SECTION 230593 - HVAC TESTING, ADJUSTING AND BALANCING CONTINUED <br />2.3 EXAMINATION CONTINUED <br />B. TEST AND VERIFICATION OF CONTROL SYSTEM <br />1. THE AIR BALANCE AND TESTING AGENCY, WITH THE AID OF THE CONTROL CONTRACTOR, <br />SHALL VERIFY THAT THE CONTROL SYSTEMS ARE PERFORMING IN ACCORDANCE TO THE <br />SPECIFIED CRITERIA. <br />2. THIS PROCEDURE SHALL NOT RELIEVE THE CONTROL CONTRACTOR OF ANY <br />RESPONSIBILITIES. THIS PARAGRAPH IS INTENDED TO INSURE THAT THE CONTROL <br />SYSTEM IS COMPLETELY OPERATIONAL AND ADJUSTED AT THE TIME THE AIR SYSTEMS <br />TESTING AND BALANCING IS BEING ACCOMPLISHED. <br />2.4 PREPARATION <br />A. PREPARE A TAB PLAN THAT INCLUDES STRATEGIES AND STEP-BY-STEP PROCEDURES, <br />B. COMPLETE SYSTEM -READINESS CHECKS AND PREPARE REPORTS. <br />C. PROVIDE INSTRUMENTS REQUIRED FOR TESTING, ADJUSTING AND BALANCING OPERATIONS. <br />2.5 PROCEDURES <br />A. GENERAL <br />1. ALL PROCEDURES SHALL BE IN ACCORDANCE WITH AND MEET ALL THE REQUIREMENTS <br />OF EITHER AABC OR NEBB PROCEDURAL STANDARDS FOR ALL EQUIPMENT AND SYSTEMS <br />INCLUDED IN THE PROJECT. THE REQUIREMENTS LISTED IN THIS SECTION ARE <br />INTENDED TO BE SUPPLEMENTARY TO THE REQUIREMENTS OF THESE STANDARDS. <br />B. EXISTING SYSTEMS <br />1. PERFORM A PRE -CONSTRUCTION INSPECTION OF EXISTING EQUIPMENT THAT IS TO <br />REMAIN AND BE REUSED. <br />2. MEASURE AND RECORD THE OPERATING SPEED, AIRFLOW AND STATIC PRESSURE OF <br />EACH FAN. <br />a. MEASURE MOTOR VOLTAGE AND AMPERAGE. COMPARE THE VALUES TO MOTOR <br />NAMEPLATE INFORMATION. <br />3. BEFORE PERFORMING TESTING AND BALANCING OF EXISTING SYSTEMS, INSPECT EXISTING <br />EQUIPMENT THAT IS TO REMAIN AND BE REUSED TO VERIFY THAT EXISTING EQUIPMENT <br />HAS BEEN CLEANED AND REFURBISHED. <br />a. DEFICIENCIES NOTED IN THE PRE -CONSTRUCTION REPORT ARE CORRECTED. <br />4. PERFORM TESTING AND BALANCING OF EXISTING SYSTEMS TO THE EXTENT THAT <br />EXISTING SYSTEMS ARE AFFECTED BY THE RENOVATION WORK. <br />2.6 TOLERANCES <br />A. BALANCE ALL SYSTEMS TO WITHIN PLUS OR MINUS 10% OF DESIGN PARAMETERS. WHEN <br />SYSTEM PERFORMANCE ALLOWS, BALANCE SYSTEMS SO THAT TOTAL SYSTEM FLOWS ARE AT <br />A MINIMUM OF 100% OF DESIGN PARAMETERS, WITHOUT CAUSING ANY INDIVIDUAL FLOW <br />LOCATION TO BE MORE THAN 10% IN EXCESS OF DESIGN PARAMETERS. <br />2.7 REPORTING <br />A. FINAL REPORT <br />1. GENERAL: PREPARE A CERTIFIED WRITTEN REPORT; TABULATE AND DIVIDE THE REPORT <br />INTO SEPARATE SECTIONS FOR TESTED SYSTEMS AND BALANCED SYSTEMS. <br />a. INCLUDE A CERTIFICATION SHEET AT THE FRONT OF THE REPORT'S BINDER, SIGNED <br />AND SEALED BY THE CERTIFIED TESTING AND BALANCING ENGINEER. <br />b. INCLUDE A LIST OF INSTRUMENTS USED FOR PROCEDURES, ALONG WITH PROOF OF <br />CALIBRATION. <br />2.8 INSPECTIONS <br />A. FINAL INSPECTION: <br />1. AFTER INITIAL INSPECTION IS COMPLETE AND DOCUMENTATION BY RANDOM CHECKS <br />VERIFIES THAT TESTING AND BALANCING ARE COMPLETE AND ACCURATELY DOCUMENTED <br />IN THE FINAL REPORT, REQUEST THAT A FINAL INSPECTION BE MADE. <br />2. IF RECHECKS YIELD MEASUREMENTS THAT DIFFER FROM THE MEASUREMENTS <br />DOCUMENTED IN THE FINAL REPORT BY MORE THAN THE TOLERANCES ALLOWED, THE <br />MEASUREMENTS SHALL BE NOTED AS "FAILED." <br />3. IF THE NUMBER OF "FAILED" MEASUREMENTS IS GREATER THAN 10 PERCENT OF THE <br />TOTAL MEASUREMENTS CHECKED DURING THE FINAL INSPECTION, THE TESTING AND <br />BALANCING SHALL BE CONSIDERED INCOMPLETE AND SHALL BE REJECTED. <br />B. TAB WORK WILL BE CONSIDERED DEFECTIVE IF IT DOES NOT PASS FINAL INSPECTIONS. <br />C. PREPARE TEST AND INSPECTION REPORTS. <br />PART 1 GENERAL <br />1.1 QUALITY ASSURANCE <br />A. CONSTRUCT DUCTWORK TO THE UNIFORM MECHANICAL CODE AND SMACNA, HVAC DUCT <br />CONSTRUCTION STANDARDS - METAL AND FLEXIBLE, LATEST EDITION. <br />PART 2 PRODUCTS <br />2.1 SHEET METAL MATERIALS <br />A. COMPLY WITH SMACNA'S "HVAC DUCT CONSTRUCTION STANDARDS --METAL AND FLEXIBLE" <br />FOR ACCEPTABLE MATERIALS, MATERIAL THICKNESS AND DUCT CONSTRUCTION METHODS, <br />UNLESS OTHERWISE INDICATED. SHEET METAL MATERIALS SHALL BE FREE OF PITTING, <br />SEAM MARKS, ROLLER MARKS, STAINS, DISCOLORATIONS AND OTHER IMPERFECTIONS. <br />B. GALVANIZED SHEET STEEL: LOCK -FORMING QUALITY; COMPLYING WITH ASTM A 653/A 653M <br />AND HAVING G60 (Z180) COATING DESIGNATION; DUCTS SHALL HAVE MILL-PHOSPHATIZED <br />FINISH FOR SURFACES EXPOSED TO VIEW. <br />2.2 LOW VELOCITY DUCTWORK AND FITTINGS <br />A. GENERAL <br />1. LOW VELOCITY DUCTWORK SHALL BE DEFINED AS ALL DUCTWORK NOT SPECIFICALLY <br />DEFINED AS MEDIUM VELOCITY DUCTWORK. <br />2, FABRICATE, INSTALL AND SUPPORT IN ACCORDANCE WITH SMACNA HVAC DUCT <br />CONSTRUCTION STANDARDS - METAL AND FLEXIBLE, THE UNIFORM MECHANICAL CODE, <br />AND AS INDICATED. PROVIDE DUCT MATERIAL, GAGES, REINFORCING AND SEALING FOR <br />OPERATING PRESSURES INDICATED. <br />B. RECTANGULAR DUCT AND FITTING FABRICATION <br />1. FABRICATE DUCTS, ELBOWS, TRANSITIONS, OFFSETS, BRANCH CONNECTIONS, AND OTHER <br />CONSTRUCTION ACCORDING TO SMACNA'S "HVAC DUCT CONSTRUCTION <br />STANDARDS --METAL AND FLEXIBLE' AND COMPLYING WITH REQUIREMENTS FOR METAL <br />THICKNESS, REINFORCING TYPES AND INTERVALS, TIE -ROD APPLICATIONS AND JOINT <br />TYPES AND INTERVALS. <br />C. ROUND AND FLAT -OVAL DUCT AND FITTING FABRICATION <br />1. GENERAL <br />a. DIAMETER AS APPLIED TO FLAT -OVAL DUCTS IN THIS ARTICLE IS THE DIAMETER OF A <br />ROUND DUCT WITH A CIRCUMFERENCE EQUAL TO THE PERIMETER OF A GIVEN SIZE OF <br />FLAT -OVAL DUCT. <br />b. ROUND, LONGITUDINAL- AND SPIRAL LOCK -SEAM DUCTS: FABRICATE SUPPLY DUCTS OF <br />GALVANIZED STEEL ACCORDING TO SMACNA'S "HVAC <br />c. DUCT CONSTRUCTION STANDARDS --METAL AND FLEXIBLE." <br />d. FLAT -OVAL, SPIRAL LOCK -SEAM DUCTS: FABRICATE SUPPLY DUCTS ACCORDING TO <br />SMACNA'S "HVAC DUCT CONSTRUCTION STANDARDS --METAL AND FLEXIBLE" FABRICATE <br />DUCTS LARGER THAN 72 INCHES (1830 MM) IN DIAMETER WITH CONTINUOUSLY <br />BUTT -WELDED LONGITUDINAL SEAMS. <br />2.3 MEDIUM VELOCITY DUCTWORK AND FITTINGS <br />A. GENERAL <br />1. MANUFACTURERS <br />a. UNITED MCGILL CORP., b. VENTLINE, c. METCO. <br />2. BASIS OF DESIGN <br />a. UNITED MCGILL CORP., MODEL UNI-SEAL; UN -LINED. <br />3. UNITED MCGILL CORP., MODEL K-27; LINED WITH INSULATION. <br />4. MEDIUM VELOCITY DUCTWORK SHALL BE DEFINED AS ALL DUCTWORK BETWEEN THE AIR <br />HANDLING UNIT OR MAIN SYSTEM FAN AND THE TERMINAL SUPPLY BOXES; OR EXHAUST. <br />5. FABRICATE, INSTALL AND SUPPORT IN ACCORDANCE WITH SMACNA HVAC DUCT CONSTRUCTION <br />STANDARDS - METAL AND FLEXIBLE, THE UNIFORM MECHANICAL CODE AND AS INDICATED. <br />PROVIDE DUCT MATERIAL, GAGES, REINFORCING AND SEALING FOR OPERATING PRESSURES. <br />B. ROUND DUCTS <br />DUCT SIZE INCHES U.S. DUCT GAUGE UP TO 8 TO 14 TO 26 TO 36 <br />FITTING SIZE INCHES U.S. DUCT GAUGE UP TO 26 TO 50 <br />C. FLAT OVAL DUCTS <br />1. DUCT GAUGE: IN ACCORDANCE WITH SMACNA. <br />DUCT SIZE (MAJOR AXIS) INCHES U.S. DUCT GAUGE UP TO 24 TO 48 <br />FITTING SIZE INCHES U.S. DUCT GAUGE UP TO 36 CHEMICAL FUME HOOD EXHAUST DUCTWORK <br />2.4 CHEMICAL FUME HOOD EXHAUST DUCTWORK <br />A. FABRICATE AND SUPPORT IN ACCORDANCE WITH SMACNA, HVAC DUCT CONSTRUCTION STANDARD, <br />METAL AND FLEXIBLE AND THE UNIFORM MECHANICAL CODE. PROVIDE DUCT MATERIAL, GAGES, <br />REINFORCING AND SEALING FOR OPERATING PRESSURES INDICATED. <br />2.5 FLEXIBLE DUCTS: <br />A. MANUFACTURERS: <br />1. GENFLEX, 2. THERMAFLEX, 3. THERMOLD, 4. WIREMOLD, 5. HART & COOLEY <br />B. BASIS OF DESIGN: THERMAFLEX, MODEL G-KM. <br />C. U.L. 181 CLASS 1 FLEXIBLE AIR DUCT COMPLYING WITH NFPA STANDARD 9OA; FACTORY <br />FABRICATED ASSEMBLY COMPOSED OF AN INNER LINER, COATED WOUND SPRING STEEL WIRE, 1 <br />INCH THICK FIBERGLASS INSULATION (INSTALLED R-VALUE 4.3) AND A VAPOR BARRIER OUTER <br />JACKET. <br />2.6 HANGERS AND SUPPORTS <br />A. HANGER MATERIALS: GALVANIZED SHEET STEEL OR THREADED STEEL ROD AT THE CONTRACTOR'S <br />OPTION, WITH THE FOLLOWING LIMITATIONS: <br />1. HANGERS EXPOSED IN FINISHED AREAS: USE THREADED ROD. <br />2. STRAP AND ROD SIZES: COMPLY WITH SMACNA'S "HVAC DUCT CONSTRUCTION <br />STANDARDS --METAL AND FLEXIBLE" FOR STEEL SHEET WIDTH AND THICKNESS AND FOR <br />STEEL ROD DIAMETERS. <br />B. DUCT ATTACHMENTS: SHEET METAL SCREWS, BLIND RIVETS OR SELF -TAPPING METAL SCREWS; <br />COMPATIBLE WITH DUCT MATERIALS. <br />PART 3 EXECUTION <br />3.1 DUCT APPLICATIONS <br />A. STATIC -PRESSURE CLASSES: UNLESS OTHERWISE INDICATED, CONSTRUCT DUCTS ACCORDING TO <br />THE FOLLOWING. MEDIUM VELOCITY DUCTS SHALL INCLUDE ALL SUPPLY DUCTWORK BETWEEN <br />FANS AND VAV BOXES. MEDIUM VELOCITY DUCTWORK SHALL ALSO INCLUDE EXHAUST SYSTEMS <br />SYSTEMS WITH VELOCITIES IN EXCESS OF 1,800 FPM. <br />1. LOW VELOCITY DUCTS: 2-INCH WG OR 1.5 TIMES THE LISTED EXTERNAL PRESSURE OF THE <br />FAN SERVING THE DUCT SYSTEM, WHICHEVER IS HIGHER. <br />2. MEDIUM VELOCITY DUCTS: 6-INCH WG OR 1.5 TIMES THE LISTED EXTERNAL PRESSURE OF <br />THE FAN SERVING THE DUCT SYSTEM, WHICHEVER IS HIGHER. <br />3.2 DUCT INSTALLATION <br />A. CONSTRUCT AND INSTALL DUCTS ACCORDING TO SMACNA'S "HVAC DUCT CONSTRUCTION <br />STANDARDS -METAL AND FLEXIBLE," UNLESS OTHERWISE INDICATED. <br />B. INSTALL DUCTS, UNLESS OTHERWISE INDICATED, VERTICALLY AND HORIZONTALLY AND PARALLEL <br />AND PERPENDICULAR TO BUILDING LINES; AVOID DIAGONAL RUNS. <br />C. COORDINATE LAYOUT WITH SUSPENDED CEILING, FIRE- AND SMOKE -CONTROL DAMPERS, LIGHTING <br />LAYOUTS AND SIMILAR FINISHED WORK. <br />D. FIRE -RATED PARTITION PENETRATIONS: WHERE DUCTS PASS THROUGH INTERIOR PARTITIONS AND <br />EXTERIOR WALLS, INSTALL APPROPRIATELY RATED FIRE OR FIRE/SMOKE DAMPERS, SLEEVES AND <br />FIRESTOPPING SEALANT. <br />E. INSTALL DUCTS WITH HANGERS AND BRACES DESIGNED TO WITHSTAND, WITHOUT DAMAGE TO <br />EQUIPMENT, SEISMIC FORCE REQUIRED BY APPLICABLE BUILDING CODES. REFER TO SMACNA'S <br />"SEISMIC RESTRAINT MANUAL: GUIDELINES FOR MECHANICAL SYSTEMS." <br />3.3 SEAM AND JOINT SEALING <br />A. SEAL DUCT SEAMS AND JOINTS ACCORDING TO SMACNA'S "HVAC DUCT CONSTRUCTION <br />STANDARDS --METAL AND FLEXIBLE" FOR DUCT PRESSURE CLASS INDICATED. <br />1. FOR PRESSURE CLASSES LOWER THAN 2-INCH WG, SEAL TRANSVERSE JOINTS. <br />SECTION 233300 - DUCT ACCFSSCRIFS <br />PART 1 GENERAL <br />1.1 SUBMITTALS <br />A. GENERAL <br />1. PRODUCT DATA FOR SPECIFIED MATERIALS. <br />PART 2 PRODUCTS <br />2.1 BACKDRAFT DAMPERS <br />A. MANUFACTURERS <br />1. AIR CONTROL PRODUCTS, 2. AMERICAN WARMING AND VENTILATION, 3. GREENHECK, 4. <br />POTTORFF, 5. RUSKIN. <br />B. DESCRIPTION: MULTIPLE -BLADE; PARALLEL ACTION; GRAVITY BALANCED; CENTER -PIVOTED BLADES <br />OF MAXIMUM 6-INCH WIDTH; SEALED EDGES; ASSEMBLED IN RATTLE -FREE MANNER WITH <br />90-DEGREE STOP; STEEL BALL BEARINGS AND AXLES; ADJUSTMENT DEVICE TO PERMIT SETTING <br />FOR VARYING DIFFERENTIAL STATIC PRESSURE. <br />PART 1 GENERAL <br />1.1 SUBMITTALS <br />A. GENERAL <br />1. PRODUCT DATA FOR SPECIFIED MATERIALS. <br />PART 2 PRODUCTS <br />2A BACKDRAFT DAMPERS <br />A. MANUFACTURERS <br />1. AIR CONTROL PRODUCTS, 2. AMERICAN WARMING AND VENTILATION, 3, GREENHECK, 4. <br />POTTORFF, 5. RUSKIN. <br />B. DESCRIPTION: MULTIPLE -BLADE; PARALLEL ACTION; GRAVITY BALANCED; CENTER -PIVOTED <br />BLADES OF MAXIMUM 6-INCH WIDTH; SEALED EDGES; ASSEMBLED IN RATTLE -FREE MANNER <br />WITH 90-DEGREE STOP; STEEL BALL BEARINGS AND AXLES; ADJUSTMENT DEVICE TO PERMIT <br />SETTING FOR VARYING DIFFERENTIAL STATIC PRESSURE. <br />2.2 <br />DUCT -MOUNTING ACCESS DOORS <br />A. <br />MANUFACTURERS <br />1. CESCO PRODUCTS, 2. DUCTMATE INDUSTRIES, <br />INC., 3. GREENHECK, <br />4. MCGILL AIRFLOW <br />CORPORATION, 5. NAILOR INDUSTRIES <br />INC. <br />B. <br />GENERAL DESCRIPTION: FABRICATE DOORS <br />AIRTIGHT AND SUITABLE FOR <br />DUCT PRESSURE <br />CLASS. <br />C. <br />STANDARD ACCESS DOOR: DOUBLE WALL; <br />DUCT MOUNTING; FABRICATED <br />OF GALVANIZED <br />SHEET METAL WITH INSULATION FILL AND <br />THICKNESS AS INDICATED FOR <br />DUCT PRESSURE <br />CLASS. <br />2.3 FLEXIBLE CONNECTORS <br />A. MANUFACTURERS <br />1. AMERICAN WARMING AND VENTILATING, 2. CESCO PRODUCTS, 3. DUCTMATE INDUSTRIES, <br />INC., 4. GREENHECK, 5. MCGILL AIRFLOW CORPORATION, 6. NAILOR INDUSTRIES INC., 7. <br />POTTORFF, 8. VENTFABRICS, INC. <br />B. GENERAL DESCRIPTION: FLAME-RETARDANT OR NONCOMBUSTIBLE FABRICS, COATINGS AND <br />ADHESIVES COMPLYING WITH UL 181, CLASS 1. <br />2.4 TURNING VANES <br />A. MANUFACTURERS <br />1. AMERICAN WARMING AND VENTILATING, 2. CESCO PRODUCTS, 3. DUCTMATE INDUSTRIES, <br />INC., 4. ELMDOR, 5. GREENHECK, 6, MCGILL AIRFLOW CORPORATION, 7. NAILOR <br />INDUSTRIES INC., 8. POTCRFF, 9. UNITED MCGILL., 10. VENTFABRICS, INC. <br />2.5 VOLUME BALANCING DAMPERS <br />A. MANUFACTURERS <br />1. AMERICAN WARMING AND VENTILATION, 2. GREENHECK, 3. POTTORFF, 4. RUSKIN, 5. <br />DURODYNE. <br />B. GENERAL DESCRIPTION: FACTORY FABRICATED WITH REQUIRED HARDWARE AND ACCESSORIES; <br />DAMPER BLADES STIFFENED FOR STABILITY; LOCKING DEVICE TO HOLD SINGLE -BLADE <br />DAMPERS IN A FIXED POSITION WITHOUT VIBRATION; DUCT PENETRATIONS FOR DAMPER <br />COMPONENTS SEALED CONSISTENT WITH PRESSURE CLASS. <br />PART 3 EXECUTION <br />3.1 GENERAL <br />A. INSTALL DUCT ACCESSORIES ACCORDING TO APPLICABLE DETAILS IN SMACNA'S "HVAC DUCT <br />CONSTRUCTION STANDARDS --METAL AND FLEXIBLE". <br />3.2 ACCESS DOORS <br />A. APPLICATION <br />1. PROVIDE ACCESS DOORS (IN BUILDING WALLS, CEILINGS, ETC.) AS REQUIRED TO ACCESS <br />ALL SYSTEM COMPONENTS THAT REQUIRE MAINTENANCE. <br />3.3 DUCT -MOUNTING ACCESS DOORS <br />A. GENERAL <br />1. LABEL ACCESS DOORS ACCORDING TO DIVISION 23 SECTION "HVAC IDENTIFICATION." <br />B. APPLICATION <br />1. STANDARD ACCESS DOOR. <br />a. PROVIDE WHERE REQUIRED FOR TESTING AND BALANCING PURPOSES. <br />b. PROVIDE WHERE REQUIRED TO PROVIDE ACCESS TO ALL SYSTEM <br />COMPONENTS THAT REQUIRE MAINTENANCE. <br />3.4 FLEXIBLE CONNECTORS <br />A. INSTALL FLEXIBLE CONNECTORS IMMEDIATELY ADJACENT TO EQUIPMENT IN DUCTS ASSOCIATED <br />WITH FANS AND MOTORIZED EQUIPMENT SUPPORTED BY VIBRATION ISOLATORS. <br />3.5 FLEXIBLE DUCTS <br />A. CONNECT DIFFUSERS OR LIGHT TROFFER BOOTS TO LOW PRESSURE DUCTS DIRECTLY OR <br />WITH MAXIMUM 60-INCH (1500-MM) LENGTHS OF FLEXIBLE DUCT CLAMPED OR STRAPPED IN <br />PLACE. DO NOT USE FLEXIBLE DUCTS TO CREATE BENDS GREATER THAN 45'. <br />3.6 TURNING VANES <br />A. APPLICATION <br />1. PROVIDE TURNING VANES IN ALL ELBOWS THAT ARE NOT RADIUSED FOR ALL DUCT <br />SYSTEMS. USE SINGLE VANE CONSTRUCTION FOR LOW VELOCITY SYSTEMS AND DOUBLE <br />VANE CONSTRUCTION FOR MEDIUM VELOCITY SYSTEMS. <br />3.7 VOLUME BALANCING DAMPERS <br />A. INSTALLATION <br />1. WHERE DAMPERS ARE INSTALLED ABOVE INACCESSIBLE CEILINGS, PROVIDE CONCEALED <br />DAMPER REGULATOR AND COVER PLATE. <br />B. APPLICATION <br />1. PROVIDE FOR EACH GRID IN THE DUCTWORK SERVING THAT GRID, WHETHER INDICATED ON <br />THE DRAWINGS OR NOT. OPTIONAL REGISTER DAMPERS PROVIDED AS AN ACCESSORY TO <br />GRD'S ARE NOT AN ACCEPTABLE ALTERNATIVE, UNLESS SUCH ACCESSORY DAMPERS ARE <br />SCHEDULED ON THE DRAWINGS AND SUPPLEMENTARY BALANCING DAMPERS ARE NOT <br />SHOWN ON THE FLOOR PLAN DRAWINGS. USE STANDARD VOLUME DAMPERS UNLESS <br />NOTED TO BE LOW LEAKAGE VOLUME DAMPERS. <br />SECTION 233710 - GRILLES, REGISTERS AND DIFFUSERS <br />PART 1 GENERAL <br />1.1 SUBMITTALS <br />B. GENERAL <br />1. PRODUCT DATA: FOR EACH PRODUCT INDICATED, INCLUDE THE FOLLOWING: <br />a. DATA SHEET: INDICATE MATERIALS OF CONSTRUCTION, FINISH, AND MOUNTING <br />DETAILS; AND PERFORMANCE DATA INCLUDING THROW AND DROP, STATIC -PRESSURE <br />DROP AND NOISE RATINGS. <br />PART 2 PRODUCTS <br />2.1 GENERAL <br />A. DAMPERS: PROVIDED AS AN ACCESSORY TO GRD'S WHEN SCHEDULED ON THE DRAWINGS. <br />DAMPERS SHALL BE OPPOSED BLADE, HEAVY GAUGE STEEL AND SHALL BE ADJUSTABLE <br />FROM THE FACE OF THE INLET OR OUTLET. <br />B. FRAME TYPES AND MOUNTING HARDWARE: COORDINATED WITH CEILING TYPES. <br />ARCHITECTURAL PLANS SHALL TAKE PRECEDENCE WHEN REFERENCING CEILING TYPES, <br />AND CONTRACTOR SHALL REFERENCE THE ARCHITECTURAL PLANS FOR VERIFICATION OF <br />CEILING TYPE PRIOR TO ORDERING. <br />2.2 GENERAL GRILLES, REGISTERS AND DIFFUSERS <br />A. MANUFACTURERS <br />1. ANEMOSTAT, 2. KRUEGER. 3. POTTORFF, 4. PRICE, 5. TITUS, 6. TUTTLE & BAILEY. <br />B. RETURN/EXHAUST GRILLES: STEEL, ALUMINUM, OR STAINLESS STEEL CONSTRUCTION AS <br />SCHEDULED ON THE DRAWINGS; 1 1/4 INCH (32 MM) BORDER WITH FULLY WELDED <br />CORNERS; FIXED BLADES PARALLEL TO THE LONG DIMENSION WITH SPACING AND <br />DEFLECTION AS SCHEDULED ON THE DRAWINGS; COUNTERSUNK SCREW MOUNTING HOLES <br />FOR SURFACE MOUNT; NO MOUNTING HOLES FOR LAY -IN MOUNT. <br />BASIS OF DESIGN: TITUS 350/355 SERIES. <br />C. MODULAR CORE CEILING DIFFUSERS: STEEL OR ALUMINUM CONSTRUCTION; MINIMUM 1 <br />INCH (25 MM) DEPTH FOR DUCT CONNECTION; 4 FIXED LOUVER DIRECTIONAL MODULES, <br />INDIVIDUALLY REMOVABLE AND ADJUSTABLE WITHOUT TOOLS. <br />1. BASIS OF DESIGN: TITUS MCD SERIES. <br />2.3 LINEAR SLOT CEILING DIFFUSERS <br />A. MANUFACTURERS <br />1. PRICE, 2. TITUS, 3. TUTTLE & BAILEY. <br />B. SLOT SUPPLY DIFFUSERS: HEAVY GAUGE EXTRUDED ALUMINUM FRAME AND SUPPORT <br />BARS; AERODYNAMICALLY CURVED 'ICE TONG' SHAPED PATTERN CONTROLLERS FOR 180 <br />DEGREE AIR PATTERN CONTROL AND DAMPERING; CENTER T-BARS. <br />C. SLOT RETURN GRILLES: SAME AS SUPPLY DIFFUSERS, BUT WITH PATTERN CONTROLLER <br />OMITTED. PROVIDE WITH LIGHT SHIELD IN PLENUM RETURN APPLICATIONS. <br />D. BASIS OF DESIGN <br />1. STANDARD T-BAR APPLICATIONS: TITUS TBD-30 SERIES. <br />2. NARROW T-BAR APPLICATIONS: TITUS ML SERIES WITH MP SERIES PLENUM. <br />3. SURFACE MOUNT APPLICATIONS: TITUS ML SERIES WITH MP SERIES PLENUM. <br />PART 3 EXECUTION <br />3.1 GENERAL <br />A. INSTALLATION <br />1. CHECK LOCATIONS AND MAKE NECESSARY ADJUSTMENTS IN POSITION TO CONFORM <br />WITH ARCHITECTURAL FEATURES, SYMMETRY AND LIGHTING ARRANGEMENT. LOCATE IN <br />ACCORDANCE WITH ARCHITECTURAL REFLECTED CEILING PLAN WHEN INDICATED. <br />2. CEILING -MOUNTED OUTLETS AND INLETS: DRAWINGS INDICATE GENERAL ARRANGEMENT <br />OF DUCTS, FITTINGS, AND ACCESSORIES. AIR OUTLET AND INLET LOCATIONS HAVE <br />BEEN INDICATED TO ACHIEVE DESIGN REQUIREMENTS FOR AIR VOLUME, NOISE <br />CRITERIA, AIRFLOW PATTERN, THROW AND PRESSURE DROP. MAKE FINAL LOCATIONS <br />WHERE INDICATED, AS MUCH AS PRACTICABLE. FOR UNITS INSTALLED IN LAY -IN <br />CEILING PANELS, LOCATE UNITS IN THE CENTER OF PANEL. WHERE ARCHITECTURAL <br />FEATURES OR OTHER ITEMS CONFLICT WITH INSTALLATION, NOTIFY ARCHITECT FOR A <br />DETERMINATION OF FINAL LOCATION. <br />EL <br />z <br />Y) <br />c� <br />U <br />0 <br />_ ii Oak <br />es Ave <br />Suite 100 <br />Everett. tPJA 98901 <br />S a n <br />4100 194th Street SW Suite 400 <br />Lynnwood Washington 98036-4613 <br />(206) 667-0555 <br />Copyright Reserved <br />The Contractor shall verify and be responsible for all dimensions. DO <br />NOT scale the drawing -any errors or omissions shall be reported to <br />Stantec without delay. <br />The Copyrights to all designs and drawings are the property of <br />Stantec. Reproduction or use for any purpose o [her than that <br />authorized by Stantec is forbidden. <br />'11*' ®F WAS�r J" <br />6 <br />3, �G I SS�� ��.�y'�' <br />SI®NAL � <br />u. <br />r=LU <br />S� l"13 <br />t1> <br />7j� <br />-\ =1 <br />T <br />0 <br />4- <br />_T0 <br />T <br />�v <br />JOB. NO. II';)-1017 <br />DF21z,1VJN BY R MI <br />CHECKED BY F J <br />11-08-1I< <br />. 1")' F{II'a f, A710NS <br />