Laserfiche WebLink
problems are arising in the field due to the lack of an approved mechanical permit for the <br /> building. <br /> • For the question of required ventilation for habitable spaces and bathrooms the guiding code is <br /> the 2015 International Property Maintenance Code (please find attached). <br /> o In short, if the kitchen and/or toilet rooms have a window(of a minimum size)that <br /> opens directly to the exterior,ventilation is satisfied (in existing buildings). If the kitchen <br /> and/or toilet room does not have a window that opens directly to the exterior, as is the <br /> case with some of the toilet rooms in this building, mechanical exhaust is required. <br /> • For the laundry room, an exhaust fan and dryer ducts are required to be vented to the outside <br /> per IMC Section 403.3.1.1 and IPMC Section 403.5.These items should be part of the <br /> mechanical permit for the building. <br /> • As the corridor is not habitable space, it will not require ventilation. <br /> Other items found: <br /> • We are not able to find a permit(s)for the water heaters in the basement mechanical room - <br /> which are required.A permit was found for the gas piping (M1808-022). <br /> Thank you for your inquiry. Please let me know if I may be of further service. <br /> Sincerely, <br /> Tony Lee <br /> Building Official <br /> 0 3200 Cedar Street 0 425.257.8810 tlee@everettwa.gov <br /> Everett,WA 98201 425.257.8401 fax everettwa.gov <br />