MECHANICAL PLAN <br />SCALE: 3116" =1'-®„ NORTH <br />ROOFTOP UNNT SCHEDULE <br />COOLING SECTIONS <br />NOM <br />FAN SECTION <br />HEATING SECTION (NATURAL GAS) <br />(DX) <br />ELECTRICAL <br />TAG <br />FG <br />MODEL <br />TOMS <br />L6S. <br />COMMENTS <br />OUTSIDE AIR <br />AIR <br />(MIN) <br />INPUT <br />OUTPUT <br />AFUE <br />TOTAL <br />EER <br />VOLTS <br />PIS <br />MCA <br />MOP <br />RTU-1 <br />CARRIER <br />48HCDE09 <br />8.5 <br />3500 CFM <br />550 CFM <br />125000.0 Btu/h <br />103000 Btu/h <br />82 <br />97000 Btu/h <br />12 <br />208 V <br />3 <br />48.0 A <br />60 A <br />1100 <br />1-7 <br />RTU-2 CARRIER 48HCDB05 4 <br />1600 CFM 200 CFM <br />72000:0 Btu/h 56000 Btulh 82 48500 Btulh 13 <br />1 208 V 3 31.0 A 40 A 1 700 1 1-6 <br />COMMENTS: <br />1. PROVIDE WITH CURB ADAPTER <br />4, PROVIDE WITH 2" FILTERS, MIN MERV 13 - (2) SETS <br />2. PROVIDE WITH ELECTRICAL DISCONNECT <br />5, PROVIDE WITH ECONOMIZER <br />3. PROVIDE WITH 120V CONVENIENCE OUTLET POWERED FROM UNIT <br />6. PROGRAMMABLE ELECTRONIC PROGRAMMABLE THERMOSTAT <br />7. PROVIDE WITH DUCT SMOKE DETECTOR <br />FLEXIBLE DUCT <br />CONNECTIONS WITH <br />TRANSITIONS (TYP) <br />CURB ADAPTER AS <br />REQUIRED <br />PROVIDE (2) LAYERS OF 2" THICK -J <br />'SOUND SEAL° MODEL "QFA-9" <br />QUILTED INSULATION WITH B10FS <br />FLEXIBLE BARRIER WITHIN CURB, - <br />STAGGER JOINTS <br />,RR 00 OFT U IT I TALL TI TAIL <br />SCALE: NTS <br />/ UNION <br />GAS SHUT OFF <br />VALVE DIRT POCKET <br />C <br />NATURAL GAS SUPPLY <br />� TO EQUIPMENT <br />i -ROOF <br />-,I u <br />ti 4* <br />R ROOF DRAIN <br />�L • <br />L AIR TERMINAL (DIFFUSER) <br />AS INDICATED ON PLAN <br />FLEX -DUCT TAP DTL. <br />SCALE; 1/4'° =1'_0" <br />S3 <br />300 CFM <br />ECHANICAL PLAN KEY NOTES <br />1. DEMO AND REMOVE EXISTING RTU AND ALL EXISTING DUCT WORK. PROVIDE AND <br />INSTALL NEW ROOF TOP UNIT PER SCHEDULE THIS SHEET. UNIT SHALL BE PROVIDED <br />WITH CURB ADAPTER AS REQUIRED TO CONNECT TO EXISTING CURB. NEW THROUGH <br />BASE ELECTRICAL CONNECTION BY ELECTRICAL CONTRACTOR. REFER TO DETAIL THIS <br />SHEET FOR ADDITIONAL INFORMATION. <br />2. LOCATION OF NEW 7-DAY PROGRAMMABLE THERMOSTAT. PROVIDE NEW CONTROL <br />WIRING TO NEW UNIT. <br />3. DIGITAL REMOTE SETPOINT FOR THERMA-FUSER VAV IN ROOM FOR HEATING & <br />COOLING. TYPICAL OF ALL LOCATIONS. REQUIRES 24V CONTROL WIRING. PROVIDE <br />TRANSFORMER AS REQUIRED. <br />4, PANASONIC FV-30 VQ3 290 CFM TRANSFER EXHAUST FAN WITS-! LINE VOLTAGE WALL <br />MOUNTED THERMOSTATIC CONTROL RANGE FROM 75-90 dF. DUCT TO PLENUM SPACE <br />IS AWAY FROM ROOM. PROVIDE ALL REQUIRED TRANSITIONS AND FITTINGS. <br />5. PANASONIC FV-30 VQ3 290 CFM CEILING EXHAUST FAN. WIRE TO TIMECLOCK. PROVIDE <br />NEW EXHAUST DUCT FROM FAN AND TIE INTO EXISTING EXHAUST DUCT PRIOR TO <br />PENETRATING THROUGH ROOF. PROVIDE ALL REQUIRED TRANSITIONS AND FITTINGS. <br />INSTALL BACKDRAFT DAMPER ON EACH EXHAUST DUCT. <br />6. EXISTING RTU TO BE ABANDONED IN PLACE, EXISTING MAIN TRUNK THROUGH ROOF TO <br />REMAIN, CAP BELOW ROOF. ALL EXISTING DUCT WORK SHALL BE COMPLETELY <br />REMOVED. <br />MECHANICAL LEGEND <br />CEILING MOUNTED SUPPLY AIR DIFFUSER <br />AN (SEE AIR TERMINAL SCHEDULE FOR MORE INFO) <br />CEILING MOUNTED RETURN AIR GRILLE <br />(SEE AIR TERMINAL SCHEDULE FOR MORE INFO) <br />o CEILING MOUNTED EXHAUST FAN <br />(SEE PLAN MOTES FOR MORE INFO) <br />++H FLEX DUCT PER PLAN <br />SQUARE DUCT PER PLAN <br />ROUND DUCT PER PLAN <br />DIRECTION OF AIRFLOW <br />O 7 DAY PROGRAMMABLE THERMOSTAT <br />\RJ REMOTE THERMA-FUSER VAV ADJUSTER <br />AIR TERMINAL SCHEDULE <br />I <br />TYPE <br />SIZE <br />NECK SIZE <br />DESCRIPTION <br />I FG. <br />M DEL <br />QTYe <br />NOTES <br />SUPPLY <br />S1 <br />24"x24" <br />6"o <br />SUPPLY <br />TITUS <br />TMS-AA <br />19 <br />1-4 <br />S2 <br />24"x24" <br />8" u <br />SUPPLY <br />TITUS <br />TMS-AA <br />6 <br />1-4 <br />S2VAV <br />24"x24" <br />8"o <br />SUPPLY <br />THERMA-FUSER <br />TF-HC-8-ADJ-R8-D3 <br />4 <br />1-7 <br />S3 <br />24"x24'° <br />10" as <br />SUPPLY <br />TITUS <br />TMS-AA <br />5 <br />14 <br />RETURN <br />R1 <br />24'°x24" <br />24'°x24" <br />RETURN <br />TITUS <br />300RS <br />9 <br />1-3 <br />AIR TERMINAL NOTES <br />1. AIR PATTERN ALL DIRECTIONS UNLESS OTHERWISE NOTED ON PLAN. <br />2. COLOR PER OWNER <br />3. PROVIDE AND INSTALL VOLUME DAMPER <br />4 REFER TO MECHANICAL FLOOR PLAN FOR CRM & NECK SIZE <br />5 PROVIDE WITH DIGITAL REMOTE SET POINT - REQUIRES 24V CONTROL LINE <br />6 PROVIDE WITH RELIEF RING TO MATCH NECK SIZE <br />7 PROVIDE POWER FEED 8r TRANSFORMER <br />I i MOUNTED L.i I i_ AN{ DTL <br />SCALE: NTS <br />VOLUME DAMPER <br />SUPPLY DUCT <br />GALVANIZED DUCTWORK <br />1 1/2" WRAP <br />INSULATION R6 MIN <br />VALUE <br />GALV. ALL THREAD ROD <br />GALV. STEEL WITH OUTSIDE <br />INSULATION MIN. R6 VALUE <br />CLASS 1 CORNING OR EQUAL <br />OUTSIDE WRAP <br />GENERAL MECHANICAL NOTES MECHANICAL SPECIFICATIONS <br />1, VERIFY ALL DIMENSIONS AT JOB SITE. INSULATION -PIPING: <br />2. ESTABLISH, WITH ARCHITECT'S APPROVAL, FINAL LOCATION OF ALL PROVIDE ALL LABOR, MATERIALS, ETC., REQUIRED TO PRODUCE A COMPLETE <br />EQUIPMENT. FINISH INSULATION SYSTEM). <br />3, DUCT SHALL BE GALV. WITH WRAP INSULATOR AS SPECIFIED 2" MIN. R-6 <br />VALUE OR AS REQUIRED BY CODE. FLAME/SMOKE RATINGS: <br />4. CEILING DIFFUSER SIZES AS SHOWN ON PLANS INDICATE NECK SIZE <br />PROVIDE COMPOSITE MECHANICAL INSULATION (INSULATION JACKETS, <br />DIFFUSERS SHALL BE EQUAL TO METAL AIRE MFG. <br />COVERINGS, SEALERS, MASTICS, AND ADHESIVES) WITH FLAME-SPREAD0&1 <br />9� <br />a �, <br />5. SEAL AIRTIGHT WHERE DUCTS PASS THRU WALLS, -FLOORS, ROOFS, OR <br />RATING OF 25OR LESS AND SMOKE DEVELOPED RATING OF 150 OR LESS AS <br />DUCTS. <br />TESTED BY ANSI/ASTM E84 (NFPA 255) METHODS. <br />6. ALL WORK SHALL BE CONFORMED TO THE CITY CODES AND ALL OTHER <br />AUTHORITIES HAVING JURISDICTION, OBTAIN PERMITS AND PAY ALL FEES, <br />TYPE: "FIBERGLASS 25" ASJ (ALL SERVICE JACKET) GLASS FIBER OR EQUAL. <br />7. VERIFY AT JOB SITE THE EXACT LOCATIONS OF EXISTING STRUCTURAL <br />GLASS FIBER SHALL BE HEAVY DENSITY RIGID GLASS FIBER MOLDED SNAP -ON <br />MEMBERS SUCH AS BEAMS, COLUMNS ETC. TO LOCATE EQUIPMENT, <br />SECTION WITH A WHITE VINYL JACKET AND VAPOR BARRIER LAMINATE OF <br />8. VERIFY AT JOB SITE ALL GENERAL WORK TO BE DONE AS SPECIFIED AS <br />ALUMINUM FOIL AND GLASS FIBER REINFORCED KRAFT PAPER. <br />NOTED OR AS REQUIRED FOR INSTALLATION OF VARIOUS AIR <br />FITTINGS: INCLUDE PUMPS, VALVES, SPECIALTIES, ETC... COVER FITTINGS WITH <br />CONDITIONING AND EQUIPMENT PRIOR TO THE SUBMISSION OF BIDS. <br />BLANKET INSULATION (SAME THICKNESS AS ADJACENT PIPE INSULATION), <br />9. ALL HVAC UNITS SHALL BE PROVIDED WITH THE SMOKE DUCT DETECTOR <br />SECURE WITH TWINE. INSTALL "ZESTON'S" ONE PIECE PRE -MOLDED COVER. <br />OWNER <br />AT EACH ZONE. <br />SECURE WITH'°ZESTON"S" TAPE. <br />VISIONWORKS <br />10. PROVIDE CLEAR PLASTIC BOXES FOR ALL THERMOSTATS. <br />HANGERS: PROVIDE CALCIUM SILICATE INSULATION AT EACH HANGER. <br />175 E HOUSTON STREET <br />11. ALL DUCTWORK SHALL BE FABRICATED IN THE UNITED STATES. <br />APPLICATION: ALL SEAMS, LAPS. AND END JOINTS WILL BE SEALED BY SELF- <br />SAN ANTONIO, TX 78205 <br />12. THE LOCATION OF DUCTWORK AND MECHANICAL EQUIPMENT AS SHOWN IS <br />SEALING LAP ON JACKET OR JOINT SEALING STRIPS INSTALLED IN <br />PROJECT <br />SCHEMATIC. THE MECHANICAL EQUIPMENT CONTRACTOR SHALL BE <br />ACCORDANCE WITH MANUFACTURERS RECOMMENDATIONS AND STAPLED. <br />VISIONWORKS #1407 - GREENTREE PLAZA <br />RESPONSIBLE FOR COORDINATING THE EXACT LOCATION OF ALL <br />WHERE STAPLES ARE USED, THEY SHALL BE FLOOD SEALED BENJAMIN FOSTER <br />305 SE EVERETT MALL WAY, SUITE 21 <br />DUCTWORK AND EQUIPMENT IN RELATION TO ALL PLUMBING, ELECTRICAL <br />30-36 OR EQUAL MASTIC. <br />EVERETT, WA 98208 <br />AND STRUCTURAL ITEMS SO AS 70 MAINTAIN PROPER CLEARANCES AND <br />THICKNESS: 2". <br />ELEVATIONS OF ALL FINISH MATERIALS AND ALL SUCH COORDINATION AND <br />MANUFACTURERS: OWNS -CORNING, CERTAINTEED, ARMSTRONG. <br />ANY MATERIALS AND SCHEDULES WHILE FULLY MAINTAINING THE DESIGN <br />INTENT OF ALL M.E.P. ITEMS. <br />DUCTWORK AND ACCESSORIES: <br />13. H.V.A.C. TO COORDINATE WITH REFLECTIVE CEILING PLAN. <br />I TYPE SYSTEM: LOW PRESSURE. ALL DUCTWORK AND FITTINGS, SELECTIONS, <br />. <br />14. MOUNT THERMOSTATS 44" FROM ABOVE FINISHED FLOOR TO THE TOP <br />APPLICATIONS AND INSTALLATION SHALL BE IN ACCORDANCE WITH SMANCA" - <br />� <br />PLATE AND 8" TO ONE SIDE OF THE LIGHT SWITCHES WHERE BOTH OCCUR <br />"HVAC DUCT CONSTRUCTION STANDARDS". CONSTRUCTION: LOW PRESSURE <br />IN THE SAME LOCATIONS, UNLESS OTHERWISE NOTED. <br />DUCTWORK SHALL BE CONSTRUCTED OF GALVANIZED STEEL SHEETS. <br />15. PROVIDE ALL HVAC WITH 1" THICK AIR FILTERS. FILTERS SHALL BE FARR <br />DUCTWORK SHALL CONFORM ACCURATELY TO THE DIMENSIONS INDICATED,MN <br />30/30 MEDIUM EFFICIENCY, PLEATED, DISPOSABLE TYPE. <br />AND SHALL BE STRAIGHT AND SMOOTH ON THE INSIDE WITH JOINTS NEATLY <br />-�;�. <br />16. COMPLY WITHNEBB'S "PROCEDURAL STANDARDS FOR TESTING- <br />FINISHED. DUCTS SHALL BE SECURE AND ANCHORED TO THE BUILDING <br />= <br />ADJUSTING -BALANCING OF ENVIRONMENTAL SYSTEMS" FOR SYSTEMS. <br />STRUCTURAL COMPONENTS AND FRAMING, AND SHALL BE FABRICATED AND <br />EQUIPMENT &APPARATUS USED IN THIS PROJECT, SUBMIT TEST REPORTS <br />SUPPORTED IN SUCH A MANNER TO PREVENT VIBRATION AND PULSATION <br />SIGNED BY THE TEST AND BALANCE SUPERVISOR WHO PERFORMED THE <br />UNDER OPERATING CONDITIONS. BUTTON PUNCH OR BOLD CONNECTIONS IN <br />WORK. <br />STANDING SEAMS SHALL BE SPACED AT NOT GREATER THAN 6-INCH ON <br />17. INSTALLATION SHALL BE IN ACCORDANCE WITH THE 2018 INTERNATIONAL <br />CENTERS. LONGITUDINAL LOCKS OR SEAMS TERMED " BUTTON PUNCH SNAP <br />SCHEID <br />MECHANICAL CODE. <br />LOCK" ARE ACCEPTABLE IN LIEU OF PITTSBURG LOCKS. ELBOWS SHALL BE <br />18. ALL MATERIALS ABOVE CEILING IN PLENUM SPACE SHALL HAVE A MINIMUM <br />RADIUS TYPE WITH A CENTER RADIUS OF 1-1/2 TIMES THE WIDTH OR DIAMETER <br />,­ <br />1.0 HOUR FIRE RATING, <br />OF THE DUCT. WHERE SPACE DOES NOT PERMIT, THE USE, OF SHORT RADIUS <br />19. THE CONTRACTOR SHALL BE APPROVED BY THE LANDLORD TO BALANCE <br />ELBOWS HAVING A MINIMUM RADIUS OF 1.0 TIMES THE WIDTH OR DIAMETER OF <br />THE SYSTEMS TO DESIGN SPECIFICATIONS. THE CONTRACTOR SHALL <br />THE DUCT, OR SQUARE ELBOWS WITH FACTORY FABRICATED TURNING VANES <br />CONTACT <br />SCHEDULE ALL WORK THROUGH THE LANDLORDS FIELD REP. <br />MAY BE USED. ALL DUCT JOINTS AND TRANSVERSE AND LONGITUDINAL SEAMS <br />0.716.884.0059 <br />F. 716.884.6414 <br />20. CONTRACTOR SHALL ADHERE TO ALL REQUIREMENTS SPECIFIED BY <br />SHALL BE SEALED WITH A LATEX TYPE DUCT SEALER APPROVED BY THE <br />SCHEIDAIA.COM <br />LANDLORD. <br />ENGINEER. FITTINGS: SQUARE ELBOWS, FITTINGS, AND BRANCH TAKE -OFFS <br />21, FLEX DUCTWORK SHALL NOT EXCEED MAXIMUM OF 5'-0". WHERE REQUIRED <br />SHALL BE DESIGNED AND CONSTRUCTED AS SPECIFIED IN SMACNA. ALL <br />CONTRACTOR SHALL EXTEND ROUND GALVANIZED TO FLEX. <br />GENERAL VENTILATION ITEMS SHALL COMPLY WITH NFPA BULLETIN 90A. <br />22. CONTRACTOR SHALL CHANGE HVAC FILTERS UPON COMPLETION OF <br />SLEEVED AND FRAMED OPENINGS: SPACE BETWEEN THE SLEEVED OR FRAMED <br />WORK, <br />OPENING AND THE DUCT AND THE DUCT INSULATION SHALL BE PACKED WITH <br />23. CONTRACTOR SHALL HAVE THE EXISTING ROOF TOP UNITS INSPECTED <br />MINERAL WOOL OR OTHER APPROVED MATERIAL TO MEET THE REQUIREMENTS <br />PRIOR TO START OF WORK. SUBMIT REPORT OF CONDITION AND <br />OF WALL CONSTRUCTION FOR SMOKE OR FIRE CONTROL. <br />CERTIFICATION THAT THE UNIT COMPLIES WITH THE REQUIREMENTS OF <br />WASHINGTON AND IS PROPERLY TAGGED. PROVIDE REPORT TO <br />AIR DEVICES: <br />'VISIONARY PROPERTIES' WITH A COPY TO THE ARCHITECT AND LANDLORD. <br />SEE SCHEDULES ON THE PLANS. <br />24. CONTRACTOR SHALL ALLOW FOR RISE AND DROP OF DUCTWORK, ALLOW <br />MIN. 6" CLEARANCE FROM TOP OF LIGHT FIXTURE TO BOTTOM OF DUCT. <br />HEATINGICOOLING UNITS: <br />SEE SCHEDULE & DETAILS THIS SHEET. <br />ACOUSTICAL DUCT LINING: <br />LOCATION: RETURN AIR DUCTS, AIR TRANSFER DUCTS, OR AS INDICATED ON <br />THE PLANS. <br />TYPE: V THICK, 1.5LB DENSITY FIBERGLASS DUCT LINER MATERIAL. IN <br />ACCORDANCE WITH FED. SPEC. HH-1-545, TYPES I AND II, <br />APPLICATION: APPLY WITH RETAINING PIN AND GALVANIZED SHEET METAL <br />DISCS AS PER THE MANUFACTURERS RECOMMENDATIONS. GENERAL DUCT <br />DIMENSIONS INDICATED ON THE DRAWINGS ARE FOR INSIDE CLEAR <br />DIMENSIONS. LININGS IN AIR DUCTS AND EQUIPMENT SHALL MEET THE <br />EROSION TEST METHOD DESCRIBED IN UNDERWRITERS LABORATORIES INC. <br />PUBLICATION NO. 181. <br />INSULATION - DUCTWORK: <br />A ISSUE DATE DESCRIPTION <br />PROVIDE ALL LABOR, MATERIALS, ETC -...REQUIRED TO PRODUCE A <br />08/27/2021 CHECK SET ---- <br />COMPLETELY FINISHED INSULATION SYSTEM FOR THE FOLLOWING: <br />SUPPLY AIR DUCTWORK. <br />09/01/2021 PERMIT SET <br />FLAME AND SMOKE RATINGS: PROVIDE COMPOSITE MECHANICAL INSULATION <br />-� <br />(INSULATION JACKETS, COVERINGS, SEALERS, MASTICS, AND ADHESIVES WITH <br />FLAME SPREAD RATING OF 25 OR LESS, AND SMOKE DEVELOPMENT RATING OF <br />i <br />150 OR LESS, AS TESTED BY ANSI/ASTM E84 (NFPA 255) METHODS. <br />SUPPLY DUCT INSULATION: <br />MAKE: OWENS CORNING, CERTAINTEED, KEENE. <br />TYPE: BLANKET FIBERGLASS IN CONCEALED AREAS, RIGID TYPE IN EXPOSED <br />AREAS PROVIDE WITH FIRE RETARDANT JACKET <br />NUT J -ANGLE, CHANNEL, OR UNISTRUT. - NUT <br />SIZE FOR LOAD. <br />NOTE: <br />MIN. INSULATION R6 VALUE PER 2018 <br />INTERNATIONAL MECHANICAL CODE <br />(�A­T APE E DUCT HA DTL. <br />SCALE: 1/4" = 1'-0" <br />A <br />B- <br />9FIVE 45° THREE SECTION APPLICATION: SEAT JOINTS AND LAB WITH VAPOR BARRIER MASTIC AND VAPOR <br />SECTION ELBOW ELBOW JOINT STRIPS. BLANKET INSULATION ON DUCTS WITH MECHANICAL FASTENERS <br />AT NO MORE THAN 18" O.C. RIGID INSULATION WILL BE IMPALED ON PINS <br />LOCATED NO LESS THAN 12" O.C. THE PINS SHALL BE COVERED WITH <br />,90 BENJAMIN/FOSTER 30-35 MASTIC AND CAPS. <br />®° SCHEDULE (UNLESS OTHERWISE NOTED): R-6 FOR SUPPLY DUCTWORK. <br />i� ° <br />- - - - - TEMPERATURE CONTROLS: <br />PROVIDED BY EQUIPMENT MANUFACTURER AND MECHANICAL CONTRACTOR - <br />INSTALLED BY MECHANICAL CONTRACTOR, ALL WIRING IN EMT BY THIS <br />90° BRANCH TAKE -OFF 45° BRANCH TAKE -OFF CONTRACTOR & SUBCONTRACTOR <br />4 HVAC OD DUCT FITTINGS DTL, <br />4)-SCALE: TOILET NROOM F EXHAUST: <br />NTS ON: <br />CEILING FAN TO BE CONTROLLED BY TIMECLOCK <br /><c lEiOIRLESS AIR AiR I- <br />FLOW FLODU 15° OR LESS - <br />TRANSFORMATION EXPANSION <br />TURNING VANES --\ <br />TURNING VANES THREE <br />jr <br />TURNING <br />VANES <br />90° ELBOW <br />45° ELBOW SIMILAR NO THROAT RADIUS <br />SLOPE = 1"IN 7MAX. <br />VIN <br />TURNING 0,4°,MIN. <br />4 SUPPLY OR RETURN WYE ) <br />(RECTANGULAR DUCT) l <br />AIR SCOOP <br />SPIN -IN <br />CONNECTION <br />MINIMUM SUPPORT STRAP <br />PER 2018 INTERNATIONAL j - 0 <br />MECHANICAL CODE �/� °� L- <br />90° ELBOW TAKE -OFF <br />SUSPENDED CEILING RETURN AIR BRANCH USE ONLY IN AREAS <br />FITTING WHERE SPACE IS LIMITED <br />HVAC DUCT INSTALLATION DTL. <br />SCALE: NTS <br />ELEC/IT ROOM VENTILATION: _ - <br />CEILING TRANSFER FAN SHALL TO HAVE THERMOSTATIC CONTROL WITH SEALISIGNATURE <br />RANGE OF 75-90 DEGREES AND BE DUCTED BELOW ROOF DECK. PROVIDE <br />A9R <br />OPERABLE DAMPER. <br />30° <br />FLOW <br />ADJUSTING BALANCING TESTING AND INSPECTION: 1482 <br />TESTING, BALANCING, AND ADJUSTING: REGISTERED <br />CONTRACTION <br />ALL AIR SYSTEMS SHALL BE BALANCED. TESTING, BALANCING, AND ADJUSTING HIT T <br />SHALL BE PERFORMED BY FIRMS IN COMPLIANCE WITH THE PARAGRAPH ON <br />/01/2021 <br />PERFORMANCE. <br />�0 <br />FIELD TESTS: DOiG AS M. CHEI <br />PROPOSED TESTING PROGRAM SHALL BE SUBMITTED TO THE ARCHITECT AT STA E F A G 0 <br />_ <br />LEAST TWO WEEKS PRIOR TO THE SCHEDULED TEST TO ASSURE AGREEMENT <br />p <br />AS TO PERSONAL AND INSTRUMENTATION REQUIRED, AND THE SCOPE OF <br />D <br />TESTING PROGRAM. FINAL TEST REPORT SHALL BE ON PREPARED FORMS AND. <br />MUST BE SUBMITTED TO OWNER AND ARCHITECT. <br />FULL RADIUS <br />VERIFICATION OF DIMENSIONS: <br />THE CONTRACTOR SHALL BECOME FAMILIAR WITH ALL DETAILS OF THE WORK, <br />VERIFY ALL DIMENSIONS IN THE FIELD, AND SHALL ADVISE THE ARCHITECT OF <br />ANY DISCREPANCY BEFORE PERFORMING WORK. <br />SLOPE = VIN 7"MAX- <br />VI N 4"MIN C®ORDINATION. This drawing is copyrighted under the United States Copy Right Law and is the property <br />HEATING CONTRACTOR SHALL COORDINATE ALL WORK AND MATERIALS WITH of Scheid Architectural, the use of this drawing in any form without written permission is <br />strictly prohibited. <br />OTHER CONTRACTORS. THIS WORK SHALL INCLUDE, BUT NOT BE LIMITED TO SHEET TITLE <br />THE FOLLOWING: ELECTRICAL WORK: PROVIDE WIRING DIAGRAMS, MOTOR <br />STARTER RECOMMENDATIONS (INCLUDING: TYPE, SIZE, AND FUSING MECHANICAL PLANS, NOTES <br />REQUIREMENTS), LOCATION OF STARTERS AND DISCONNECT SWITCHES. SCHEDULES <br />GUAGUA NTEE- <br />® Zz ON FINAL COMPLETION, FURNISH TO OWNER, A WRITTEN GUARANTEE <br />LL-D1 COVERING THE COMPLETE INSTALLATION FOR A PERIOD OF (1) YEAR FROM ' C)�b <br />THE DATE OF WORK STATING IN EFFECT THAT ANY DEFECTS IN MATERIALS OR-- <br />� �,I a1 a a. IT <br />WORKMANSHIP OCCURRING DURING TERMS OF SAID GUARANTEE SHALL BE ` ` W "u .i a` <br />MADE GOOD BY THE CONTRACTOR WITHOUT THE EXPENSE OF THE OWNER, <br />FULL RADIUS ELBOW <br />TAKE -OFF <br />SHEET <br />