a <br />. <br />bad 'v <br />o a� <br />n <br />�� w <br />to <br /><� <br />w <br />of <br />I <br />0 <br />ILL-m <br />N <br />0 <br />LAJ N <br />0 <br />PA / <br />PM: L. LUCERO <br />DRAWN BY: D.S. <br />JOB NO.: SEA21-6033-00 <br />SHEET <br />