SECTION 210000 - FIRE SUPPRESSION PIPING SYSTEMS
<br />1.1 SCOPE OF WORK/DESIGN CRITERIA
<br />A. THE MEANING AND INTENTION OF THESE SPECIFICATIONS, IN CONJUNCTION WITH THE
<br />DRAWING(S), IS TO COVER A COMPLETELY INSTALLED, FULLY OPERATING FIRE
<br />SPRINKLER PROTECTION SYSTEM FOR THE ENTIRE BUILDING. TO ACCOMPLISH THIS
<br />PURPOSE, THE CONTRACTOR SHALL PROVIDE ALL DESIGN, MATERIALS, EQUIPMENT
<br />AND LABOR NECESSARY AND REQUIRED AND WILL BEAR ALL EXPENSES INCIDENTAL
<br />TO THE SATISFACTORY COMPLETION OF THE WORK.
<br />B. IT SHALL BE THE CONTRACTOR'S RESPONSIBILITY TO DESIGN AND INSTALL THE
<br />SYSTEM SO THAT NO INTERFERENCES EXIST BETWEEN THE FIRE PROTECTION PIPING,
<br />AND EQUIPMENT AND SYSTEMS INSTALLED BY OTHER DISCIPLINES.
<br />C. COMPLY WITH APPLICABLE LOCAL CODES, STATE AND LOCAL FIRE MARSHAL'S
<br />STANDARDS, INTERNATIONAL BUILDING CODE, INTERNATIONAL FIRE CODE AND NFPA 13
<br />FOR INSTALLATION AND DESIGN OF SYSTEMS.
<br />D. THE DESIGN SHALL BE GOVERNED FIRST AND FOREMOST BY CODE COMPLIANCE AND
<br />SECONDLY BY THE SPECIFICATIONS/CONTRACT DOCUMENTS. IF A DISCREPANCY
<br />EXISTS BETWEEN CODE AND CONTRACT DOCUMENTS, THE STRICTER SHALL BE
<br />COMPLIED WITH. IF SUCH DISCREPANCY EXISTS, NOTIFICATION IS EXPECTED AND AN
<br />ADDENDUM WILL BE ISSUED.
<br />E. CONTRACTOR IS RESPONSIBLE FOR FEES AND PERMIT COSTS RELATED TO INSTALLING
<br />SYSTEM EXCEPT AS NOTED.
<br />SECTION 220000 - GENERAL PLUMBING REQUIREMENTS
<br />PART 1 GENERAL
<br />1.1 SCOPE OF WORK
<br />INCLUDE COMPLETE AND FUNCTIONAL PLUMBING SYSTEMS - INCLUDING ALL
<br />REQUIRED MATERIALS, LABOR, EQUIPMENT AND SERVICES NECESSARY TO ACHIEVE
<br />THE DESIRED FINAL PRODUCT.
<br />1.2 APPLICABLE CODES
<br />A. WORK SHALL BE PERFORMED IN ACCORDANCE WITH APPLICABLE CODES AND
<br />STANDARDS AS ADOPTED BY THE AUTHORITIES HAVING JURISDICTION INCLUDING
<br />AMENDMENTS. FOLLOWING IS A LISTING OF MAJOR CODES AND STANDARDS, THE
<br />REQUIREMENTS OF WHICH SHALL BE CONSIDERED PART OF THE SCOPE OF THIS
<br />PROJECT. THIS LIST SHOULD NOT BE CONSIDERED COMPREHENSIVE AND CODES OR
<br />STANDARDS NOT INCLUDED IN THIS LIST SHOULD NOT BE CONSIDERED TO BE
<br />EXCLUDED FROM THE SCOPE OF THE PROJECT.
<br />1. AMERICANS WITH DISABILITIES ACT (ADA).
<br />2. APPLICABLE STATE AND LOCAL CODES AND ORDINANCES.
<br />3. NATIONAL ELECTRICAL CODE.
<br />4. INTERNATIONAL BUILDING CODE.
<br />5. INTERNATIONAL FIRE CODE.
<br />6. INTERNATIONAL MECHANICAL CODE.
<br />7. UNIFORM PLUMBING CODE.
<br />8. WASHINGTON STATE NON-RESIDENTIAL ENERGY CODE.
<br />9. WASHINGTON STATE INDOOR AIR QUALITY CODE.
<br />10. WASHINGTON STATE BOILER AND UNFIRED PRESSURE VESSEL CODE.
<br />1.3 PERMITS AND FEES
<br />A. ALL PERMITS AND INSPECTIONS REQUIRED TO COMPLETE THE SCOPE OF WORK
<br />SHALL BE INCLUDED IN THE BID PRICE.
<br />B. ALL FEES REQUIRED BY UTILITY PROVIDERS SHALL BE INCLUDED IN THE DIVISION 22
<br />BID PRICE.
<br />1.4 SCOPE AND APPROPRIATE USE OF BID DOCUMENTS
<br />A. THESE SPECIFICATIONS AND ACCOMPANYING DRAWINGS ARE INTENDED TO
<br />COMMUNICATE THE DESIGN CONCEPT FOR THIS PROJECT AND OUTLINE THE SCOPE
<br />OF WORK. WORK NOT SPECIFICALLY NOTED IN THESE SPECIFICATIONS OR THE
<br />ACCOMPANYING DRAWINGS, BUT WHICH IS REQUIRED TO COMPLETE THE PROJECT,
<br />SHALL BE INCLUDED AS PART OF CONTRACTOR'S SCOPE.
<br />B. THESE SPECIFICATIONS AND THE ACCOMPANYING DRAWINGS ARE INTENDED TO
<br />SUPPLEMENT EACH OTHER. INFORMATION INCLUDED IN EITHER ONE SHALL BE
<br />INCORPORATED INTO THE PROJECT AS IF INCLUDED IN BOTH. IN THE EVENT OF
<br />ANY CONFLICTS, THE MOST STRINGENT REQUIREMENTS SHALL BE CONSIDERED THE
<br />GOVERNING SCOPE OF WORK UNTIL AND UNLESS CLARIFICATION CAN BE OBTAINED
<br />BY THE CONTRACTOR.
<br />C. DRAWINGS ARE INTENDED TO INDICATE THE GENERAL ARRANGEMENT OF PIPING,
<br />DUCTWORK, EQUIPMENT AND OTHER COMPONENTS OF SYSTEMS. THEY SHALL BE
<br />FOLLOWED AS CLOSELY AS POSSIBLE, BUT SHALL BE CONSIDERED DIAGRAMMATIC IN
<br />NATURE. THEY ARE NOT INTENDED TO SHOW EVERY COMPONENT, FITTING, OFFSET,
<br />ETC. COMPONENTS, FITTINGS, OFFSETS, ETC. AS REQUIRED TO MEET THE INTENT OF
<br />THE DOCUMENTS AND TO ACHIEVE COORDINATION WITH OTHER TRADES SHALL BE
<br />INCLUDED IN THE DIVISION 22 SCOPE OF WORK.
<br />1.5 ROUTING AND LOCATIONS
<br />A. IT IS THE CONTRACTOR'S RESPONSIBILITY TO COORDINATE EQUIPMENT LOCATIONS
<br />AND SYSTEM ROUTING WITH AVAILABLE SPACE AND WITH ALL OTHER TRADES.
<br />1.6 SCHEDULING
<br />A. IT IS UNDERSTOOD THAT WHILE DRAWINGS ARE TO BE FOLLOWED AS CLOSELY AS
<br />CIRCUMSTANCES PERMIT, THE CONTRACTOR SHALL BE RESPONSIBLE FOR
<br />INSTALLATION OF SYSTEMS ACCORDING TO THE TRUE INTENT AND MEANING OF
<br />CONTRACT DOCUMENTS. ANYTHING NOT CLEAR OR IN CONFLICT WILL BE EXPLAINED
<br />BY MAKING APPLICATION TO OWNER'S REPRESENTATIVE. THE CONTRACTOR SHALL
<br />FAMILIARIZE HIMSELF WITH HIS SCOPE OF WORK AS WELL AS THE REQUIRED
<br />COORDINATION WITH OTHER TRADES AND THE SCHEDULING OF OTHER TRADES
<br />SUFFICIENTLY TO ADDRESS COORDINATION ISSUES IN A TIMELY MANNER SUCH THAT
<br />THEY DO NOT RESULT IN REMEDIAL WORK FOR OTHER TRADES.
<br />B. THE CONTRACTOR SHALL COORDINATE WITH THE WORK OF VARIOUS TRADES WHEN
<br />INSTALLING INTERRELATED WORK. BEFORE INSTALLATION OF PLUMBING ITEMS,
<br />PROPER PROVISIONS SHALL BE MADE TO AVOID INTERFERENCES. CHANGES
<br />REQUIRED IN WORK SPECIFIED IN DIVISION 22 CAUSED BY NEGLECT TO DO SO
<br />SHALL BE MADE AT NO COST TO OWNER.
<br />1.7 CUTTING AND PATCHING
<br />A. THE DIVISION 22 CONTRACTOR SHALL BE RESPONSIBLE FOR ALL CUTTING AND
<br />PATCHING REQUIRED TO COMPLETE THE DIVISION 22 SCOPE OF WORK.
<br />1.8 GUARANTEE
<br />A. ALL DIVISION 22 SYSTEMS AND EQUIPMENT SHALL BE GUARANTEED FOR A MINIMUM
<br />PERIOD OF ONE YEAR.
<br />B. THE GUARANTEE SHALL BEGIN AT THE DATE OF ACCEPTANCE, UNLESS WRITTEN
<br />DOCUMENTATION IS PROVIDED NOTING OTHERWISE.
<br />1.9 QUALITY ASSURANCE
<br />A, MATERIAL AND EQUIPMENT QUALIFICATIONS
<br />1. PROVIDE MATERIALS AND EQUIPMENT THAT ARE STANDARD PRODUCTS OF
<br />MANUFACTURERS REGULARLY ENGAGED IN THE MANUFACTURE OF SUCH
<br />PRODUCTS, WHICH ARE OF A SIMILAR MATERIAL, DESIGN AND WORKMANSHIP.
<br />STANDARD PRODUCTS SHALL HAVE BEEN IN SATISFACTORY COMMERCIAL OR
<br />INDUSTRIAL USE FOR 2 YEARS PRIOR TO BID OPENING. THE 2-YEAR USE
<br />SHALL INCLUDE APPLICATIONS OF EQUIPMENT AND MATERIALS UNDER SIMILAR
<br />CIRCUMSTANCES AND OF SIMILAR SIZE. THE PRODUCT SHALL HAVE BEEN FOR
<br />SALE ON THE COMMERCIAL MARKET THROUGH ADVERTISEMENTS,
<br />MANUFACTURERS' CATALOGS OR BROCHURES DURING THE 2 YEAR PERIOD.
<br />A. SERVICE SUPPORT: THE EQUIPMENT ITEMS SHALL BE SUPPORTED BY SERVICE
<br />ORGANIZATIONS. WHEN REQUESTED TO GAIN APPROVAL, SUBMIT A CERTIFIED LIST
<br />OF QUALIFIED PERMANENT SERVICE ORGANIZATIONS FOR SUPPORT OF THE
<br />EQUIPMENT WHICH INCLUDES THEIR ADDRESSES AND QUALIFICATIONS.
<br />B. UL LISTINGS: ALL EQUIPMENT SHALL BE PROVIDED WITH A UL OR APPROVED
<br />EQUIVALENT LABEL WHEN LABELING IS AVAILABLE FOR THAT TYPE OF EQUIPMENT.
<br />C. ALL CONTROL PANELS SHALL BE UL LISTED (OR EQUIVALENT APPROVED LABEL).
<br />D. PRESSURE VESSELS SHALL BE PROVIDED IN ACCORDANCE WITH APPLICABLE
<br />PRESSURE VESSEL ORDINANCES.
<br />E ALL MECHANICAL EQUIPMENT SHALL HAVE AN AIC RATING OF 100,000 OR
<br />OTHERWISE SPECIFIED ON ELECTRICAL ONE -LINE DIAGRAMS FAULT CURRENT FOR
<br />EACH PIECE OF EQUIPMENT.
<br />1,10 SUBMITTALS
<br />A. SUBMITTAL INFORMATION SHALL BE PROVIDED AND APPROVED ON ALL MATERIALS
<br />AND EQUIPMENT PRIOR TO ORDERING.
<br />B. PROVIDE INDICATION OF WHICH OPTIONS AND ACCESSORIES ARE TO BE INCLUDED.
<br />C. INCLUDE ALL SCHEDULED INFORMATION FOR EQUIPMENT LISTED IN SCHEDULES ON
<br />THE DRAWINGS.
<br />D. REVIEW WILL BE FOR GENERAL CONFORMANCE ONLY AND SHALL NOT RELIEVE THE
<br />CONTRACTOR FOR ANY DEVIATIONS FROM THE REQUIREMENTS OF THE DOCUMENTS
<br />UNLESS CLEAR WRITTEN REFERENCE IS MADE BY THE CONTRACTOR IN THE
<br />SUBMITTAL TO PROPOSED DEVIATIONS.
<br />1.11 DELIVERY, STORAGE, AND HANDLING
<br />A. FOLLOW MANUFACTURER'S DIRECTIONS IN DELIVERY, STORAGE, PROTECTION AND
<br />INSTALLATION OF EQUIPMENT AND MATERIALS.
<br />B. HANDLE, STORE, AND PROTECT EQUIPMENT AND MATERIALS TO PREVENT DAMAGE
<br />BEFORE AND DURING INSTALLATION IN ACCORDANCE WITH THE MANUFACTURER'S
<br />RECOMMENDATIONS AND AS APPROVED BY THE CONTRACTING OFFICER. REPLACE
<br />DAMAGED OR DEFECTIVE ITEMS.
<br />1.12 OPERATION AND MAINTENANCE MANUALS
<br />A. PROVIDE A CONSOLIDATED OPERATION AND MAINTENANCE MANUAL FOR DIVISIONS
<br />21, 22 AND 23, REFER TO SECTION 230000 FOR REQUIREMENTS.
<br />SECTION 220500 - EAT PLUMBING MATERIALS AND METHODS
<br />PART 1 GENERAL
<br />1.1 SUBMITTALS
<br />A. PRODUCT DATA FOR SPECIFIED MATERIALS.
<br />B. WELDING CERTIFICATES.
<br />1.2 DELIVERY, STORAGE, AND HANDLING
<br />A. DELIVER PIPES AND TUBES WITH FACTORY -APPLIED END CAPS. MAINTAIN END
<br />CAPS THROUGH SHIPPING, STORAGE AND HANDLING TO PREVENT PIPE END DAMAGE
<br />AND TO PREVENT ENTRANCE OF DIRT, DEBRIS, AND MOISTURE.
<br />PART 2 PRODUCTS
<br />2.1 ACCESS DOORS
<br />A. ACCESS DOORS SHALL BE PROVIDED BY DIVISION 22 WHEN SERVING DIVISION 22
<br />SYSTEMS AND EQUIPMENT IN ACCORDANCE WITH THE REQUIREMENTS OF DIVISION
<br />08.
<br />2.2 DIELECTRIC FITTINGS
<br />A. DESCRIPTION: COMBINATION FITTING OF COPPER ALLOY AND FERROUS MATERIALS
<br />WITH THREADED, SOLDER -JOINT, PLAIN OR WELD -NECK END CONNECTIONS THAT
<br />MATCH PIPING SYSTEM MATERIALS.
<br />2.3 ESCUTCHEONS
<br />A. DESCRIPTION: CHROME PLATED STEEL MANUFACTURED WALL AND CEILING
<br />ESCUTCHEONS AND FLOOR PLATES, WITH AN ID TO CLOSELY FIT AROUND PIPE,
<br />TUBE AND INSULATION OF INSULATED PIPING AND AN OD THAT COMPLETELY
<br />COVERS OPENING.
<br />2.4 JOINING MATERIALS
<br />A. REFER TO INDIVIDUAL DIVISION 22 PIPING SECTIONS FOR SPECIAL JOINING
<br />MATERIALS NOT LISTED BELOW. JOINING MATERIAL REQUIREMENTS LISTED IN
<br />INDIVIDUAL SECTIONS SHALL SUPERSEDE THE REQUIREMENTS IN THIS SECTION.
<br />B. SOLDER FILLER METALS: ASTM B 32, LEAD-FREE ALLOYS. INCLUDE
<br />WATER-FLUSHABLE FLUX ACCORDING TO ASTM B 813.
<br />C. BRAZING FILLER METALS: AWS A5.8, BCUP SERIES, COPPER -PHOSPHORUS ALLOYS
<br />FOR GENERAL -DUTY BRAZING, UNLESS OTHERWISE INDICATED; AWS A5.8, BAG1,
<br />SILVER ALLOY FOR REFRIGERANT PIPING, UNLESS OTHERWISE INDICATED.
<br />PART 3 EXECUTION
<br />3.1 GENERAL
<br />A. MECHANICAL DEMOLITION
<br />1. REFER TO DIVISION 1 AND MECHANICAL SECTIONS FOR GENERAL DEMOLITION
<br />REQUIREMENTS AND PROCEDURES.
<br />2. DISCONNECT, DEMOLISH AND REMOVE MECHANICAL SYSTEMS, EQUIPMENT AND
<br />COMPONENTS INDICATED TO BE REMOVED.
<br />3. IF PIPE, INSULATION OR EQUIPMENT TO REMAIN IS DAMAGED IN APPEARANCE
<br />OR IS UNSERVICEABLE, REMOVE DAMAGED OR UNSERVICEABLE PORTIONS AND
<br />REPLACE WITH NEW PRODUCTS OF EQUAL CAPACITY AND QUALITY.
<br />B. PIPING SYSTEMS - COMMON REQUIREMENTS
<br />1. INSTALL PIPING ACCORDING TO THE FOLLOWING REQUIREMENTS AND DIVISION 23
<br />SECTIONS SPECIFYING PIPING SYSTEMS.
<br />2. INSTALL PIPING IN CONCEALED LOCATIONS, UNLESS OTHERWISE INDICATED AND
<br />EXCEPT IN EQUIPMENT ROOMS AND SERVICE AREAS.
<br />3. INSTALL PIPING INDICATED TO BE EXPOSED AND PIPING IN EQUIPMENT ROOMS
<br />AND SERVICE AREAS AT RIGHT ANGLES OR PARALLEL TO BUILDING WALLS.
<br />DIAGONAL RUNS ARE PROHIBITED UNLESS SPECIFICALLY INDICATED OTHERWISE.
<br />4. INSTALL PIPING TO PERMIT VALVE SERVICING.
<br />5. SELECT SYSTEM COMPONENTS WITH PRESSURE RATING EQUAL TO OR GREATER
<br />THAN SYSTEM OPERATING PRESSURE.
<br />6. FIRE -BARRIER PENETRATIONS: MAINTAIN INDICATED FIRE RATING OF WALLS,
<br />PARTITIONS, CEILING, AND FLOORS AT PIPE PENETRATIONS. SEAL PIPE
<br />PENETRATIONS WITH FIRESTOP MATERIALS. REFER TO DIVISION 7 SECTION
<br />"THROUGH -PENETRATION FIRESTOP SYSTEMS" FOR MATERIALS.
<br />3.2 ACCESS DOORS
<br />A. PROVIDE ACCESS DOORS WHERE SPECIALTIES ARE NOT EXPOSED UNLESS
<br />INDICATED TO BE PROVIDED UNDER OTHER DIVISIONS.
<br />3.3 DIELECTRIC FITTINGS
<br />A. PROVIDE DIELECTRIC FITTINGS WHENEVER CONNECTING PIPING OF DISSIMILAR
<br />M ETALS.
<br />3.4 ESCUTCHEONS
<br />A. INSTALL ESCUTCHEONS FOR PENETRATIONS OF WALLS, CEILINGS AND FLOORS IN
<br />FINISHED SPACES.
<br />3.5 PAINTING
<br />A. DAMAGE AND TOUCHUP: REPAIR MARRED AND DAMAGED FACTORY -PAINTED FINISHES
<br />WITH MATERIALS AND PROCEDURES TO MATCH ORIGINAL FACTORY FINISH.
<br />3.6 SLEEVES
<br />A. PROVIDE SLEEVES FOR ABOVE GRADE PIPING PENETRATIONS OF WALLS, ROOFS AND
<br />FLOORS.
<br />SECTION 220523 - PLUMBING GENERAL DUTY VALVES
<br />PART 1 GENERAL
<br />1.1 SUBMITTALS
<br />A. PRODUCT DATA: FOR EACH TYPE OF VALVE INDICATED. INCLUDE BODY, SEATING,
<br />AND TRIM MATERIALS, VALVE DESIGN, PRESSURE AND TEMPERATURE
<br />CLASSIFICATIONS, END CONNECTIONS, ARRANGEMENT, DIMENSIONS AND REQUIRED
<br />CLEARANCES.
<br />PART 2 PRODUCTS
<br />2.1 GENERAL
<br />A. VALVE STANDARDIZATION: VALVES FROM ONE OR MORE MANUFACTURERS MAY BE
<br />USED, HOWEVER VALVES SUPPLIED FOR EACH SPECIFIC VALVE TYPE SHALL BE THE
<br />PRODUCT OF ONE MANUFACTURER.
<br />2.2 GENERAL MATERIALS
<br />A. BODY
<br />1. BRONZE: NO YELLOW BRASS ALLOYS CONTAINING MORE THAT 15 PERCENT
<br />ZINC. FOR USE UP TO 150 PSIG WSP, ASTM B 62 AND OVER 150 PSIG TO
<br />300 PSIG 2124 KPA) WSP, ,ASTM B 61.
<br />B. STEM
<br />1. CAST MANGANESE BRONZE: ASTM B 584.
<br />2. CAST SILICON BRASS: ASTM B 584.
<br />3. STAINLESS STEEL: AS SPECIFIED FOR PARTICULAR TYPE OF VALVE.
<br />C. TRIM
<br />1. AS SPECIFIED FOR PARTICULAR TYPE OF VALVE.
<br />D. VALVE GROOVED ENDS: AWWAC606.
<br />E. THREADED: WITH THREADS ACCORDING TO ASME 81.20.1.
<br />2.3 GENERAL VALVES
<br />A. MANUFACTURERS: ANVIL/GRUVLOK, CRANE, GRINNELL, MILWAUKEE, NIBCO, STOCKHAM,
<br />WALWORTH, WATTS.
<br />B. BALL VALVES: 3 PIECE CAST BRONZE BODY AND TAIL PIECE; SOLID BLOW-OUT
<br />PROOF STEM; TEFLON SEATS; FULL PORT STAINLESS STEEL BALL; TEFLON SEALS;
<br />CORROSION RESISTANT STEEL LEVER HANDLES WITH VINYL GRIPS; BALANCING STOP;
<br />THREADED OR SOLDER CONNECTIONS FOR VALVES 2 INCHES (51 MM) AND
<br />SMALLER.
<br />1. PRESSURE RATINGS:
<br />a. NPS 2 AND SMALLER: 150 PSIG WSP, 600 PSIG CWP.
<br />2. BASIS OF DESIGN: NIBCO T585-70 (THREADED); NIBCO S585-70 (SOLDER);
<br />NIBCO T585-70-NS (INSULATED APPLICATIONS).
<br />C. BUTTERFLY VALVES: 200 PSIG WOG BI-DIRECTIONAL DIFFERENTIAL PRESSURE AT 275
<br />DEG F; VALVE SHALL BE CAPABLE FOR USE AS ISOLATION VALVE AND
<br />RECOMMENDED BY THE MANUFACTURER FOR DEAD END SERVICE AT FULL RATED
<br />PRESSURE WITHOUT THE NEED FOR DOWNSTREAM FLANGES; DUCTILE IRON BODY,
<br />LUGGED TYPE, (LUG FOR EACH BOLT HOLE, DRILLED AND TAPPED FOR CAP
<br />SCREWS), WITH REPLACEABLE REINFORCED RESILIENT EPT (EPDM) SEATS,
<br />ALUMINUM -BRONZE OR NICKEL PLATED DUCTILE IRON DISCS; STAINLESS STEEL
<br />STEMS AND SHALL NOT HAVE EXPOSED STEM -TO -DISC FASTENERS; RAISED NECKS
<br />ABLE TO ACCOMMODATE 2 INCHES (51 MM) OF INSULATION.
<br />PART 3 EXECUTION
<br />3.1 VALVE APPLICATIONS
<br />A. REFER TO PIPING SECTIONS FOR SPECIFIC VALVE APPLICATIONS. IF VALVE
<br />APPLICATIONS ARE NOT INDICATED, USE THE FOLLOWING:
<br />1. SHUTOFF SERVICE: BALL OR BUTTERFLY VALVES.
<br />2. THROTTLING SERVICE: BALL OR BUTTERFLY VALVES.
<br />SECTION 220529 - PLUMBING MANGERS AND SUPPORTS
<br />PART 1 GENERAL
<br />1.1 SUBMITTALS
<br />A. PRODUCT DATA FOR SPECIFIED MATERIALS.
<br />1.2 PERFORMANCE REQUIREMENTS
<br />A. DESIGN SEISMIC -RESTRAINT HANGERS AND SUPPORTS FOR PIPING AND EQUIPMENT
<br />AND OBTAIN APPROVAL FROM AUTHORITIES HAVING JURISDICTION.
<br />PART 2 PRODUCTS
<br />2.1 STEEL PIPE HANGERS AND SUPPORTS
<br />A. MANUFACTURERS: CRANE, ERICO/MICHIGAN HANGER CO., FEE AND MASON, GRINNELL
<br />CORP., TOLCO INC.
<br />B. DESCRIPTION: MSS SP-58, TYPES 1 THROUGH 58, FACTORY -FABRICATED
<br />COMPONENTS.
<br />C. GALVANIZED, METALLIC COATINGS: PRE -GALVANIZED OR HOT DIPPED.
<br />PART 3 EXECUTION
<br />3.1 HANGER AND SUPPORT APPLICATIONS
<br />A. GENERAL
<br />1. COMPLY WITH MSSSP-69 FOR PIPE HANGER SELECTIONS AND APPLICATIONS.
<br />3.2 HANGER AND SUPPORT INSTALLATION
<br />A. STEEL PIPE HANGER INSTALLATION: COMPLY WITH MSSSP-69 AND MSSSP-89.
<br />INSTALL HANGERS, SUPPORTS, CLAMPS AND ATTACHMENTS AS REQUIRED TO
<br />PROPERLY SUPPORT PIPING FROM BUILDING STRUCTURE.
<br />B. THERMAL -HANGER SHIELD INSTALLATION: INSTALL IN PIPE HANGER OR SHIELD FOR
<br />INSULATED PIPING.
<br />3.3 ADJUSTING
<br />A. HANGER ADJUSTMENTS: ADJUST HANGERS TO DISTRIBUTE LOADS EQUALLY ON
<br />ATTACHMENTS AND TO ACHIEVE INDICATED SLOPE OF PIPE.
<br />SECTION 220553 - IDENTIFICATION FOR PLUMBING PIPING AND EQUIPMENT
<br />PART 1 GENERAL
<br />1.1 SUBMITTALS
<br />A. GENERAL
<br />1. PRODUCT DATA FOR SPECIFIED MATERIALS.
<br />1.2 QUALITY ASSURANCE
<br />A. ASME COMPLIANCE: COMPLY WITH ASMEA13.1, "SCHEME FOR THE IDENTIFICATION OF
<br />PIPING SYSTEMS," FOR LETTER SIZE, LENGTH OF COLOR FIELD, COLORS AND
<br />VIEWING ANGLES OF IDENTIFICATION DEVICES FOR PIPING.
<br />PART 2 PRODUCTS
<br />2.1 PIPE MARKERS
<br />A. GENERAL: PREPRINTED, COLOR -CODED, WITH LETTERING INDICATING SERVICE AND
<br />SHOWING DIRECTION OF FLOW.
<br />1. COLORS: COMPLY WITH ASME A13.1, UNLESS OTHERWISE INDICATED.
<br />2. PIPES WITH OD, INCLUDING INSULATION, LESS THAN 6 INCHES: FULL -BAND PIPE
<br />MARKERS EXTENDING 360 DEGREES AROUND PIPE AT EACH LOCATION.
<br />3. ARROWS: INTEGRAL WITH PIPING SYSTEM SERVICE LETTERING TO ACCOMMODATE
<br />BOTH DIRECTIONS OR AS SEPARATE UNIT ON EACH PIPE MARKER TO INDICATE
<br />DIRECTION OF FLOW.
<br />2.2 TAGS
<br />A. STAMPED OR ENGRAVED WITH 1/4-INCH LETTERS FOR PIPING SYSTEM ABBREVIATION
<br />AND 1/2 INCH NUMBERS.
<br />PART 3 EXECUTION
<br />3.1 GENERAL
<br />A. PREPARATION
<br />1. DEGREASE AND CLEAN SURFACES TO RECEIVE ADHESIVE FOR IDENTIFICATION
<br />MATERIALS.
<br />2. PROVIDE IDENTIFYING DEVICES AFTER COMPLETION OF COVERINGS AND PAINTING.
<br />3.2 PIPE MARKERS
<br />A. GENERAL: PREPRINTED, COLOR -CODED, WITH LETTERING INDICATING SERVICE, AND
<br />SHOWING DIRECTION OF FLOW.
<br />PART 1 GENERAL
<br />1.1 QUALITY ASSURANCE
<br />A. GENERAL
<br />1. CONFORM TO MAXIMUM FLAME SPREAD/SMOKE DEVELOPED RATING OF 25/50 IN
<br />ACCORDANCE WITH ASTM E84, NFPA 255, AND UL 723.
<br />1.2 DELIVERY, STORAGE AND HANDLING
<br />A. PACKAGING: INSULATION MATERIAL CONTAINERS SHALL BE MARKED BY
<br />MANUFACTURER WITH APPROPRIATE ASTM STANDARD DESIGNATION, TYPE AND
<br />GRADE AND MAXIMUM USE TEMPERATURE.
<br />PART 2 PRODUCTS
<br />2.1 GENERAL
<br />A. PRODUCTS SHALL NOT CONTAIN ASBESTOS, LEAD, MERCURY, OR MERCURY
<br />COMPOUNDS.
<br />B. FOR INDOOR APPLICATIONS, USE ADHESIVES THAT HAVE A VOC CONTENT OF 50
<br />G/L OR LESS WHEN CALCULATED ACCORDING TO 40 DFR 59, SUBPART D (EPA
<br />METHOD 24).
<br />2.2 PIPE INSULATION
<br />A. GLASS FIBER
<br />1. MANUFACTURER
<br />a. KNAUF, b. OWENS CORNING, c. SCHULLER, MICRO-LOK, AP-T PLUS.
<br />2. INSULATION: ASTM C547; RIGID MOLDED; NONCOMBUSTIBLE; 'K' ('KSI') VALUE:
<br />ASTM C177, 0.24 AT 75 DEG F; 850 DEG F MAXIMUM SERVICE TEMPERATURE;
<br />0.2 PERCENT MAXIMUM MOISTURE ABSORPTION BY VOLUME.
<br />3. VAPOR BARRIER JACKET: WHITE KRAFT PAPER WITH GLASS FIBER YARN; BONDED
<br />TO ALUMINIZED FILM WITH PRESSURE SENSITIVE TAPE LAP SEALING SYSTEM;
<br />MOISTURE VAPOR TRANSMISSION: ASTM E96; 0.02 PERM -INCHES.
<br />4. ADHESIVES: COMPLY WITH MIL-A-3316C, CLASS 2, GRADE A.
<br />2.3 JACKETS AND FITTING COVERS
<br />A. PVC PLASTIC JACKET AND FITTING COVERS (INTERIOR APPLICATIONS):
<br />1. MANUFACTURERS
<br />a. ZESTON 2000
<br />2. JACKETS AND FITTING COVERS: ASTM D1784; ONE PIECE MOLDED TYPE FITTING
<br />COVERS AND SHEET MATERIAL; OFF-WHITE COLOR; MINIMUM SERVICE
<br />TEMPERATURE: 0 'F -18 'C; MAXIMUM SERVICE TEMPERATURE: 450 7 230' C;
<br />THICKNESS: 20 MIL 0.50 MM.
<br />3. JACKETS AND FITTING COVERS (VAPOR BARRIER JACKETS): ASTM D1784; ONE
<br />PIECE MOLDED TYPE FITTING COVERS AND SHEET MATERIAL; OFF-WHITE COLOR;
<br />MINIMUM SERVICE TEMPERATURE: 0 °F -18 'C; MAXIMUM SERVICE TEMPERATURE:
<br />450 °F 230 'C; MOISTURE VAPOR TRANSMISSION - ASTM E96 - 0.002
<br />PERM -INCHES 0.0029NG/(SXMXPA); THICKNESS: 20 MIL 0.50 MM.
<br />PART 3 EXECUTION
<br />3.1 GENERAL
<br />A. PREPARATION
<br />1. SURFACE PREPARATION: CLEAN AND DRY SURFACES TO RECEIVE INSULATION.
<br />REMOVE MATERIALS THAT WILL ADVERSELY AFFECT INSULATION APPLICATION.
<br />B. INSTALLATION
<br />1. INSTALL INSULATION MATERIALS, ACCESSORIES, AND FINISHES WITH SMOOTH,
<br />STRAIGHT AND EVEN SURFACES; FREE OF VOIDS THROUGHOUT THE LENGTH OF
<br />EQUIPMENT, DUCTS AND FITTINGS AND PIPING INCLUDING FITTINGS, VALVES AND
<br />SPECIALTIES.
<br />2. INSTALL INSULATION MATERIALS, FORMS, VAPOR BARRIERS OR RETARDERS,
<br />JACKETS AND THICKNESS REQUIRED FOR EACH ITEM OF EQUIPMENT, DUCT
<br />SYSTEM AND PIPE SYSTEM AS SPECIFIED.
<br />3.2 PIPING INSULATION
<br />A. GENERAL
<br />1. INSULATION INSTALLATION ON STRAIGHT PIPES AND TUBES:
<br />a. SECURE EACH LAYER OF INSULATION TO PIPE WITH WIRE OR BANDS AND
<br />TIGHTEN BANDS WITHOUT DEFORMING INSULATION MATERIALS.
<br />2. INSULATION INSTALLATION ON PIPE FITTINGS AND ELBOWS:
<br />a. INSTALL PREFORMED SECTIONS OF SAME MATERIAL AS STRAIGHT SEGMENTS OF
<br />PIPE INSULATION WHEN AVAILABLE. SECURE ACCORDING TO MANUFACTURER'S
<br />WRITTEN INSTRUCTIONS.
<br />3.3 JACKETS AND FITTING COVERS
<br />A. PROVIDE PVC JACKETS FOR INTERIOR APPLICATIONS, AND ALUMINUM JACKETS FOR
<br />EXTERIOR APPLICATIONS.
<br />PART 1 GENERAL
<br />1.1 SUBMITTALS
<br />A. GENERAL
<br />1. EQUIPMENT PRODUCT DATA: PROVIDE COMPONENT SIZES, ROUGH -IN
<br />REQUIREMENTS, SERVICE SIZES AND FINISHES.
<br />B. PIPE PRODUCT DATA
<br />1. PROVIDE DATA ON PIPE MATERIALS, PIPE FITTINGS, VALVES AND ACCESSORIES.
<br />1.2 OPERATION AND MAINTENANCE MATERIALS
<br />A. GENERAL
<br />1. INCLUDE CERTIFICATES FOR ALL REQUIRED PIPING SYSTEM TESTS AND
<br />INSPECTIONS.
<br />1.3 DELIVERY, STORAGE AND HANDLING
<br />A. ACCEPT VALVES ON SITE IN SHIPPING CONTAINERS WITH LABELING IN PLACE.
<br />INSPECT FOR DAMAGE.
<br />PART 2 PRODUCTS
<br />2.1 PIPING
<br />A. WATER PIPING, ABOVE GRADE
<br />1. COPPER TUBING: ASTM B88, TYPE L, HARD DRAWN; ASME B16.22
<br />WROUGHT COPPER AND BRONZE FITTINGS; ASTM B32 FITTINGS, SOLDER,
<br />GRADE 95TA.
<br />2.2 FLANGES, UNIONS, AND COUPLINGS
<br />A. PIPE SIZE 2 INCHES AND UNDER
<br />1. COPPER TUBE AND PIPE: CLASS 150 BRONZE UNIONS WITH SOLDERED
<br />JOINTS.
<br />2.3 RO AND DI WATER SYSTEMS
<br />A. FOR RO AND DI WATER SYSTEMS, US POLYPROPYLENE (PP) TUBING WITH S
<br />SOCKET WELDS.
<br />B. BALL VALVES MADE FROM ASTM D4101 RESIN.
<br />1. BALL VALVES, NPS2 "AND SMALLER; MSS SP-122, UNION TYPE WITH
<br />SOCKET ENDS AND PRESSURE RATING OF NOT LESS THAN 150 PSIG AT
<br />73 DEGREES F.
<br />PART 3 EXECUTION
<br />3.1 GENERAL
<br />A. INSTALL DOMESTIC WATER PIPING LEVEL AND PLUMB.
<br />3.2 PIPING
<br />A. WATER SERVICE
<br />1. CONNECT DOMESTIC WATER PIPING TO EXTERIOR WATER -SERVICE PIPING.
<br />USE DIELECTRIC FITTING TO JOIN DISSIMILAR PIPING MATERIALS.
<br />GENERAL PIPING VALVE APPLICATIONS
<br />1. PROVIDE SHUTOFF VALVE CLOSE TO WATER MAIN ON EACH BRANCH AND
<br />RISER SERVING PLUMBING FIXTURES OR EQUIPMENT, ON EACH WATER
<br />SUPPLY TO EQUIPMENT AND ON EACH WATER SUPPLY TO PLUMBING
<br />FIXTURES THAT DO NOT HAVE SUPPLY STOPS.
<br />3.3 TRAP PRIMERS
<br />A. PROVIDE TRAP PRIMERS FOR ALL FLOOR DRAINS, AND WHERE INDICATED ON
<br />DRAWINGS.
<br />3.4 WATER HAMMER ARRESTERS
<br />A. INSTALL IN WATER PIPING ACCORDING TO PDI-WH 2O1.
<br />B. AT A MINIMUM, PROVIDE IN ALL BRANCH LINES SERVING FLUSH VALVE
<br />WATER CLOSETS, PRESSURE -ASSISTED FLUSH TANK WATER CLOSETS, FLUSH
<br />VALVE URINALS, LAVATORIES AND SHOWERS. REFER TO PDI-WH 201 FOR
<br />ADDITIONAL LOCATION REQUIREMENTS.
<br />3.5 HANGER AND SUPPORT INSTALLATION
<br />A. SUPPLEMENTAL APPLICATION INFORMATION
<br />1, VERTICAL PIPING:
<br />a. MSS TYPE 8 OR TYPE 42 CLAMPS.
<br />b. MSS TYPE 52, SPRING HANGERS, AT BASE.
<br />2. HORIZONTAL PIPING:
<br />a. 100 FEET AND SHORTER: HANGERS FOR STATIONARY PIPING MAY BE USED.
<br />b. LONGER THAN 100 FEET: HANGERS FOR SUPPORT OF PIPING SUBJECT TO
<br />LONGITUDINAL MOVEMENT DUE TO EXPANSION AND CONTRACTION SHALL BE
<br />USED.
<br />3.6 CLEANING
<br />A. PURGE NEW PIPING AND PARTS OF EXISTING DOMESTIC WATER PIPING THAT
<br />HAVE BEEN ALTERED, EXTENDED OR REPAIRED BEFORE USING.
<br />B. USE PURGING AND DISINFECTING PROCEDURES PRESCRIBED BY AUTHORITIES
<br />HAVING JURISDICTION OR IF METHODS ARE NOT PRESCRIBED, PROCEDURES
<br />DESCRIBED IN EITHER AWWAC651 OR AWWA C652.
<br />SECTION 221300 - SANITARY WASTE AND VENT PIPING SYSTEMS
<br />PART 1 GENERAL
<br />1.1 SUBMITTALS
<br />A. GENERAL
<br />1. EQUIPMENT PRODUCT DATA: PROVIDE COMPONENT SIZES,
<br />ROUGH -IN -REQUIREMENTS, SERVICE SIZES AND FINISHES.
<br />1.2 OPERATION AND MAINTENANCE MATERIALS
<br />A. GENERAL
<br />1. INCLUDE CERTIFICATES FOR ALL REQUIRED PIPING SYSTEM TESTS AND
<br />INSPECTIONS.
<br />1.3 DELIVERY, STORAGE AND HANDLING
<br />A. PROVIDE TEMPORARY END CAPS AND CLOSURES ON PIPING AND FITTINGS.
<br />MAINTAIN IN PLACE UNTIL INSTALLATION.
<br />PART 2 PRODUCTS
<br />2.1 PIPING
<br />A. WASTE AND VENT PIPING (UNPRESSURLZED), ABOVE GRADE
<br />1. CAST IRON (HUBLESS): ASTM A 888/CLSPI 301 SERVICE WEIGHT.
<br />a. FITTINGS: CAST IRON TO MATCH PIPING.
<br />b. JOINTS: ASTM C 1277 HEAVY DUTY SHIELDED COUPLINGS WITH STAINLESS
<br />STEEL SHIELD, BANDS AND TIGHTENING DEVICES; ASTM C 564 RUBBER
<br />SLEEVE.
<br />2.2 CLEANOUTS
<br />A. MANUFACTURERS: J.R. SMITH, JOSAM, WADE, ZURN.
<br />B. GENERAL: BODY MATERIAL AS REQUIRED TO MATCH CONNECTED PIPING;
<br />FULL SIZE TO 4 INCHES; NOT LESS THAN 4 INCHES
<br />,.... LARGER
<br />BRONZEEXTENSIONS WITH FLUSH FRAMES AND BRASS REMOVABLE COVER PLATE
<br />C. FLOOR CLEANOUTS: COATED CAST IRON BODY; SCORIATED HEAVY DUTY
<br />NICKEL re FULLY ADJUSTABLE j SECURED TO BODY;
<br />SEALED IRON CLOSURE PLUG.
<br />v
<br />2727 sakes we.
<br />sull:e 10i2
<br />Ever +i .)(9_'J1
<br />RE V �Sa JC)ME-',
<br />(I s-tanteec
<br />4100 194th Street SW Suite 400
<br />Lynnwood Washington 98036-4613
<br />(206( 667-0555
<br />Copyright Reserved
<br />The Contractor shall verify and be responsible for all dimensions. DO
<br />NOT scale the drawing -any errors or omissions shall be reported to
<br />Stantec without delay.
<br />The Copyrights to all designs and drawings are the property of
<br />Stantec. Reproduction or use for any purpose other than that
<br />authorized by Stantec is forbidden.
<br />®y WASkly
<br />C
<br />LU-,
<br />C
<br />0
<br />4-
<br />4-
<br />-,
<br />w
<br />4M
<br />�v
<br />JOB. 1\10. 19-1, 1 7
<br />DR�,V,N BY � YB M
<br />C FCKED BY FJ
<br />fly' E Ire lI R C,;III, T I 0 �rkl S
<br />
|