Laserfiche WebLink
I <br /> Section 40 90 00 PROCESS CONTROL SYSTEM GENERAL PROVISIONS <br /> I2.02 PLC <br /> I A. The Programmable Logic Controller shall be a Rugid RUG9D with R9CAGE 9- <br /> slot expansion rack. <br /> B. Display shall be Rugid LCD2 20 line by 40 character LCD display. <br /> IC. Input and Output cards shall be as shown on the drawings. <br /> 111 2.03 PILOT DEVICES, OPERATORS, LIGHTS AND PUSHBUTTONS <br /> A. GENERAL <br /> V1. Pilot devices (control units and stations): heavy duty, oil-tight type per <br /> NEMA lCS-1. Pilot devices shall be contained within metal housings. <br /> IProvide 30-millimeter pilot devices unless otherwise indicated. <br /> B. SELECTOR SWITCHES <br /> II1. Selector switches shall be for use on 120- or 24-volt control circuits. <br /> Contacts shall have a continuous current rating of 10 amperes both <br /> inductive and resistive. Selector switches shall be of the heavy duty oil <br /> I tight type. Allen Bradley 800T, 800H, GE CR104P, Square D Type K or <br /> approved equal. <br /> IC. PUSH BUTTONS <br /> 1. Push buttons and illuminated push buttons shall be for use on 120-volt <br /> I control circuits. and shall have continuous current rating of 10 amperes <br /> both inductive and resistive. Pushbuttons for"emergency" "help" <br /> applications shall have maintained contacts and red mushroom head <br /> I <br /> operators. Allen Bradley Bulletin 800T, 800H or approved equal. <br /> D. INDICATING LIGHTS <br /> I 1. Indicating lights shall be push-to-test LED type unless otherwise noted. <br /> Illuminated pushbutton type with the pushbutton wired for the push-to-test <br /> function required. Provide universal voltage LED lamp suitable for use on <br /> I12-130 volts alternating or direct current. <br /> 2. Provide lens colors for indicating function. Unless noted otherwise, <br /> provide the following lens color: <br /> Ia. Green color shall be used for"Running", <br /> b. Red color shall be used for"Stopped", <br /> Ic. Amber shall be used for"Alarm" or"Fault", <br /> d. White shall be used for"OK" and <br /> Ie. Blue shall be used for"Maintenance Mode"or"Alternate Mode". <br /> 3. Provide Rockwell Automation (Allen-Bradley) 800T or 800H series, or <br /> equal.I <br /> City of Everett 40 90 00-7 January 2022 <br /> Evergreen Pump Station Modifications <br /> UP3747-3 <br /> IIssued for Bid <br />